fix(control): after a restart the battery credits the car the meter shows - #1926

Merged
frahlg merged 26 commits into
car-before-battery-chargefrom
ev-base-after-restart
Oct 28, 2026
Merged

frahlg merged 26 commits into
car-before-battery-chargefrom
ev-base-after-restart

Conversation

@frahlg

@frahlg frahlg commented Oct 27, 2026 •

Copy link
Copy Markdown
Member

Problem

Item C10 in the 27 Oct random-rig triage (section 3, item 11), seed 207532.

After Core restarted, the meter took about 6 s to return. In that time FTW sent 0 A orders to the charger. The charger takes 40 s to apply an order, so the car kept drawing about 8.2 kW from before the restart. When the meter returned, FTW ordered 6,210 W (9 A).

The charger's offer log held only those 0 A orders, so the battery side (clampEVBatteryHeadroom, through evShownW) took 0 W as the EV draw the meter shows. It counted the 6,210 W order as a 9 A rise to come and held the battery in discharge for room the car did not need. With battery_covers_ev off, the battery stayed at -4,285 W, then -1,595 W and -1,285 W for about 30 s, at 5.5-5.7 % SoC. That fed the seed's floor violation at 456.7 s.

Change

evFoundDrawW (in ev_fuse_budget.go) lets the battery side count a charger's measured draw as part of the meter reading.

When. Only while the charger has no order from this run that has surely landed: from the first offer Core logs for it with no fuse limit set, until that offer is older than the charger's settle time. That happens at Core's start, and at a plug-in once no other managed charger was plugged (the limit resets when the pool empties). A plug-in beside another plugged car does not open the window.

Which sample. The charger's telemetry is live and its last poll succeeded (Store.OnlineLowerW), and its current sample passes qualifiedFuseObservation. While the window is open, noteDraw (called from recordEVOffers) keeps the charger's samples for up to 20 s. Since the final review, Core judges a sample by when it first arrived on Core's clock (evDraw.got), not by the charger's stamp. A draw counts only when Core saw one sample arrive between evMeterDelay (1 s) and 1 s plus one control interval before the site reading (arrivedBy). A sample already there when noteDraw began to watch the charger (watchFrom) never counts: Core does not know when it arrived. The draw is the lowest of that sample and every sample since, up to the current one. So a rise sampled after the reading never counts, whatever the charger's clock, and a drop since the sample always does.

How much. Core does not know the offer in force in this window: one from before the restart (perhaps under an older max_charge_w), or the charger's own default. A car drawing less than that offer may still rise toward it before Core's order lands. So each charger counts:

  • its draw, as above, each sample taken at the lowest of the sample, raw and smoothed;
  • less the rise the car may still make past FTW's latest offer, up to a cap: min(latest, draw - max(0, cap - latest)). The cap is the larger of the loadpoint's max_charge_w and the site fuse's rating (siteFuseMaxW, In x V x phases);
  • less the part of the latest offer that evShownW already counts.

A charger with no max_charge_w counts nothing. The credit is above zero only when the draw plus the latest offer exceeds the cap. On the seed (16 A fuse, max_charge_w 11,040 W) that changes nothing; on a site whose fuse allows more than the car's draw plus Core's latest offer, the credit is zero, which is the base behaviour. In total the credit never exceeds the consumption the site meter shows less the offers already shown. siteConsumptionW takes the grid reading less each live battery, PV and V2X reading at the higher of raw and smoothed (Store.SumOnlineHigherW).

clampEVBatteryHeadroom adds the credit to evShownW. The car's own limit (evMeterLimit, evInMeterW, EVFuseBudget) never reads it, so nothing here lets the car rise.

The charger and output reads go through two new health-gated accessors in go/internal/telemetry (OnlineLowerW, SumOnlineHigherW), so the PR adds no direct telemetry reads (check-telemetry-reads.sh: 133, none added).

Review follow-ups

First review (fixed in e53aa4b): the charger reading counted with no freshness check, and the consumption bound used smoothed outputs. Both fixed as described above.

Second review (fixed in 6b10baa):

  1. Blocking: the credit treated the car's draw as a ceiling. On the PR's fixture, a car at 8.2 kW under a 16 A offer in force put 19.00 A on each phase once it rose; on the plant, L2 peaked at 19.30 A, over 1.2 x In. The credit now keeps room for that rise, as above. The reviewer suggested min(latest, draw) - max(0, cap - draw). I used min(latest, draw - max(0, cap - latest)): the car's peak before the order lands is the cap and after it the latest offer, so the reviewer's form counts latest - draw twice when the car draws below the latest offer. Both give 3,450 W for the seed.
    For the cap I used max_charge_w, not the charger's reported max_a. Drivers mean different things by max_a (offer in force, a hardware register, a config value), and Core reads no charger limit today. (The third review showed max_charge_w alone is not the safe side; see below.)
  2. OCPP sample cadence: partial fix, now stated and tested. A sample counts only on the ticks just after it, and the battery holds its discharge between them. On the seed's plant with 10 s MeterValues the battery still reaches its level 2 s later than with 1 s samples, before the 9 A order counts as shown. A charger sampling every 30 s or more gets no credit before then, which is the base behaviour. Widening the window would let a car that stopped since the sample count as drawing, so I left it.
  3. Nits. Tests now cover the raw and smoothed guards, and the doc comment states the window's scope as above.

Third review (fixed in caacc8d):

  1. Blocking: a charger sample newer than the site reading counted. The window allowed a sample up to one control interval after the meter. With a 3 s meter, a car under a 16 A offer in force rose between meter samples; the charger read 11,040 W while the meter still showed 6,900 W, the credit took the full 6,210 W, and L2 sat at 19.30 A for 2 s. A sample now counts only when measured at or before the site reading (p.At.After(meterAt) skips it). On the reviewer's sweep (meter 1/2/3/5/10 s, L2 9-13 A, rise at 9-20 s) no case now reaches 1.2 x In; the worst peak is 17.41 A. The 72 cases that fail a sim check (3, 5 and 10 s meters, peak 16.41 or 17.41 A) fail the same way with the credit removed, so they come from other dispatch code and belong in a separate issue.
    Cost: real drivers poll on their own schedules, so on ticks where the charger's last sample came after the meter's, the credit does not apply and the battery keeps base behaviour on that tick.
  2. Blocking: max_charge_w is not a bound on the offer in force. After a restart that lowers max_charge_w, the charger still runs the earlier offer; a charger's own default may also be higher. Head went to 0 W (19.00 A per phase on the unit fixture, 19.30 A on the plant) where base kept the discharge. The cap is now the larger of max_charge_w and the site fuse's rating. Core's earlier offers never exceed the fuse line, and a charger whose default exceeds the main fuse can overload it with or without this PR. I did not use the saved offer from controller_offer_restore.go: it exists only for the same session within 10 minutes, and it says nothing of a charger's default at plug-in.

Fourth review (fixed in 551febd):

  1. Blocking: the charger's clock. The third-round check compared the charger's sample time (for OCPP, the MeterValues timestamp from the charger's own clock, often cut to the whole second) with the time the site reading arrived on Core's clock. A charger clock 1 s or more behind Core's stamped a rise sampled after the reading as before it, and L2 reached 19.30 A again. The same gap opens when the meter's own delay from measurement to arrival is longer than the charger's. I took the reviewer's suggested shape: a sample must be stamped evClockAllowance (5 s) before the reading arrived, and the draw is the lowest of all samples from then until now. A 1 s margin alone was not enough, as the reviewer showed (2 and 3 s lags still reached 19.30 A).
    I keep the samples in chargerOffers (noteDraw), not in the store's control observations, because the store stamps them with the wall clock and drops points more than 10 s old. The plant sim runs on its own clock, so the store's points never reach it, and the sim tests could not cover the fix.
    Covered: a charger clock behind Core's plus the meter's delay, together less than about 5 s. On the third review's plant case, lags of 1-6 s now stay at 16.41 A (the no-credit value), and an 8 s lag still reaches 19.30 A. A charger clock ahead of Core's gets no credit at all, because ControlPowerObservation rejects a sample stamped after its arrival.
    Cost: the credit starts about 5 s later. A charger sampling every 10 s counts on the ticks 5-7 s after each sample, not 0-2 s. The seed's tests still pass in both forms.
  2. Should-fix: no test covered the max_charge_w half of the rise cap. Added TestEVFoundDrawWMaxChargeAboveFuse (the reviewer's case: a 22 kW charger on 3 x 25 A, draw 14,000 W, latest offer 11,000 W, credit 2,920 W). With capW := s.siteFuseMaxW() it returns 7,750 W and fails.

Final review fix (040ebb10)

Blocking: the 5 s evClockAllowance let the credit count a sample taken 5-7 s before the reading. A car that stopped after it (a fast charger applying the stale-meter 0 A, or the car pausing) still counted, and L2 reached 21.00 A when the car resumed (no credit: 18.10 A). The credit now uses Core's receipt time, as the reviewer proposed, with a 1 s evMeterDelay. The reviewer's receipt time alone did not fix the case on the plant: Core began to watch the charger at 7 s, so a sample stamped 2 s first showed up then and looked fresh. A sample already there when Core began to watch now never counts.

  • New TestSiteSimRestartOldSampleOfACarThatStopped (the reviewer's case 1): 21.00 A before, 18.10 A after.
  • TestEVFoundDrawWBounds: the "stamped less than evClockAllowance" case is now "a sample that arrived with the site reading, however early its stamp" (no credit). Fixtures now set a receipt 1 s before the reading.
  • Probes, not committed: the reviewer's case 2 (40 s charger, car pausing 5-11 s, 10 sample phases) peaks at 19.00 A at most, the no-credit peak. Clock lags of 5, 8 and 15 s in the ChargerClockBehind shape peak at 16.41 A.
  • go test -race ./internal/control/ ./cmd/ftw/, go test ./internal/control/ ./internal/loadpoint/ (field matrix included) and the hygiene scripts pass.

The sections below describe earlier rounds; evClockAllowance no longer exists.

Tests

In go/internal/control/ev_base_after_restart_test.go:

  • TestEVBaseAfterRestartCreditsMeasuredDraw: seed 207532's numbers. Before the PR the battery was held at -3,599 W. Now it keeps only the discharge the car's rise to 16 A needs on L2 (-207 W).

  • TestEVBaseAfterRestartCarBelowOfferInForce (new, the second review's case): a car at 8.2 kW under a 16 A offer in force. On the previous head the battery went to 0 W, 19.00 A per phase after the rise. Now each phase stays at 16 A.

  • TestEVBaseAfterRestartCreditStaysInsideTheMeter: the charger claims 8.2 kW but the meter shows 680 W of consumption. The credit stops at 680 W.

  • TestEVBaseAfterRestartNeedsACurrentChargerSample: a failed poll, a sample 10 s older than the site reading, and a site reading 10 s older than the sample give no credit.

  • TestEVBaseAfterRestartConsumptionReadsCurrentOutput and TestSiteConsumptionWTakesTheSmallerOutput (new): lagging smoothed values cannot raise the consumption bound, and nor can a reading ahead of the meter.

  • TestEVFoundDrawWBounds: cases for the rise to the cap, no max_charge_w, and the draw at the lowest of the sample, raw and smoothed. New in the third round: max_charge_w below the fuse (cap stays at the fuse), and a charger sample measured after the site reading (no credit). New in the fourth round: a sample stamped less than evClockAllowance before the reading (no credit); a rise stamped 1 s before the reading by a charger clock behind Core's (the earlier draw counts: 2,070 W, not 6,210 W); a lower sample since the reading (it counts); and only a sample older than one control interval before the reading, with a later higher one (no credit). The fixture now stamps the charger's sample evClockAllowance before the site reading (chargerData, setChargerSample). Cases that test the other bounds set both max_charge_w and the fuse to 6,210 W (setRiseCapW).

  • TestEVFoundDrawWMaxChargeAboveFuse (new, fourth review): the rise reserve runs to max_charge_w when that is above the fuse's rating.

  • TestEVFoundDrawWLeavesOutShownOffers: offers already shown come off the consumption bound.

  • TestSiteSimRestartEndsDischargeForACarAlreadyDrawing: the seed's shape on the plant sim. The battery reaches its level 4 s after the meter returns, and the sim's fuse checks pass for 2 minutes.

  • TestSiteSimRestartTenSecondSamples (new): the same with OCPP-style 10 s samples (new evEvery in the sim harness). It fails with 30 s samples.

  • TestSiteSimRestartCarRisesUnderOfferInForce (new, the second review's plant case): the car lifts its own limit 14 s in under a 16 A offer in force. No phase reaches 1.2 x In and the sim's heat check passes. Previous head: 19.30 A. L2 still reaches 16.41 A for about 3 s, the same as the base branch. The credit does not cause it: the battery's first step after the restart goes to -2,000 W even with 30 s or 60 s samples, which get no credit.

  • TestSiteSimRestartCarRisesBetweenMeterSamples (new, third review): a 3 s meter, the car at 10 A under a 16 A offer in force lifts its limit 11 s in. Previous head: 19.30 A. Now under 1.2 x In and the sim's checks pass.

  • TestSiteSimRestartChargerClockBehind (new, fourth review): the third review's case with the charger's clock 1, 2 and 3 s behind Core's (new evClockLag in the sim harness). Previous head: 19.30 A in each. Now under 1.2 x In and the sim's checks pass.

  • TestEVBaseAfterRestartMaxChargeLoweredAtRestart (new, third review): max_charge_w 7,360 W, car 7 kW, 16 A in force. Previous head: battery 0 W, 19.00 A per phase after the rise. Now 16.00 A.

  • TestSiteSimRestartMaxChargeLoweredAtRestart (new, third review): the plant form, max_charge_w 8,280 W, car lifts its limit 14 s in. Previous head: 19.30 A. Now 16.41 A, the same as with no credit; under 1.2 x In and the sim's checks pass.

In go/internal/telemetry/telemetry_test.go: TestOnlineLowerWNeedsALivePoll, TestSumOnlineHigherWSumsTheNamedTypes.

Fail before, pass after: with only the old credit formula restored, CreditsMeasuredDraw, CarBelowOfferInForce, three Bounds cases and CarRisesUnderOfferInForce fail. Mutation runs (each alone): raw only or smoothed only in either accessor, no failed-poll check, no sample in the draw, no raw/smoothed in the draw, no rise reserve, no max_charge_w gate, 20 s skew, no - shownW, no consumption bound. Each fails at least one test.

Third round, each fix reverted alone: the old one-interval-after window fails CarRisesBetweenMeterSamples (19.30 A) and the new Bounds case; max_charge_w as the cap fails MaxChargeLoweredAtRestart in both forms (19.00 A, 19.30 A) and the new Bounds case. With no credit at all, CreditsMeasuredDraw, EndsDischargeForACarAlreadyDrawing, TenSecondSamples and four more still fail, so the seed's fix holds.

Fourth round, fail before: with the previous ev_fuse_budget.go (and the allowance set to 0 in the fixture), TestSiteSimRestartChargerClockBehind fails at 19.30 A for each lag, and the clock-behind Bounds case gives 6,210 W instead of 2,070 W. Mutations of the new code (each alone): no lowest over the kept samples, no "before" from the kept samples, allowance 0 or 1 s, no freshness check on the current sample, no lower bound on kept samples, no "before" check at all, keeping only the latest sample, and the fuse-only cap. Each fails at least one test.
Sweeps (the reviewer's harness, run locally, not committed): the broad closed-loop sweep (2,304 cases) fails the sim in the same 16 cases with and without the credit; none reaches 1.2 x In. The credit releases the battery earlier in 376 cases (384 on the previous head), and 8 cases peak at exactly 16.00 A against 15.41 A with no credit, with no time over In. The third review's sweep with a 1 s clock lag (384 cases): none at 1.2 x In, worst 17.41 A, the same as with no credit (previous head: 6 cases, worst 20.30 A).

  • go test -race ./internal/control/... ./internal/telemetry/... ./internal/loadpoint/...: ok (at 551febd)
  • make verify: clean at 551febd (Docker steps skipped)
  • check-telemetry-reads.sh against origin/master and the base: none added. check-no-planning-docs.sh: clean.
  • TestSite/siterig not run; the runner does that.

Risk

Low. The change only makes the battery reserve less room for an EV rise in the restart window, by a measured draw that Core saw arrive at least 1 s before the site reading (and no higher than any sample since), less the rise the car may still make to the larger of max_charge_w and the fuse rating, inside the consumption the meter shows.

Left open:

  • A sample that was already there when Core began to watch the charger gives no credit, so a charger that samples every 10 s or more gets its first credit only after its next sample.
  • A driver that stamps a lagged value as fresh still passes the sample check. The consumption bound limits that, but cannot tell house load from car load.
  • A charger whose own default exceeds the site fuse's rating can rise past the reserve. It can overload the fuse without this PR too.
  • The fuse cap leaves no credit on sites whose fuse allows more than the car's draw plus Core's latest offer. The seed's case is fixed only where that sum exceeds the fuse rating. Trusting max_charge_w as the cap would give more credit but reopens the second blocking finding; that trade is the owner's call.
  • After evSettle (20 s for a charger that declares no response time), evShownW counts the order as shown, though a 40 s charger has not applied it. That is base behaviour, not this PR's.

Stack and merge order

Stacked on #1925 (car-before-battery-charge), merged up to date into this branch (3623603, in b152e84). Full order: #1910 → #1891 → #1913 → #1923 → #1924 → #1925 → this PR.

Other open PRs on these files: #1789, #1782, #1763 and #1792 (ev_battery_headroom.go, ev_fuse_budget.go), and #1921 (telemetry/store.go, in a different hunk). #1910, #1923 and #1914 also touch sitesim_test.go in other hunks.

🤖 Generated with Claude Code

frahlg and others added 3 commits October 27, 2026 19:05
Core now works to the fuse rating unless a site sets a margin. Every
explicit safety_margin_a is kept. A stored value of exactly 0.5 A, the
old default, adds one load-time notice and changes nothing.

The peak-limit error names the margin only when it is above 0, and the
settings field shows 0 with help that says the margin is opt-in.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
The changeset said FTW works to the fuse rating unless a site sets a
margin. On this PR's base every per-phase line still sits 1 A under the
rating; that holds only once #1910 and the step-4 amendment of #1891
land. The changeset now names what this PR changes: the default, and
the whole-site import and export limits.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
…hows

After a restart, the 0 A orders FTW sent while the meter was stale counted
as the EV base the meter shows. With the car still drawing 8.2 kW from
before, a new 6.2 kW order then counted as a 9 A rise to come, and the
battery was held in discharge for the car (seed 207532).

Until a charger's first order of this run can have landed, the battery
side now counts the charger's live measured draw as in the reading, never
above the latest order and never above the consumption the site meter
shows. The car's own limit does not read it.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
@chatgpt-codex-connector

chatgpt-codex-connector Bot commented Oct 27, 2026 •

Copy link
Copy Markdown

Codex Review Summary

This comment shows the latest Codex review activity on this pull request.

Review Status Commit Review trigger
📝 Code Review ✅ Completed 2026-10-27T23:09:21.172912Z ef7ca51 PR opened
ℹ️ About Codex in GitHub

Your team has set up Codex to review pull requests in this repo. Reviews are triggered when you

  • Open a pull request for review
  • Mark a draft as ready
  • Comment "@codex review" or "@codex security review".

Codex reacts with 👀 while any review is running, comments if it has suggestions, and reacts with 👍 once all reviews finish with no findings.

@chatgpt-codex-connector chatgpt-codex-connector Bot left a comment

Copy link
Copy Markdown

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

💡 Codex Review

Here are some automated review suggestions for this pull request.

Reviewed commit: ef7ca51638

ℹ️ About Codex in GitHub

Your team has set up Codex to review pull requests in this repo. Reviews are triggered when you

  • Open a pull request for review
  • Mark a draft as ready
  • Comment "@codex review".

If Codex has suggestions, it will comment; otherwise it will react with 👍.

Codex can also answer questions or update the PR. Try commenting "@codex address that feedback".

Comment thread go/internal/control/ev_fuse_budget.go Outdated
Comment on lines +394 to +398
r := store.Get(c.driver, telemetry.DerEV)
if r == nil || !store.DriverHealth(c.driver).TelemetryLive() {
continue
}
drawW := math.Min(r.RawW, r.SmoothedW)

Copy link
Copy Markdown

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

P2 Badge Align the EV draw credit with the site-meter observation

During the restart window, a charger reading can already show a newly applied rise while the latest site-meter reading still predates it. TelemetryLive() does not establish that the draw was present in that meter observation, and the consumption bound can be satisfied by ordinary household load. For example, on a balanced 16 A site, a meter showing 1 kW while the battery discharges 5 kW gives a 6 kW consumption bound. If the charger subsequently reports a new 6.21 kW draw, this credits 6 kW and lets clampEVBatteryHeadroom end the discharge, although actual import then becomes 12.21 kW, above the 11.04 kW fuse limit. The earlier fitBatteryRisesToFuse does not prevent this because ending discharge at a zero target contributes no positive riseW. Only credit draw established to be included in the meter observation, and add a regression case where the charger reports a rise before the next meter poll.

Useful? React with 👍 / 👎.

frahlg and others added 4 commits October 28, 2026 00:33
Review of #1926 found two ways the restart credit let the battery end a
discharge into room the car's pending rise still needs:

- The charger reading counted with no check that it was current. A held
  reading after a failed poll, or a sample older than the site reading,
  could show a car that a fast charger had already stopped. The draw now
  counts only when the last poll succeeded and the charger measured it
  within one control interval of the site reading.
- The consumption bound subtracted the smoothed battery, PV and V2X
  values, which lag an output that just fell. It now takes the higher of
  raw and smoothed for each, so the bound stays at or below what the
  meter shows.

New tests pin both, plus the shown-offer subtractions and a window that
outlasts evSettle.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Rebases #1914 onto the top of the fuse stack. The one conflict was the
margin in the site sim's boot; it now reads simFuseSafetyA.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
simFuseSafetyA follows the config default, now 0. fitScenario takes the
room under the line and sets the house from simFuseSafetyA, so its exact
fit stays twelve whole steps at any margin. "charger's own load
balancer" passes at margin 0, so its known line goes.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
With the stack under it, the default moves the car's and the battery's
per-phase line as well as the site totals. 0.5 A stops being the
default, so #1910's changeset no longer calls it that.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
frahlg and others added 3 commits October 28, 2026 01:20
At the 0 A default the scenario passes only because the charger's own
balancer sits at 25 A, the rating and so the line. The bug is still in
Core: a cut comes off an offer the car does not draw. Two known variants
keep it tracked and turn red once it is fixed: the stored 0.5 A margin
(over 24.5 A for more than 11 s) and a balancer at 25.5 A at margin 0
(over 25 A for more than 11 s).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
frahlg and others added 15 commits October 28, 2026 06:07
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
After a restart Core does not know the offer in force on the charger, so
a car drawing below it may still rise before Core's order lands. The
credit now counts only the draw less that possible rise past the latest
offer, with the rise measured to the loadpoint's max_charge_w; a charger
with no max_charge_w gets no credit.

The charger and output reads move into health-gated telemetry accessors
(OnlineLowerW, SumOnlineHigherW). Tests cover the raw and smoothed
guards, a 10 s OCPP sample cadence on the plant, and the review's car
rising under a 16 A offer in force.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
The battery side's restart credit (evFoundDrawW) had two gaps.

A charger sample measured after the site reading counted as part of
it. A car that rose in that gap was credited for draw the meter did
not show yet, and the battery ended its discharge into room the rise
had taken. With a 3 s meter, L2 reached 19.30 A. A sample now counts
only when measured at or before the site reading.

The rise reserve took max_charge_w as the most the unknown offer in
force can be. A charger still on an offer from before a restart that
lowered max_charge_w, or on its own higher default, could rise past
it: 19.00 A per phase on the unit fixture, 19.30 A on the plant. The
reserve now runs to the larger of max_charge_w and the site fuse's
rating.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
The restart credit compared a charger's sample time, stamped by the
charger's own clock (OCPP MeterValues), with the time the site reading
arrived on Core's clock. A charger clock 1 s or more behind Core's let
a rise sampled after the reading count as already in it, and L2 reached
19.30 A on the third review's plant case.

A sample now counts only when stamped evClockAllowance (5 s) before the
reading arrived, and the draw is the lowest of that sample and every
sample since. noteDraw keeps the charger's samples while the restart
window is open.

Also tests the max_charge_w half of the rise cap: a 22 kW charger on a
3 x 25 A fuse keeps the reserve up to max_charge_w.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Brings in the current tips of #1910, #1891, #1913, #1923, #1924,
#1925 and #1926.

The only conflict was #1910's changeset: it now carries #1910's new
sentence on an offline battery's relief, and keeps this branch's
"a 0.5 A margin" wording, since 0.5 A is no longer the default here.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
…move

The SiteFuseSafetyA comment read as if the margin were needed by
default; it now says zero is the default and when to set one. The
changeset named "the site's total import and export limits", which
reads as the hourly import_limit; that limit does not move. It now
names the fuse's import and export ceilings.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
A mutation that restored a hidden 0.5 A margin at startup passed every
suite. This test pins the value newControlStateFromConfig hands Core.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
At margin 0 Core holds the phases at the 16 A line. Rig s18-16's 0.1 A
house step at small_step then lands over the line until Core cuts: on
fdfbfec the phase read 16.101 A for 3 s and Core cut the battery
4851 -> 4719 W within 2 s. The criterion "own commands stay inside the
rated fuse" counted that stretch as Core's and failed. The owner's rule
judges an overage between In and 1.2 x In by the I2t model.

The criterion now skips the 10 s after the step, the same gap the minor
window already leaves. On the fdfbfec record Core's own commands peak
at 16.008 A before the step and 16.005 A after it, inside 16.01 A.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
The 5 s clock allowance let the restart credit count a charger sample
taken 5-7 s before the site reading. A car that stopped after that
sample (a fast charger applying the 0 A sent while the meter was stale,
or the car pausing) still counted, the battery ended the discharge the
car's return needed, and L2 reached 21 A on a 16 A fuse when it resumed.

Core now judges a sample by when it first arrived on Core's clock. It
counts as in the reading only when it arrived evMeterDelay (1 s) before
the reading, and no more than one control interval before that. A sample
already there when Core began to watch the charger arrived at a time
Core does not know, so it never counts. The charger's stamp only tells
samples apart, so a charger clock behind Core's no longer matters.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
At margin 0 the car in s8-60-25 settles at the rating, as the owner's
rule says, and the rig's old 1 A hidden margin failed it: 271 s above
24 A against 67 s allowed, with no second over 25 A. siterig/full has the
same threshold in overage() (s9, s10, s11), the random invariants and
s15bat.

Port #1907's judge hunks: s3, s8, s9-s11, s15bat and the invariants now
count time over the fuse rating. TestS8JudgesAtTheFuse and #1907's
TestInvariantsJudgeAtTheFuse fail on the old judges.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
fix(config): fuse safety_margin_a defaults to 0
@frahlg
frahlg merged commit a3f9a7b into car-before-battery-charge Oct 28, 2026
frahlg added a commit that referenced this pull request Oct 28, 2026
…1913, #1923, #1924, #1925, #1926, #1914)

* fix(control): one log of FTW's own EV offers

The battery side read a 20 s pool log of EV offers (State.evOffers), while
the EV fuse limit keeps each charger's offers for its declared response
time, or 180 s when it declares none. After 20 s the battery counted a slow
charger's unshown raise as already in the meter and charged into that room;
when the car started, a 25 A site read 32.6 A per phase for 3 s.

Delete State.evOffers and its two writers. evInMeterW and
clampEVBatteryHeadroom read evShownW, each charger's latest offer less
what it may not show yet. The hourly peak in stepEVMeterLimit takes each
charger's highest offer of the last evSettle from the same log.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery fuse guard reads each phase with its direction

Delete perPhaseOverageW, perPhaseOverageReadingW and perPhaseReliefW.
The battery fuse guard, the fuse saver and the forced discharge read the
signed phase currents (phaseCurrentsA, with #1849's sum check and dead
zone), count the batteries' own move on each phase, and relieve to the
car's working limit, the fuse less max(1 A, safety_margin_a).

Item A5 of the stable plan.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery waits only for a declared charger response time

The first A6 change gave the battery side the EV limit's 180 s guess
for every charger that declares no response time. Only Easee Cloud
declares one, so on every other charger the battery reserved the car's
whole demand on top of a reading that already showed the car, and
stopped charging for 3 minutes after each car start or raise. On the
#1868 shape (rig s18) battery charge stayed at 0 W until 180 s.

evShownW now uses the charger's declared power_max_age_s, and evSettle
when it declares none, as master did. Easee Cloud declares 180 s, so the
slow-charger case stays fixed.

Tests: the slow-charger test now declares 180 s, and a new plant test
runs the s18 shape with a fast charger that declares nothing.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): fuse guard reads phases after the hold caps the targets

The guard took the phase relief from the original request, then the 30 s
fuse hold capped that request and the relief came off again. A charge
limited by one phase switched between 1380 W and 0 W on every dispatch.
Predict the aggregate and the phases from the held targets instead.

The phase reader now takes the meter's raw total from OnlineMeterW, the
same reading as its currents, so an offline meter's cached phases drive
no relief. The batteries' raw power is read in one helper. dispatch.go
keeps its 41 cached telemetry reads.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): car and battery-beside-car work to the fuse rating less safety_margin_a

The EV phase limit was In - 1 A, fixed in code. It is now fuseLineA():
In - safety_margin_a, with no floor. A rise moves one step once it fits
under the line, a start takes all the room, and battery charge beside a
car uses the same line. The hour's import limit keeps its own margins.
Starts and per-phase cuts round down to whole charger amps, since
chargers round offers to the nearest amp.

Step 3 (PR b) of the fuse-at-rating plan (owner rule of 27 Oct).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): keep covered offers whole and leave battery relief out of EV room

Two review findings on the fuse-line change:

- A cut rounds to whole charger amps only when a new cut is needed. When
  cuts on their way cover the overage, the offer stays as it is. Rounding
  a kept step-table offer took the car 6200 -> 5500 -> 4800 -> 0 W in 3 s
  on a 0.6 A overage while a 180 s cut travelled.
- Dispatch records the discharge the fuse guard adds to each battery, and
  an EV rise or start does not count it as room. Before, the car rose into
  the relief and the battery fed it 650 W at the line for as long as the
  house load stayed.

The noisy-line sim test now pins the slow one-step cycle at an exact fit
(at most 5 cuts an hour, never a stop) and no moves with part of a step
left, instead of allowing 45 moves an hour.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery fuse guard reads each phase with its direction

Delete perPhaseOverageW, perPhaseOverageReadingW and perPhaseReliefW.
The battery fuse guard, the fuse saver and the forced discharge read the
signed phase currents (phaseCurrentsA, with #1849's sum check and dead
zone), count the batteries' own move on each phase, and relieve to the
car's working limit, the fuse less max(1 A, safety_margin_a).

Item A5 of the stable plan.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): fuse guard reads phases after the hold caps the targets

The guard took the phase relief from the original request, then the 30 s
fuse hold capped that request and the relief came off again. A charge
limited by one phase switched between 1380 W and 0 W on every dispatch.
Predict the aggregate and the phases from the held targets instead.

The phase reader now takes the meter's raw total from OnlineMeterW, the
same reading as its currents, so an offline meter's cached phases drive
no relief. The batteries' raw power is read in one helper. dispatch.go
keeps its 41 cached telemetry reads.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery relieves to the fuse less safety_margin_a

phaseFuseReliefW now reads fuseLineA(), the line the car uses since the
EV change, instead of max(1 A, safety_margin_a). There is no floor under
the margin: at margin 0 the battery works to the fuse rating.

Tests return to the rating where they had moved to the 1 A limit, and a
new property test covers In x phases x margin in both directions.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): re-record golden records at the fuse less safety_margin_a

Replayed from stored inputs; only records whose dispatch changed against
the parent branch were replaced.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery fuse cut lands on the line, not half a margin below

applyFuseGuard cut a battery charge or discharge by the overage plus
half of safety_margin_a. The guard now predicts from the held targets
and keeps its 30 s hold, so the extra cut only parked the phase below
the line the user set. Cut by the overage only.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* docs(changeset): name the limit the battery cut lands on

The changeset said the phase lands on the fuse less safety_margin_a.
On #1891 as it stands, the phase line is the fuse less max(1 A,
safety_margin_a), so at the 0.5 A default a 16 A phase settles at
15 A, not 15.5 A. Say what this PR changes, cutting only by the
overage, without naming a line that depends on step 4.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(config): fuse safety_margin_a defaults to 0

Core now works to the fuse rating unless a site sets a margin. Every
explicit safety_margin_a is kept. A stored value of exactly 0.5 A, the
old default, adds one load-time notice and changes nothing.

The peak-limit error names the margin only when it is above 0, and the
settings field shows 0 with help that says the margin is opt-in.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* docs(changeset): say what the default change moves on its own

The changeset said FTW works to the fuse rating unless a site sets a
margin. On this PR's base every per-phase line still sits 1 A under the
rating; that holds only once #1910 and the step-4 amendment of #1891
land. The changeset now names what this PR changes: the default, and
the whole-site import and export limits.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): relief stays at the line after a PV drop (C3, seed 207533)

On a 16 A fuse with no margin the battery holds 3 kW of discharge with L1
at 14.4 A; PV drops 1280 W and L1 reads 16.3 A. The relief must bring L1
to 16 A and keep it there while the reading sits at the line with the
battery at its relief power. Without phaseFuseReliefW's own-move count
the relief flips between -3214 W and -3005 W on every tick and L1 crosses
the rating 13 times; with it, L1 crosses once.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): phase relief reads each battery live, in the decision's reading

The merge of #1876 moved stopPhaseReliefW's live reads into
phaseSample.moveW. Pin it: a battery that went offline, moved on to a
newer reading or has no reading gives no phase relief. With the cached
RawW read #1891 had, the offline and newer-reading cases relieve 2310 W
and the no-reading case counts a 2000 W charge from 0 W.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery relief holds when the battery's reading lags the meter

The phase relief counts the battery's move from its own reading. When
that reading lags the meter by a tick, the meter already shows the relief
while the reading does not, so the relief came off; on the next tick it
went back on top of the reading's catch-up. In the 207533 shape (16 A,
margin 0) with a one-tick lag the order ran -3214, -3005, -3422, -3005,
... -5717 W and L1 went back to 16.3 A on every other tick: 13 crossings.

A move from the battery's last command (the one it got in the last
dispatch) may now not pass the room the meter shows either. That bound
only tightens, and a phase already over the line gives it no room, so it
never asks for more than to stay at the last command: a battery that
falls short of its order does not wind it up. With lag 1 or 2 the order
holds -3214 W with L1 at 16.0 A and one crossing, on the PV step.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): a landed EV cut covers nothing later; a raise that no longer fits comes off

The site meter now tells Core how much of a charger's offers it already
shows. A move shaped like an order landing (every phase alike, or one
phase alone for a one-phase car) moves that level toward the latest
offer. A cut the meter shows no longer covers an overage that an outside
step causes after it, and no longer nets against a raise sent after it.
Where a landing and a house step fall in one reading, a cut covers a
phase that has risen since only up to the overage it had then.

C4: our own rise on its way, as the meter tells it, is judged as the
reading it will make. Above 1.2 x In, or over the line on a phase whose
heat budget is spent, it comes off on this reading, down to the line.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): a one-phase house move is not the car's cut landing

seeOffers kept one shown level for every phase, so a house load moving on
one phase alone read as a three-phase cut landing and took the cut's cover
off the phase it was sent for. With a 40 s charger Core then stacked a
second cut and left L1 2 A under the line for over 2 min. The shown level
is now kept per phase: a three-phase order moves every phase alike, and a
phase that moves alone moves only its own level.

The loadpoint now reports a car it has seen draw on all three phases as
CarPhases 3. For such a car a one-phase move is never the car, so a house
step on one phase while a raise travels no longer hides the raise, and C4
cuts on that reading.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): a battery charge rise fits each phase before it is sent

The battery fuse guard judged a rise from the battery's own reading and
the meter's phases, so it took a rise the meter did not show yet as
already shown. With the meter a poll behind the battery, a PV surplus that
grew each tick stacked rises past the line, then the relief cut them back:
16.4 A on a 16 A fuse and a charge that rose and fell (C2, seeds 207530,
207535).

fitBatteryRisesToFuse caps charge above the battery's latest order to
(fuseLineA - worst phase - own unshown rises) x V x phases. The unshown
rises are the battery's orders of the last evSettle and the chargers'
raises, counted as evShownW counts them, so the car comes first. Holding
an order is never a rise and the check never cuts; an overage stays with
the relief. No margin and no floor: the order ends at the line.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery rise check counts slow batteries and direction-less phases

A battery order now stays unshown until evSettle after the battery's own
reading reaches it, so a battery that ramps slower than evSettle no longer
gets a second rise on top of an order the meter cannot show yet.

On a meter with phase currents but no phase power while the total
exports, a phase counts as export only when the other phases cannot
carry the export alone; any other phase counts as import. Before, every
phase flipped to export, so a three-phase charge could rise into a phase
that imports beside two exporting ones.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): the car comes before battery charge

With battery_covers_ev off, dispatch took the car out of the meter
reading before the battery decided. The battery then saw the PV the
car was using as export and charged from it while the site imported
for the car (rig seeds 207535, 207539, 207530: about 10 kW import).

The battery now charges only from the surplus the meter shows after
the car. Where the house alone has surplus, the battery sees the meter
with the car included, and any discharge stops at once, since it would
feed the car. A planned PV charge on the energy path takes only the
surplus the car leaves; a planned grid purchase keeps its charge.
Cover off still never discharges the battery for the car.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): peak shaving drops a running charge for the car

Manual peak_shaving gave zero error for any import under the peak
limit, so a battery charge that was running when the car started held
while the site imported for the car, with battery_covers_ev on or off.
When the site imports while the car and the battery both charge, the
charge now comes down by the import, to 0 at most. Under the peak limit
the battery still never discharges.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): after a restart the battery credits the car the meter shows

After a restart, the 0 A orders FTW sent while the meter was stale counted
as the EV base the meter shows. With the car still drawing 8.2 kW from
before, a new 6.2 kW order then counted as a 9 A rise to come, and the
battery was held in discharge for the car (seed 207532).

Until a charger's first order of this run can have landed, the battery
side now counts the charger's live measured draw as in the reading, never
above the latest order and never above the consumption the site meter
shows. The car's own limit does not read it.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): credit a found car only from a current charger sample

Review of #1926 found two ways the restart credit let the battery end a
discharge into room the car's pending rise still needs:

- The charger reading counted with no check that it was current. A held
  reading after a failed poll, or a sample older than the site reading,
  could show a car that a fast charger had already stopped. The draw now
  counts only when the last poll succeeded and the charger measured it
  within one control interval of the site reading.
- The consumption bound subtracted the smoothed battery, PV and V2X
  values, which lag an output that just fell. It now takes the higher of
  raw and smoothed for each, so the bound stays at or below what the
  meter shows.

New tests pin both, plus the shown-offer subtractions and a window that
outlasts evSettle.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): run the site sim at the new 0 A default margin

simFuseSafetyA follows the config default, now 0. fitScenario takes the
room under the line and sets the house from simFuseSafetyA, so its exact
fit stays twelve whole steps at any margin. "charger's own load
balancer" passes at margin 0, so its known line goes.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* docs(changeset): say what margin 0 moves once the fuse stack lands

With the stack under it, the default moves the car's and the battery's
per-phase line as well as the site totals. 0.5 A stops being the
default, so #1910's changeset no longer calls it that.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): keep the load-balancer bug as a known line above the line

At the 0 A default the scenario passes only because the charger's own
balancer sits at 25 A, the rating and so the line. The bug is still in
Core: a cut comes off an offer the car does not draw. Two known variants
keep it tracked and turn red once it is fixed: the stored 0.5 A margin
(over 24.5 A for more than 11 s) and a balancer at 25.5 A at margin 0
(over 25 A for more than 11 s).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): EV room reads battery relief through live telemetry

evFuseReliefW read each battery's cached RawW, which survives a driver
going offline. It now reads Store.OnlineRawW. A battery with no live
reading counts its whole recorded relief, so the car never builds on
discharge Core can no longer hold.

fuseSaverEarlyExit read each battery's SmoothedW a second time to record
relief. It now records against the live snapshot the fuse-saver decision
already took (fleetAtLivePower), so it adds no read of its own.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): an offline battery's fuse relief ends after evSettle

With no battery online, ComputeDispatch returns before it records relief,
so batteryFuseRelief kept its last value and evFuseReliefW counted all of
it for as long as the battery stayed offline. The car was held up to the
whole relief below the line. The relief now counts in full until the
default mode Core sent at the transition can have reached the meter
(evSettle), then ends.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): each offline battery's fuse relief ends after evSettle

The expiry in 8150b45 ran only when no battery was online. With a
second battery online, an offline battery's relief stayed until a
recorded dispatch rewrote the map: never while the legacy modes sat in
the deadband, and on the first tick when one did record, so the car
could rise onto discharge Core ordered a second earlier. Each offline
battery now has its own clock: its relief counts whole for evSettle
and then ends, on every dispatch path. A battery back online leaves the
clock, so its next offline period counts whole again; a test now covers
that reset.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery phase relief neither pins mixed phases nor winds up

The last-command bound held the battery at its last command when one
phase sat at the import line and another was over the export line: the
guard cut the discharge for the exporting phase and the bound put it
back. Now the bound gives way on one side while any phase is over the
other side's line, and phaseFuseReliefW's least-over move decides.

When the meter does not show the battery's move (a frozen meter, or a
worst phase a one-phase battery cannot reach), each tick added the same
overage again and the order ran out to the discharge limit. Now the
relief toward the worst phase stops at the last command once the
batteries' raw power has moved one ampere per phase since the worst
phase last moved by half an ampere. One ampere is the step in which P1
meters report phase current.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery phase anti-windup stops only when the meter cannot show the move

phaseUnresponsive stopped the relief whenever the batteries had moved
690 W and the worst phase had not moved half an ampere. On a live meter
that also happens when a load cancels the move (a balanced load starting
with the relief step, or a slow rise on the worst phase), and when the
battery's reading catches up with an order the meter already showed.
The relief then held over the line with no end.

Now it stops only when the meter repeats its phases exactly while the
batteries moved one ampere per phase, or when another phase moved by
twice the balanced share of that move (a battery off the worst phase).
The repeat is measured from the reading the meter last changed in, so a
meter that freezes on any reading is still caught.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery off the worst phase goes back, and a stale reference ends

Fourth review of the phase anti-windup (c066892):

- The worst phase's reference had no end while that phase sat over the
  line. A relief that follows a slow drift keeps it there, so the
  reference stayed while the battery moved hundreds of watts, and a load
  that later switched off on another phase read as a battery off the
  worst phase. The relief then held L1 up to 0.49 A over the line with no
  time limit. The reference now also ends when the worst phase is at or
  inside the line, or when another phase becomes the worst.
- An off-phase verdict no longer holds the last command. The batteries go
  back to their power when the worst phase last moved: what they moved
  since did not reach it. A one-phase battery no longer holds its own
  phase at -17.97 A for the whole overage (and -19.83 A, past 1.2 x In,
  when PV returns). A false verdict on a balanced battery moves the
  worst phase by at least one ampere on the next reading, which ends the
  reference, so it costs one tick instead of an open-ended hold. The
  verdict holds until the reference ends, so the relief does not go out
  again once the battery is back.
- The frozen-meter test now also compares the meter's total. A P1 meter
  reports whole amperes, so a live meter can repeat its phases while its
  total moves; that latched the relief at 1.11 x In.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): the drift test also wants no verdict on the load change

With L1 at the line ending the reference, no off-phase verdict comes when
the load on L3 switches off. Without it, the step back still ends the
hold, but with L1 at 16.8 and 17.7 A for two ticks; the test now sees
that.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): our battery order's move is not the car's cut landing

The guard in seeOffers that stops reading the meter while our battery
order moves had no test; removing it left every test green. A battery
order that lands and goes back while a cut travels to a 40 s charger
now must not lead to a second cut.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): the car-first discharge stop has its own test

Removing the PI path's immediate discharge stop left every named test
green; only the golden replay caught it. A peak_shaving loop with
battery_covers_ev off, starting from a 2.9 kW discharge while the house
alone has surplus, now requires that no order discharges into the car.

The comment on the plan back-off said the plan's grid leaves out the car.
It counts the car it planned; the comment now says so.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): the battery rise check reads only live battery power

fitBatteryRisesToFuse, unshownBatteryW and recordBatteryReadings read
the battery's cached RawW, which survives the driver going offline, and
added three direct telemetry reads that the repo-hygiene check refuses.
They now use Store.OnlineRawW, as phaseSample.moveW does: an offline
battery's last value no longer sets the rise base or the shown level.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): judge a raise's landing from the meter's rise

C4 counted a raise as landed only when a reading-to-reading move had a
charger's shape. A slow ramp, or a house load on another phase that moved
in the landing reading, left the whole raise counted as on its way on top
of a reading that already held it, and Core cut a raise that fit under
the line. The rise still to come now reads the meter's own rise since the
raise went out: the smallest across the phases for a three-phase order,
the car's phase for a one-phase car.

For a three-phase order, a move on one phase alone no longer moves the
shown level of a car not yet seen. A load cycling on the phase over the
line took the cut's cover off on each drop and never gave it back, so
Core cut again and again.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): a car not yet seen may take a raise on one phase

The smallest rise across the phases read a one-phase car not yet seen
as a raise that had not landed: its phase rose, the other two did not.
Core then cut the car from 11040 W to 0 with every phase under the line
(field matrix, car1p cases). One phase that has risen alone since the
raise went out, the others within half a step, now counts as that car
taking the raise, as the shape tracker read it before. The changeset
again says what holds: the one-phase house step case is closed for a
car seen on three phases.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): judge a one-phase landing reading by reading

For a car not yet seen on three phases, a raise counted as landed on one
phase only while the other phases stayed within 0.5 A of their reading
when the raise went out. That window spans the charger's whole response
time, so 0.6 A of house drift on another phase made the full raise count
as still to come on top of a reading that already showed it, and Core
cut the car with every phase under the line (field matrix with 0.7 A on
L2: car1p cut 11100 -> 0 W).

Each phase now keeps its rise over the readings in which the other
phases moved less than a step (aloneA). A rise of a step or more there
may be the car on that phase. Drift between readings, or under a step
in the landing reading, no longer hides it; a house load that moves a
step or more on another phase in the same reading still does.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): restart credit keeps room for the car's rise to its max

After a restart Core does not know the offer in force on the charger, so
a car drawing below it may still rise before Core's order lands. The
credit now counts only the draw less that possible rise past the latest
offer, with the rise measured to the loadpoint's max_charge_w; a charger
with no max_charge_w gets no credit.

The charger and output reads move into health-gated telemetry accessors
(OnlineLowerW, SumOnlineHigherW). Tests cover the raw and smoothed
guards, a 10 s OCPP sample cadence on the plant, and the review's car
rising under a 16 A offer in force.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): Charge now landing shown before Core logs its offer

Site rig s1-16, s1-25 and s15-25 failed on c9b52c3: the charger answered
within a second, and the meter reading that showed the car at 15.9 A came
in 7 ms before the tick that first logged the 16 A offer. The reading
could not show an offer logged after it, so the landing counted as a
raise still to come, 15.9 + 16 A passed 1.2 x In, and Core cut 11,040 W
to 5,520 W with 9 A of room on every phase. The same run of the base at
281f9f6, without this branch's commits, fails the same way; #1923's
ab02710, merged here in c0a5274, reads the meter's own rise and fixes
it. This test pins that rig shape.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): restart credit counts no sample newer than the meter

The battery side's restart credit (evFoundDrawW) had two gaps.

A charger sample measured after the site reading counted as part of
it. A car that rose in that gap was credited for draw the meter did
not show yet, and the battery ended its discharge into room the rise
had taken. With a 3 s meter, L2 reached 19.30 A. A sample now counts
only when measured at or before the site reading.

The rise reserve took max_charge_w as the most the unknown offer in
force can be. A charger still on an offer from before a restart that
lowered max_charge_w, or on its own higher default, could rise past
it: 19.00 A per phase on the unit fixture, 19.30 A on the plant. The
reserve now runs to the larger of max_charge_w and the site fuse's
rating.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): restart credit holds against a charger clock behind Core's

The restart credit compared a charger's sample time, stamped by the
charger's own clock (OCPP MeterValues), with the time the site reading
arrived on Core's clock. A charger clock 1 s or more behind Core's let
a rise sampled after the reading count as already in it, and L2 reached
19.30 A on the third review's plant case.

A sample now counts only when stamped evClockAllowance (5 s) before the
reading arrived, and the draw is the lowest of that sample and every
sample since. noteDraw keeps the charger's samples while the restart
window is open.

Also tests the max_charge_w half of the rise cap: a 22 kW charger on a
3 x 25 A fuse keeps the reserve up to max_charge_w.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* docs(control): the fuse margin is opt-in, and only the fuse ceilings move

The SiteFuseSafetyA comment read as if the margin were needed by
default; it now says zero is the default and when to set one. The
changeset named "the site's total import and export limits", which
reads as the hourly import_limit; that limit does not move. It now
names the fuse's import and export ceilings.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): battery beside a minimum-step car holds the fuse line (rig s18-16)

On #1910 and #1891 the battery rises beside the car to the working limit,
the fuse guard cuts it by the overage plus half of safety_margin_a and holds
30 s, and the battery rises again: it hunts between 15.0 and 15.5 A on a
16 A site. Where it stands when the house moves is chance, which is why
rig s18-16 failed 3 of 57 runs on those heads. #1913's cut by the overage
only keeps it on the line.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(config): an unset fuse margin reaches Core as 0

A mutation that restored a hidden 0.5 A margin at startup passed every
suite. This test pins the value newControlStateFromConfig hands Core.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): s18 judges own commands apart from the house's step

At margin 0 Core holds the phases at the 16 A line. Rig s18-16's 0.1 A
house step at small_step then lands over the line until Core cuts: on
fdfbfec the phase read 16.101 A for 3 s and Core cut the battery
4851 -> 4719 W within 2 s. The criterion "own commands stay inside the
rated fuse" counted that stretch as Core's and failed. The owner's rule
judges an overage between In and 1.2 x In by the I2t model.

The criterion now skips the 10 s after the step, the same gap the minor
window already leaves. On the fdfbfec record Core's own commands peak
at 16.008 A before the step and 16.005 A after it, inside 16.01 A.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): no cut of an unseen car, no landing from a 1p house move

Two regressions against #1913 from the final review.

A car the loadpoint has not seen on three phases may draw on one phase
Core does not know. The alone rise (aloneA) missed its landing when any
other phase moved a step in the same reading, so the whole raise counted
as still to come and C4 cut a car with every phase under the line, at
most session starts with a 10 s meter. riseAheadA now takes the largest
rise for such a car, as for a one-phase car whose phase is not known,
and the smallest only once the car is seen on three phases.

A one-phase order never knows the car's phase, so a house load moving
alone on any phase read as its cut landing and took the cover off a cut
still on its way. A one-phase move now counts only on a known car phase.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): judge a restart sample by its arrival, not its stamp

The 5 s clock allowance let the restart credit count a charger sample
taken 5-7 s before the site reading. A car that stopped after that
sample (a fast charger applying the 0 A sent while the meter was stale,
or the car pausing) still counted, the battery ended the discharge the
car's return needed, and L2 reached 21 A on a 16 A fuse when it resumed.

Core now judges a sample by when it first arrived on Core's clock. It
counts as in the reading only when it arrived evMeterDelay (1 s) before
the reading, and no more than one control interval before that. A sample
already there when Core began to watch the charger arrived at a time
Core does not know, so it never counts. The charger's stamp only tells
samples apart, so a charger clock behind Core's no longer matters.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): judge overages at the fuse rating, not fuse - 1 A

At margin 0 the car in s8-60-25 settles at the rating, as the owner's
rule says, and the rig's old 1 A hidden margin failed it: 271 s above
24 A against 67 s allowed, with no second over 25 A. siterig/full has the
same threshold in overage() (s9, s10, s11), the random invariants and
s15bat.

Port #1907's judge hunks: s3, s8, s9-s11, s15bat and the invariants now
count time over the fuse rating. TestS8JudgesAtTheFuse and #1907's
TestInvariantsJudgeAtTheFuse fail on the old judges.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

---------

Co-authored-by: Claude Opus 5.5 <noreply@anthropic.com>
frahlg added a commit that referenced this pull request Oct 28, 2026
…mit (#1919)

* fix(control): one log of FTW's own EV offers

The battery side read a 20 s pool log of EV offers (State.evOffers), while
the EV fuse limit keeps each charger's offers for its declared response
time, or 180 s when it declares none. After 20 s the battery counted a slow
charger's unshown raise as already in the meter and charged into that room;
when the car started, a 25 A site read 32.6 A per phase for 3 s.

Delete State.evOffers and its two writers. evInMeterW and
clampEVBatteryHeadroom read evShownW, each charger's latest offer less
what it may not show yet. The hourly peak in stepEVMeterLimit takes each
charger's highest offer of the last evSettle from the same log.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery fuse guard reads each phase with its direction

Delete perPhaseOverageW, perPhaseOverageReadingW and perPhaseReliefW.
The battery fuse guard, the fuse saver and the forced discharge read the
signed phase currents (phaseCurrentsA, with #1849's sum check and dead
zone), count the batteries' own move on each phase, and relieve to the
car's working limit, the fuse less max(1 A, safety_margin_a).

Item A5 of the stable plan.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery waits only for a declared charger response time

The first A6 change gave the battery side the EV limit's 180 s guess
for every charger that declares no response time. Only Easee Cloud
declares one, so on every other charger the battery reserved the car's
whole demand on top of a reading that already showed the car, and
stopped charging for 3 minutes after each car start or raise. On the
#1868 shape (rig s18) battery charge stayed at 0 W until 180 s.

evShownW now uses the charger's declared power_max_age_s, and evSettle
when it declares none, as master did. Easee Cloud declares 180 s, so the
slow-charger case stays fixed.

Tests: the slow-charger test now declares 180 s, and a new plant test
runs the s18 shape with a fast charger that declares nothing.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): fuse guard reads phases after the hold caps the targets

The guard took the phase relief from the original request, then the 30 s
fuse hold capped that request and the relief came off again. A charge
limited by one phase switched between 1380 W and 0 W on every dispatch.
Predict the aggregate and the phases from the held targets instead.

The phase reader now takes the meter's raw total from OnlineMeterW, the
same reading as its currents, so an offline meter's cached phases drive
no relief. The batteries' raw power is read in one helper. dispatch.go
keeps its 41 cached telemetry reads.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): car and battery-beside-car work to the fuse rating less safety_margin_a

The EV phase limit was In - 1 A, fixed in code. It is now fuseLineA():
In - safety_margin_a, with no floor. A rise moves one step once it fits
under the line, a start takes all the room, and battery charge beside a
car uses the same line. The hour's import limit keeps its own margins.
Starts and per-phase cuts round down to whole charger amps, since
chargers round offers to the nearest amp.

Step 3 (PR b) of the fuse-at-rating plan (owner rule of 27 Oct).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): keep covered offers whole and leave battery relief out of EV room

Two review findings on the fuse-line change:

- A cut rounds to whole charger amps only when a new cut is needed. When
  cuts on their way cover the overage, the offer stays as it is. Rounding
  a kept step-table offer took the car 6200 -> 5500 -> 4800 -> 0 W in 3 s
  on a 0.6 A overage while a 180 s cut travelled.
- Dispatch records the discharge the fuse guard adds to each battery, and
  an EV rise or start does not count it as room. Before, the car rose into
  the relief and the battery fed it 650 W at the line for as long as the
  house load stayed.

The noisy-line sim test now pins the slow one-step cycle at an exact fit
(at most 5 cuts an hour, never a stop) and no moves with part of a step
left, instead of allowing 45 moves an hour.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery fuse guard reads each phase with its direction

Delete perPhaseOverageW, perPhaseOverageReadingW and perPhaseReliefW.
The battery fuse guard, the fuse saver and the forced discharge read the
signed phase currents (phaseCurrentsA, with #1849's sum check and dead
zone), count the batteries' own move on each phase, and relieve to the
car's working limit, the fuse less max(1 A, safety_margin_a).

Item A5 of the stable plan.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): fuse guard reads phases after the hold caps the targets

The guard took the phase relief from the original request, then the 30 s
fuse hold capped that request and the relief came off again. A charge
limited by one phase switched between 1380 W and 0 W on every dispatch.
Predict the aggregate and the phases from the held targets instead.

The phase reader now takes the meter's raw total from OnlineMeterW, the
same reading as its currents, so an offline meter's cached phases drive
no relief. The batteries' raw power is read in one helper. dispatch.go
keeps its 41 cached telemetry reads.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery relieves to the fuse less safety_margin_a

phaseFuseReliefW now reads fuseLineA(), the line the car uses since the
EV change, instead of max(1 A, safety_margin_a). There is no floor under
the margin: at margin 0 the battery works to the fuse rating.

Tests return to the rating where they had moved to the 1 A limit, and a
new property test covers In x phases x margin in both directions.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): re-record golden records at the fuse less safety_margin_a

Replayed from stored inputs; only records whose dispatch changed against
the parent branch were replaced.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery fuse cut lands on the line, not half a margin below

applyFuseGuard cut a battery charge or discharge by the overage plus
half of safety_margin_a. The guard now predicts from the held targets
and keeps its 30 s hold, so the extra cut only parked the phase below
the line the user set. Cut by the overage only.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* docs(changeset): name the limit the battery cut lands on

The changeset said the phase lands on the fuse less safety_margin_a.
On #1891 as it stands, the phase line is the fuse less max(1 A,
safety_margin_a), so at the 0.5 A default a 16 A phase settles at
15 A, not 15.5 A. Say what this PR changes, cutting only by the
overage, without naming a line that depends on step 4.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(config): fuse safety_margin_a defaults to 0

Core now works to the fuse rating unless a site sets a margin. Every
explicit safety_margin_a is kept. A stored value of exactly 0.5 A, the
old default, adds one load-time notice and changes nothing.

The peak-limit error names the margin only when it is above 0, and the
settings field shows 0 with help that says the margin is opt-in.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* docs(changeset): say what the default change moves on its own

The changeset said FTW works to the fuse rating unless a site sets a
margin. On this PR's base every per-phase line still sits 1 A under the
rating; that holds only once #1910 and the step-4 amendment of #1891
land. The changeset now names what this PR changes: the default, and
the whole-site import and export limits.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): a restart seeds the fuse heat at most at the working limit

After a Core restart the I² heat model started at the first reading's
current, as if that overload had lasted. In seed 207539 one 27.94 A
reading on a 20 A fuse held an idle car back about 43 s while the model
cooled. Seed each phase at its first reading, at most the working
limit. A sustained overload after a restart is still cut on the next
reading; a cold start would have given it a fresh budget of over a
minute. The instant cut above 1.2 x In is unchanged.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): relief stays at the line after a PV drop (C3, seed 207533)

On a 16 A fuse with no margin the battery holds 3 kW of discharge with L1
at 14.4 A; PV drops 1280 W and L1 reads 16.3 A. The relief must bring L1
to 16 A and keep it there while the reading sits at the line with the
battery at its relief power. Without phaseFuseReliefW's own-move count
the relief flips between -3214 W and -3005 W on every tick and L1 crosses
the rating 13 times; with it, L1 crosses once.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): phase relief reads each battery live, in the decision's reading

The merge of #1876 moved stopPhaseReliefW's live reads into
phaseSample.moveW. Pin it: a battery that went offline, moved on to a
newer reading or has no reading gives no phase relief. With the cached
RawW read #1891 had, the offline and newer-reading cases relieve 2310 W
and the no-reading case counts a 2000 W charge from 0 W.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery relief holds when the battery's reading lags the meter

The phase relief counts the battery's move from its own reading. When
that reading lags the meter by a tick, the meter already shows the relief
while the reading does not, so the relief came off; on the next tick it
went back on top of the reading's catch-up. In the 207533 shape (16 A,
margin 0) with a one-tick lag the order ran -3214, -3005, -3422, -3005,
... -5717 W and L1 went back to 16.3 A on every other tick: 13 crossings.

A move from the battery's last command (the one it got in the last
dispatch) may now not pass the room the meter shows either. That bound
only tightens, and a phase already over the line gives it no room, so it
never asks for more than to stay at the last command: a battery that
falls short of its order does not wind it up. With lag 1 or 2 the order
holds -3214 W with L1 at 16.0 A and one crossing, on the PV step.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): a landed EV cut covers nothing later; a raise that no longer fits comes off

The site meter now tells Core how much of a charger's offers it already
shows. A move shaped like an order landing (every phase alike, or one
phase alone for a one-phase car) moves that level toward the latest
offer. A cut the meter shows no longer covers an overage that an outside
step causes after it, and no longer nets against a raise sent after it.
Where a landing and a house step fall in one reading, a cut covers a
phase that has risen since only up to the overage it had then.

C4: our own rise on its way, as the meter tells it, is judged as the
reading it will make. Above 1.2 x In, or over the line on a phase whose
heat budget is spent, it comes off on this reading, down to the line.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): a one-phase house move is not the car's cut landing

seeOffers kept one shown level for every phase, so a house load moving on
one phase alone read as a three-phase cut landing and took the cut's cover
off the phase it was sent for. With a 40 s charger Core then stacked a
second cut and left L1 2 A under the line for over 2 min. The shown level
is now kept per phase: a three-phase order moves every phase alike, and a
phase that moves alone moves only its own level.

The loadpoint now reports a car it has seen draw on all three phases as
CarPhases 3. For such a car a one-phase move is never the car, so a house
step on one phase while a raise travels no longer hides the raise, and C4
cuts on that reading.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): a battery charge rise fits each phase before it is sent

The battery fuse guard judged a rise from the battery's own reading and
the meter's phases, so it took a rise the meter did not show yet as
already shown. With the meter a poll behind the battery, a PV surplus that
grew each tick stacked rises past the line, then the relief cut them back:
16.4 A on a 16 A fuse and a charge that rose and fell (C2, seeds 207530,
207535).

fitBatteryRisesToFuse caps charge above the battery's latest order to
(fuseLineA - worst phase - own unshown rises) x V x phases. The unshown
rises are the battery's orders of the last evSettle and the chargers'
raises, counted as evShownW counts them, so the car comes first. Holding
an order is never a rise and the check never cuts; an overage stays with
the relief. No margin and no floor: the order ends at the line.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery rise check counts slow batteries and direction-less phases

A battery order now stays unshown until evSettle after the battery's own
reading reaches it, so a battery that ramps slower than evSettle no longer
gets a second rise on top of an order the meter cannot show yet.

On a meter with phase currents but no phase power while the total
exports, a phase counts as export only when the other phases cannot
carry the export alone; any other phase counts as import. Before, every
phase flipped to export, so a three-phase charge could rise into a phase
that imports beside two exporting ones.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): the car comes before battery charge

With battery_covers_ev off, dispatch took the car out of the meter
reading before the battery decided. The battery then saw the PV the
car was using as export and charged from it while the site imported
for the car (rig seeds 207535, 207539, 207530: about 10 kW import).

The battery now charges only from the surplus the meter shows after
the car. Where the house alone has surplus, the battery sees the meter
with the car included, and any discharge stops at once, since it would
feed the car. A planned PV charge on the energy path takes only the
surplus the car leaves; a planned grid purchase keeps its charge.
Cover off still never discharges the battery for the car.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): peak shaving drops a running charge for the car

Manual peak_shaving gave zero error for any import under the peak
limit, so a battery charge that was running when the car started held
while the site imported for the car, with battery_covers_ev on or off.
When the site imports while the car and the battery both charge, the
charge now comes down by the import, to 0 at most. Under the peak limit
the battery still never discharges.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): after a restart the battery credits the car the meter shows

After a restart, the 0 A orders FTW sent while the meter was stale counted
as the EV base the meter shows. With the car still drawing 8.2 kW from
before, a new 6.2 kW order then counted as a 9 A rise to come, and the
battery was held in discharge for the car (seed 207532).

Until a charger's first order of this run can have landed, the battery
side now counts the charger's live measured draw as in the reading, never
above the latest order and never above the consumption the site meter
shows. The car's own limit does not read it.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): credit a found car only from a current charger sample

Review of #1926 found two ways the restart credit let the battery end a
discharge into room the car's pending rise still needs:

- The charger reading counted with no check that it was current. A held
  reading after a failed poll, or a sample older than the site reading,
  could show a car that a fast charger had already stopped. The draw now
  counts only when the last poll succeeded and the charger measured it
  within one control interval of the site reading.
- The consumption bound subtracted the smoothed battery, PV and V2X
  values, which lag an output that just fell. It now takes the higher of
  raw and smoothed for each, so the bound stays at or below what the
  meter shows.

New tests pin both, plus the shown-offer subtractions and a window that
outlasts evSettle.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): run the site sim at the new 0 A default margin

simFuseSafetyA follows the config default, now 0. fitScenario takes the
room under the line and sets the house from simFuseSafetyA, so its exact
fit stays twelve whole steps at any margin. "charger's own load
balancer" passes at margin 0, so its known line goes.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* docs(changeset): say what margin 0 moves once the fuse stack lands

With the stack under it, the default moves the car's and the battery's
per-phase line as well as the site totals. 0.5 A stops being the
default, so #1910's changeset no longer calls it that.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): keep the load-balancer bug as a known line above the line

At the 0 A default the scenario passes only because the charger's own
balancer sits at 25 A, the rating and so the line. The bug is still in
Core: a cut comes off an offer the car does not draw. Two known variants
keep it tracked and turn red once it is fixed: the stored 0.5 A margin
(over 24.5 A for more than 11 s) and a balancer at 25.5 A at margin 0
(over 25 A for more than 11 s).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): EV room reads battery relief through live telemetry

evFuseReliefW read each battery's cached RawW, which survives a driver
going offline. It now reads Store.OnlineRawW. A battery with no live
reading counts its whole recorded relief, so the car never builds on
discharge Core can no longer hold.

fuseSaverEarlyExit read each battery's SmoothedW a second time to record
relief. It now records against the live snapshot the fuse-saver decision
already took (fleetAtLivePower), so it adds no read of its own.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): an offline battery's fuse relief ends after evSettle

With no battery online, ComputeDispatch returns before it records relief,
so batteryFuseRelief kept its last value and evFuseReliefW counted all of
it for as long as the battery stayed offline. The car was held up to the
whole relief below the line. The relief now counts in full until the
default mode Core sent at the transition can have reached the meter
(evSettle), then ends.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): each offline battery's fuse relief ends after evSettle

The expiry in 8150b45 ran only when no battery was online. With a
second battery online, an offline battery's relief stayed until a
recorded dispatch rewrote the map: never while the legacy modes sat in
the deadband, and on the first tick when one did record, so the car
could rise onto discharge Core ordered a second earlier. Each offline
battery now has its own clock: its relief counts whole for evSettle
and then ends, on every dispatch path. A battery back online leaves the
clock, so its next offline period counts whole again; a test now covers
that reset.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery phase relief neither pins mixed phases nor winds up

The last-command bound held the battery at its last command when one
phase sat at the import line and another was over the export line: the
guard cut the discharge for the exporting phase and the bound put it
back. Now the bound gives way on one side while any phase is over the
other side's line, and phaseFuseReliefW's least-over move decides.

When the meter does not show the battery's move (a frozen meter, or a
worst phase a one-phase battery cannot reach), each tick added the same
overage again and the order ran out to the discharge limit. Now the
relief toward the worst phase stops at the last command once the
batteries' raw power has moved one ampere per phase since the worst
phase last moved by half an ampere. One ampere is the step in which P1
meters report phase current.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery phase anti-windup stops only when the meter cannot show the move

phaseUnresponsive stopped the relief whenever the batteries had moved
690 W and the worst phase had not moved half an ampere. On a live meter
that also happens when a load cancels the move (a balanced load starting
with the relief step, or a slow rise on the worst phase), and when the
battery's reading catches up with an order the meter already showed.
The relief then held over the line with no end.

Now it stops only when the meter repeats its phases exactly while the
batteries moved one ampere per phase, or when another phase moved by
twice the balanced share of that move (a battery off the worst phase).
The repeat is measured from the reading the meter last changed in, so a
meter that freezes on any reading is still caught.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery off the worst phase goes back, and a stale reference ends

Fourth review of the phase anti-windup (c066892):

- The worst phase's reference had no end while that phase sat over the
  line. A relief that follows a slow drift keeps it there, so the
  reference stayed while the battery moved hundreds of watts, and a load
  that later switched off on another phase read as a battery off the
  worst phase. The relief then held L1 up to 0.49 A over the line with no
  time limit. The reference now also ends when the worst phase is at or
  inside the line, or when another phase becomes the worst.
- An off-phase verdict no longer holds the last command. The batteries go
  back to their power when the worst phase last moved: what they moved
  since did not reach it. A one-phase battery no longer holds its own
  phase at -17.97 A for the whole overage (and -19.83 A, past 1.2 x In,
  when PV returns). A false verdict on a balanced battery moves the
  worst phase by at least one ampere on the next reading, which ends the
  reference, so it costs one tick instead of an open-ended hold. The
  verdict holds until the reference ends, so the relief does not go out
  again once the battery is back.
- The frozen-meter test now also compares the meter's total. A P1 meter
  reports whole amperes, so a live meter can repeat its phases while its
  total moves; that latched the relief at 1.11 x In.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): the drift test also wants no verdict on the load change

With L1 at the line ending the reference, no off-phase verdict comes when
the load on L3 switches off. Without it, the step back still ends the
hold, but with L1 at 16.8 and 17.7 A for two ticks; the test now sees
that.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): our battery order's move is not the car's cut landing

The guard in seeOffers that stops reading the meter while our battery
order moves had no test; removing it left every test green. A battery
order that lands and goes back while a cut travels to a 40 s charger
now must not lead to a second cut.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): the car-first discharge stop has its own test

Removing the PI path's immediate discharge stop left every named test
green; only the golden replay caught it. A peak_shaving loop with
battery_covers_ev off, starting from a 2.9 kW discharge while the house
alone has surplus, now requires that no order discharges into the car.

The comment on the plan back-off said the plan's grid leaves out the car.
It counts the car it planned; the comment now says so.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): the battery rise check reads only live battery power

fitBatteryRisesToFuse, unshownBatteryW and recordBatteryReadings read
the battery's cached RawW, which survives the driver going offline, and
added three direct telemetry reads that the repo-hygiene check refuses.
They now use Store.OnlineRawW, as phaseSample.moveW does: an offline
battery's last value no longer sets the rise base or the shown level.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): judge a raise's landing from the meter's rise

C4 counted a raise as landed only when a reading-to-reading move had a
charger's shape. A slow ramp, or a house load on another phase that moved
in the landing reading, left the whole raise counted as on its way on top
of a reading that already held it, and Core cut a raise that fit under
the line. The rise still to come now reads the meter's own rise since the
raise went out: the smallest across the phases for a three-phase order,
the car's phase for a one-phase car.

For a three-phase order, a move on one phase alone no longer moves the
shown level of a car not yet seen. A load cycling on the phase over the
line took the cut's cover off on each drop and never gave it back, so
Core cut again and again.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): a car not yet seen may take a raise on one phase

The smallest rise across the phases read a one-phase car not yet seen
as a raise that had not landed: its phase rose, the other two did not.
Core then cut the car from 11040 W to 0 with every phase under the line
(field matrix, car1p cases). One phase that has risen alone since the
raise went out, the others within half a step, now counts as that car
taking the raise, as the shape tracker read it before. The changeset
again says what holds: the one-phase house step case is closed for a
car seen on three phases.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): judge a one-phase landing reading by reading

For a car not yet seen on three phases, a raise counted as landed on one
phase only while the other phases stayed within 0.5 A of their reading
when the raise went out. That window spans the charger's whole response
time, so 0.6 A of house drift on another phase made the full raise count
as still to come on top of a reading that already showed it, and Core
cut the car with every phase under the line (field matrix with 0.7 A on
L2: car1p cut 11100 -> 0 W).

Each phase now keeps its rise over the readings in which the other
phases moved less than a step (aloneA). A rise of a step or more there
may be the car on that phase. Drift between readings, or under a step
in the landing reading, no longer hides it; a house load that moves a
step or more on another phase in the same reading still does.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): restart credit keeps room for the car's rise to its max

After a restart Core does not know the offer in force on the charger, so
a car drawing below it may still rise before Core's order lands. The
credit now counts only the draw less that possible rise past the latest
offer, with the rise measured to the loadpoint's max_charge_w; a charger
with no max_charge_w gets no credit.

The charger and output reads move into health-gated telemetry accessors
(OnlineLowerW, SumOnlineHigherW). Tests cover the raw and smoothed
guards, a 10 s OCPP sample cadence on the plant, and the review's car
rising under a 16 A offer in force.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): Charge now landing shown before Core logs its offer

Site rig s1-16, s1-25 and s15-25 failed on c9b52c3: the charger answered
within a second, and the meter reading that showed the car at 15.9 A came
in 7 ms before the tick that first logged the 16 A offer. The reading
could not show an offer logged after it, so the landing counted as a
raise still to come, 15.9 + 16 A passed 1.2 x In, and Core cut 11,040 W
to 5,520 W with 9 A of room on every phase. The same run of the base at
281f9f6, without this branch's commits, fails the same way; #1923's
ab02710, merged here in c0a5274, reads the meter's own rise and fixes
it. This test pins that rig shape.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): restart credit counts no sample newer than the meter

The battery side's restart credit (evFoundDrawW) had two gaps.

A charger sample measured after the site reading counted as part of
it. A car that rose in that gap was credited for draw the meter did
not show yet, and the battery ended its discharge into room the rise
had taken. With a 3 s meter, L2 reached 19.30 A. A sample now counts
only when measured at or before the site reading.

The rise reserve took max_charge_w as the most the unknown offer in
force can be. A charger still on an offer from before a restart that
lowered max_charge_w, or on its own higher default, could rise past
it: 19.00 A per phase on the unit fixture, 19.30 A on the plant. The
reserve now runs to the larger of max_charge_w and the site fuse's
rating.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): restart credit holds against a charger clock behind Core's

The restart credit compared a charger's sample time, stamped by the
charger's own clock (OCPP MeterValues), with the time the site reading
arrived on Core's clock. A charger clock 1 s or more behind Core's let
a rise sampled after the reading count as already in it, and L2 reached
19.30 A on the third review's plant case.

A sample now counts only when stamped evClockAllowance (5 s) before the
reading arrived, and the draw is the lowest of that sample and every
sample since. noteDraw keeps the charger's samples while the restart
window is open.

Also tests the max_charge_w half of the rise cap: a 22 kW charger on a
3 x 25 A fuse keeps the reserve up to max_charge_w.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* docs(control): the fuse margin is opt-in, and only the fuse ceilings move

The SiteFuseSafetyA comment read as if the margin were needed by
default; it now says zero is the default and when to set one. The
changeset named "the site's total import and export limits", which
reads as the hourly import_limit; that limit does not move. It now
names the fuse's import and export ceilings.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): battery beside a minimum-step car holds the fuse line (rig s18-16)

On #1910 and #1891 the battery rises beside the car to the working limit,
the fuse guard cuts it by the overage plus half of safety_margin_a and holds
30 s, and the battery rises again: it hunts between 15.0 and 15.5 A on a
16 A site. Where it stands when the house moves is chance, which is why
rig s18-16 failed 3 of 57 runs on those heads. #1913's cut by the overage
only keeps it on the line.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(config): an unset fuse margin reaches Core as 0

A mutation that restored a hidden 0.5 A margin at startup passed every
suite. This test pins the value newControlStateFromConfig hands Core.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): s18 judges own commands apart from the house's step

At margin 0 Core holds the phases at the 16 A line. Rig s18-16's 0.1 A
house step at small_step then lands over the line until Core cuts: on
fdfbfec the phase read 16.101 A for 3 s and Core cut the battery
4851 -> 4719 W within 2 s. The criterion "own commands stay inside the
rated fuse" counted that stretch as Core's and failed. The owner's rule
judges an overage between In and 1.2 x In by the I2t model.

The criterion now skips the 10 s after the step, the same gap the minor
window already leaves. On the fdfbfec record Core's own commands peak
at 16.008 A before the step and 16.005 A after it, inside 16.01 A.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): no cut of an unseen car, no landing from a 1p house move

Two regressions against #1913 from the final review.

A car the loadpoint has not seen on three phases may draw on one phase
Core does not know. The alone rise (aloneA) missed its landing when any
other phase moved a step in the same reading, so the whole raise counted
as still to come and C4 cut a car with every phase under the line, at
most session starts with a 10 s meter. riseAheadA now takes the largest
rise for such a car, as for a one-phase car whose phase is not known,
and the smallest only once the car is seen on three phases.

A one-phase order never knows the car's phase, so a house load moving
alone on any phase read as its cut landing and took the cover off a cut
still on its way. A one-phase move now counts only on a known car phase.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): judge a restart sample by its arrival, not its stamp

The 5 s clock allowance let the restart credit count a charger sample
taken 5-7 s before the site reading. A car that stopped after that
sample (a fast charger applying the 0 A sent while the meter was stale,
or the car pausing) still counted, the battery ended the discharge the
car's return needed, and L2 reached 21 A on a 16 A fuse when it resumed.

Core now judges a sample by when it first arrived on Core's clock. It
counts as in the reading only when it arrived evMeterDelay (1 s) before
the reading, and no more than one control interval before that. A sample
already there when Core began to watch the charger arrived at a time
Core does not know, so it never counts. The charger's stamp only tells
samples apart, so a charger clock behind Core's no longer matters.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): judge overages at the fuse rating, not fuse - 1 A

At margin 0 the car in s8-60-25 settles at the rating, as the owner's
rule says, and the rig's old 1 A hidden margin failed it: 271 s above
24 A against 67 s allowed, with no second over 25 A. siterig/full has the
same threshold in overage() (s9, s10, s11), the random invariants and
s15bat.

Port #1907's judge hunks: s3, s8, s9-s11, s15bat and the invariants now
count time over the fuse rating. TestS8JudgesAtTheFuse and #1907's
TestInvariantsJudgeAtTheFuse fail on the old judges.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

---------

Co-authored-by: Claude Opus 5.5 <noreply@anthropic.com>
frahlg added a commit that referenced this pull request Oct 28, 2026
…ack #1888, #1907, #1908, #1920, #1922) (#1888)

* fix(control): one log of FTW's own EV offers

The battery side read a 20 s pool log of EV offers (State.evOffers), while
the EV fuse limit keeps each charger's offers for its declared response
time, or 180 s when it declares none. After 20 s the battery counted a slow
charger's unshown raise as already in the meter and charged into that room;
when the car started, a 25 A site read 32.6 A per phase for 3 s.

Delete State.evOffers and its two writers. evInMeterW and
clampEVBatteryHeadroom read evShownW, each charger's latest offer less
what it may not show yet. The hourly peak in stepEVMeterLimit takes each
charger's highest offer of the last evSettle from the same log.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): add P0 rig scenarios R1-R5

Stale meter, battery dropout, the planner floor, a SIGKILL restart and
a start into a running site had no judged rig scenario. Add r1-25 to
r5c-25 with their judges and known lines naming the Wave 1 items (A1,
A3/A4, E1, D6). The rig gains stopFTW(sig), a planner soc_min field, a
charger plugged at start and a delayed Core start. r1-25 is skipped
until device-simulator can silence the site meter.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery fuse guard reads each phase with its direction

Delete perPhaseOverageW, perPhaseOverageReadingW and perPhaseReliefW.
The battery fuse guard, the fuse saver and the forced discharge read the
signed phase currents (phaseCurrentsA, with #1849's sum check and dead
zone), count the batteries' own move on each phase, and relieve to the
car's working limit, the fuse less max(1 A, safety_margin_a).

Item A5 of the stable plan.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery waits only for a declared charger response time

The first A6 change gave the battery side the EV limit's 180 s guess
for every charger that declares no response time. Only Easee Cloud
declares one, so on every other charger the battery reserved the car's
whole demand on top of a reading that already showed the car, and
stopped charging for 3 minutes after each car start or raise. On the
#1868 shape (rig s18) battery charge stayed at 0 W until 180 s.

evShownW now uses the charger's declared power_max_age_s, and evSettle
when it declares none, as master did. Easee Cloud declares 180 s, so the
slow-charger case stays fixed.

Tests: the slow-charger test now declares 180 s, and a new plant test
runs the s18 shape with a fast charger that declares nothing.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): fuse guard reads phases after the hold caps the targets

The guard took the phase relief from the original request, then the 30 s
fuse hold capped that request and the relief came off again. A charge
limited by one phase switched between 1380 W and 0 W on every dispatch.
Predict the aggregate and the phases from the held targets instead.

The phase reader now takes the meter's raw total from OnlineMeterW, the
same reading as its currents, so an offline meter's cached phases drive
no relief. The batteries' raw power is read in one helper. dispatch.go
keeps its 41 cached telemetry reads.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): make R2, R4, R5a and R5b judge what Core does on master

Review fixes for W0-4:

- r4: Core refuses a battery hold over 1800 s, so the 3600 s hold made
  the run error before any kill. Post a 1800 s hold 300 s before the
  first kill; it outlasts both.
- r2: the site stays under 1.2 x the fuse, where Core cuts the car on
  its documented 60 s heat budget (control/fuse_heat.go), not at once.
  Judge that contract: over 1.2 x the fuse at most the charger's delay
  + 7 s, and the 60 s heat under 1.13 x the fuse. Record the time over
  fuse - 1 A and when Core sends the cut.
- r5a: start the battery at its 5 % floor so the site runs 30 A before
  Core starts, check that as setup, and judge against fuse - 0.5 A,
  Core's own line (as r3 does).
- r5b: drop the D6 known line. The saved plan is younger than
  MaxPlanAge and a fresh plan lands within seconds, so the deadline
  reserve never acts and the run does not reach D6.
- r1, r4: Charge now counts as back only once it runs unbroken to the
  next event, so a stop that starts after the restart is seen.
- README: move the r rows off the s17 line #1875 edits.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): judge R2-R5a at the fuse rating, not fuse - 0.5 A or - 1 A

Core's working limit is the fuse rating less safety_margin_a, which is
opt-in (owner rule of 27 Oct). R3 and R5a now judge the overage above
the fuse, R2 and R4 record it there, and the fixtures put Core's own
line at 25.0 A on a 25 A fuse. New cases hold exactly 25.0 A (passes)
and 25.1 A beyond the time budget (fails) for R3 and R5a.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): pin R5a's 3 s clock to the first sample at the fuse

R5a's second criterion now starts its clock at the first sample at or
under the fuse, not under fuse - 0.5 A. So a site that dips to 24.8 A
and then holds 26 A for 10 s fails, where the old judge passed. Add that
case so the clock start cannot drift back.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): the rig's "over the limit" is above the fuse, not fuse - 1 A

Core's working limit per phase is the fuse rating less safety_margin_a,
and the margin is opt-in (owner rule of 27 Oct). The invariants judge,
the overage helper behind S9-S11, S3, S8 and S15bat now count a phase as
over the limit only above the fuse rating. The fuse - 1 A and
fuse - 0.5 A metrics go; the I2 and back-under metrics read at the fuse.
Time budgets stay as they were.

This only loosens the judges, so Core that still holds In - 1 A passes.
Room expectations (S1, S12, the random roomA) stay at fuse - 1 A for now.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): the rig expects the room the fuse rating gives

S1 targets floor(fuse - house) in 1 A steps (8 970 W on 16 A with a 3 A
house, was 8 280 W). S12 counts a cut on room alone while every phase is
under fuse - 0.1 A and records fuse_limit with 6 A of room under the fuse.
The random judge measures Charge now room against the fuse, with the
car's 6 A minimum as the threshold. The stack pins safety_margin_a to 0
so the rig does not depend on Core's default.

This tightens the rig: it passes only once Core works to the rating.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): say S1-16's target is a floor while the battery covers the house

A run on a Core that stops at fuse - 1 A gave the car 9 590 W with the
battery at -5 000 W, above the 8 970 W target. S1-16 does not catch the
old line.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): car and battery-beside-car work to the fuse rating less safety_margin_a

The EV phase limit was In - 1 A, fixed in code. It is now fuseLineA():
In - safety_margin_a, with no floor. A rise moves one step once it fits
under the line, a start takes all the room, and battery charge beside a
car uses the same line. The hour's import limit keeps its own margins.
Starts and per-phase cuts round down to whole charger amps, since
chargers round offers to the nearest amp.

Step 3 (PR b) of the fuse-at-rating plan (owner rule of 27 Oct).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): keep covered offers whole and leave battery relief out of EV room

Two review findings on the fuse-line change:

- A cut rounds to whole charger amps only when a new cut is needed. When
  cuts on their way cover the overage, the offer stays as it is. Rounding
  a kept step-table offer took the car 6200 -> 5500 -> 4800 -> 0 W in 3 s
  on a 0.6 A overage while a 180 s cut travelled.
- Dispatch records the discharge the fuse guard adds to each battery, and
  an EV rise or start does not count it as room. Before, the car rose into
  the relief and the battery fed it 650 W at the line for as long as the
  house load stayed.

The noisy-line sim test now pins the slow one-step cycle at an exact fit
(at most 5 cuts an hour, never a stop) and no moves with part of a step
left, instead of allowing 45 moves an hour.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery fuse guard reads each phase with its direction

Delete perPhaseOverageW, perPhaseOverageReadingW and perPhaseReliefW.
The battery fuse guard, the fuse saver and the forced discharge read the
signed phase currents (phaseCurrentsA, with #1849's sum check and dead
zone), count the batteries' own move on each phase, and relieve to the
car's working limit, the fuse less max(1 A, safety_margin_a).

Item A5 of the stable plan.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): fuse guard reads phases after the hold caps the targets

The guard took the phase relief from the original request, then the 30 s
fuse hold capped that request and the relief came off again. A charge
limited by one phase switched between 1380 W and 0 W on every dispatch.
Predict the aggregate and the phases from the held targets instead.

The phase reader now takes the meter's raw total from OnlineMeterW, the
same reading as its currents, so an offline meter's cached phases drive
no relief. The batteries' raw power is read in one helper. dispatch.go
keeps its 41 cached telemetry reads.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery relieves to the fuse less safety_margin_a

phaseFuseReliefW now reads fuseLineA(), the line the car uses since the
EV change, instead of max(1 A, safety_margin_a). There is no floor under
the margin: at margin 0 the battery works to the fuse rating.

Tests return to the rating where they had moved to the 1 A limit, and a
new property test covers In x phases x margin in both directions.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): re-record golden records at the fuse less safety_margin_a

Replayed from stored inputs; only records whose dispatch changed against
the parent branch were replaced.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery fuse cut lands on the line, not half a margin below

applyFuseGuard cut a battery charge or discharge by the overage plus
half of safety_margin_a. The guard now predicts from the held targets
and keeps its 30 s hold, so the extra cut only parked the phase below
the line the user set. Cut by the overage only.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* docs(changeset): name the limit the battery cut lands on

The changeset said the phase lands on the fuse less safety_margin_a.
On #1891 as it stands, the phase line is the fuse less max(1 A,
safety_margin_a), so at the 0.5 A default a 16 A phase settles at
15 A, not 15.5 A. Say what this PR changes, cutting only by the
overage, without naming a line that depends on step 4.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(config): fuse safety_margin_a defaults to 0

Core now works to the fuse rating unless a site sets a margin. Every
explicit safety_margin_a is kept. A stored value of exactly 0.5 A, the
old default, adds one load-time notice and changes nothing.

The peak-limit error names the margin only when it is above 0, and the
settings field shows 0 with help that says the margin is opt-in.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* docs(changeset): say what the default change moves on its own

The changeset said FTW works to the fuse rating unless a site sets a
margin. On this PR's base every per-phase line still sits 1 A under the
rating; that holds only once #1910 and the step-4 amendment of #1891
land. The changeset now names what this PR changes: the default, and
the whole-site import and export limits.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): relief stays at the line after a PV drop (C3, seed 207533)

On a 16 A fuse with no margin the battery holds 3 kW of discharge with L1
at 14.4 A; PV drops 1280 W and L1 reads 16.3 A. The relief must bring L1
to 16 A and keep it there while the reading sits at the line with the
battery at its relief power. Without phaseFuseReliefW's own-move count
the relief flips between -3214 W and -3005 W on every tick and L1 crosses
the rating 13 times; with it, L1 crosses once.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): judge random runs by rig items R2-R7 of the 27 Oct triage

The random judge called eight nightly seeds on master 83c2b24 wrong in
ways the triage traced to the judge, not to Core:

- R2: a stretch over the fuse took only the windows open at its first
  sample. Every window that opens inside it while it is still allowed
  now extends it, a Core restart included (207530, 207539).
- R3: the battery counted as the 2 s lever while its inverter was
  offline or had no spare power. It is the lever only while it runs,
  is above its floor and its spare power covers the overage; otherwise
  the charger, at max(2, command_response_s) (207530, 207534, 207539).
- R4: a car that starts on the charger's own default, or on an order
  still on its way, is a step FTW did not take, answered by the charger
  from draw start + max(2, command_response_s) + 5 s. A stretch is
  FTW's own only after FTW's last change to the car's order was a rise,
  or its battery order moved toward import (207532, 207534, 207537).
- R5 (owner rule): between the fuse and 1.2 x the fuse a phase counts
  only once Core's 60 s I2 heat is over the fuse too; above 1.2 x at
  once (207536). r3 and r5a take the same heat budget (#1888 review).
- R6: idle seconds with room under Charge now are counted from when the
  room appears and may last evRestartDwell + command + startup + a tick
  (+ 2 s meter and tick + 3 s). The count starts again on a Charge now
  that changes the request, on each FTW cut and when Core answers after
  a restart. Only meter and charger faults excuse the car.
- R7: the floor judges FTW's own orders (status.dispatch), not the
  inverter register, against max(inverter floor, planner soc_min) with
  no +0.5 %.

TestJudge now also judges the random seeds a results directory holds,
from each run's plan.json, so a nightly run can be judged again.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): tighten the random judge after review of #1920

- A stretch over the fuse that no outside change explains is FTW's own
  again (3 s after the heat clock), in either direction. The guess that
  it was a step let export raises and warm fuses split by short dips
  pass. ownRise is gone: with that rule it decided nothing.
- A window that opens inside FTW's own raise no longer turns it into a
  step; only a step's stretch grows.
- Charge now: a cut no longer restarts the idle count. A cut FTW had
  to make stops the car, and the count starts when the car stops; a cut
  with room is FTW's doing. The restart on Core's return was dead (the
  down mask already resets the count).
- The battery lever uses the floor the floor check uses (max of the
  inverter floor and the planner soc_min). At the floor it can only
  charge less.
- Only a meter fault adds its length to a step's time. An inverter
  outage takes the battery lever away; a charger outage delays the
  charger lever by what is left of it.
- New check (R8, C1): a forced battery mode FTW does not dispatch lasts
  at most 10 s once the inverter and Core are back.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): phase relief reads each battery live, in the decision's reading

The merge of #1876 moved stopPhaseReliefW's live reads into
phaseSample.moveW. Pin it: a battery that went offline, moved on to a
newer reading or has no reading gives no phase relief. With the cached
RawW read #1891 had, the offline and newer-reading cases relieve 2310 W
and the no-reading case counts a 2000 W charge from 0 W.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery relief holds when the battery's reading lags the meter

The phase relief counts the battery's move from its own reading. When
that reading lags the meter by a tick, the meter already shows the relief
while the reading does not, so the relief came off; on the next tick it
went back on top of the reading's catch-up. In the 207533 shape (16 A,
margin 0) with a one-tick lag the order ran -3214, -3005, -3422, -3005,
... -5717 W and L1 went back to 16.3 A on every other tick: 13 crossings.

A move from the battery's last command (the one it got in the last
dispatch) may now not pass the room the meter shows either. That bound
only tightens, and a phase already over the line gives it no room, so it
never asks for more than to stay at the last command: a battery that
falls short of its order does not wind it up. With lag 1 or 2 the order
holds -3214 W with L1 at 16.0 A and one crossing, on the PV step.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): R8 counts a forced battery from when Core has the inverter back

The random judge's R8 check counted 10 s from the inverter's return. The
Modbus reconnect backoff (up to 60 s) holds Core's first good read back,
so the check could not pass even with C1 fixed (207539: 55.7 s).

The count now starts at Core's first good read of the inverter after an
outage or a restart, at the latest 60 s after the return. After an outage
it allows the registry's 30 s default retry (defaultRetryMax) until #1915
(C11) lands. While Core is stopped with SIGTERM, a running inverter must
leave its forced mode within 10 s of the stop: the driver cleanup writes
the default (triage item 10).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): R8 records the seconds Core's timers excuse

Review of #1922. The judge forgives the Modbus reconnect backoff (up
to 60 s) and the registry's default retry (up to 30 s) after a return,
while the triage line is 10 s from the return. result.json now records
those seconds as battery_forced_in_core_timers_s, so a pass such as
207539's (123 s) shows what was forgiven.

TestForcedAllowancesMatchCore reads both timers from Core's source and
fails once the registry retries the default on the first good poll
(#1915, C11) while defaultRetryMaxS is still 30.

Two R8 cases pin the judge's clock: an inverter that is back while Core
is down counts from Core's first read, and a second outage counts from
its own return.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): a landed EV cut covers nothing later; a raise that no longer fits comes off

The site meter now tells Core how much of a charger's offers it already
shows. A move shaped like an order landing (every phase alike, or one
phase alone for a one-phase car) moves that level toward the latest
offer. A cut the meter shows no longer covers an overage that an outside
step causes after it, and no longer nets against a raise sent after it.
Where a landing and a house step fall in one reading, a cut covers a
phase that has risen since only up to the overage it had then.

C4: our own rise on its way, as the meter tells it, is judged as the
reading it will make. Above 1.2 x In, or over the line on a phase whose
heat budget is spent, it comes off on this reading, down to the line.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): a one-phase house move is not the car's cut landing

seeOffers kept one shown level for every phase, so a house load moving on
one phase alone read as a three-phase cut landing and took the cut's cover
off the phase it was sent for. With a 40 s charger Core then stacked a
second cut and left L1 2 A under the line for over 2 min. The shown level
is now kept per phase: a three-phase order moves every phase alike, and a
phase that moves alone moves only its own level.

The loadpoint now reports a car it has seen draw on all three phases as
CarPhases 3. For such a car a one-phase move is never the car, so a house
step on one phase while a raise travels no longer hides the raise, and C4
cuts on that reading.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): a battery charge rise fits each phase before it is sent

The battery fuse guard judged a rise from the battery's own reading and
the meter's phases, so it took a rise the meter did not show yet as
already shown. With the meter a poll behind the battery, a PV surplus that
grew each tick stacked rises past the line, then the relief cut them back:
16.4 A on a 16 A fuse and a charge that rose and fell (C2, seeds 207530,
207535).

fitBatteryRisesToFuse caps charge above the battery's latest order to
(fuseLineA - worst phase - own unshown rises) x V x phases. The unshown
rises are the battery's orders of the last evSettle and the chargers'
raises, counted as evShownW counts them, so the car comes first. Holding
an order is never a rise and the check never cuts; an overage stays with
the relief. No margin and no floor: the order ends at the line.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery rise check counts slow batteries and direction-less phases

A battery order now stays unshown until evSettle after the battery's own
reading reaches it, so a battery that ramps slower than evSettle no longer
gets a second rise on top of an order the meter cannot show yet.

On a meter with phase currents but no phase power while the total
exports, a phase counts as export only when the other phases cannot
carry the export alone; any other phase counts as import. Before, every
phase flipped to export, so a three-phase charge could rise into a phase
that imports beside two exporting ones.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): the car comes before battery charge

With battery_covers_ev off, dispatch took the car out of the meter
reading before the battery decided. The battery then saw the PV the
car was using as export and charged from it while the site imported
for the car (rig seeds 207535, 207539, 207530: about 10 kW import).

The battery now charges only from the surplus the meter shows after
the car. Where the house alone has surplus, the battery sees the meter
with the car included, and any discharge stops at once, since it would
feed the car. A planned PV charge on the energy path takes only the
surplus the car leaves; a planned grid purchase keeps its charge.
Cover off still never discharges the battery for the car.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): peak shaving drops a running charge for the car

Manual peak_shaving gave zero error for any import under the peak
limit, so a battery charge that was running when the car started held
while the site imported for the car, with battery_covers_ev on or off.
When the site imports while the car and the battery both charge, the
charge now comes down by the import, to 0 at most. Under the peak limit
the battery still never discharges.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): after a restart the battery credits the car the meter shows

After a restart, the 0 A orders FTW sent while the meter was stale counted
as the EV base the meter shows. With the car still drawing 8.2 kW from
before, a new 6.2 kW order then counted as a 9 A rise to come, and the
battery was held in discharge for the car (seed 207532).

Until a charger's first order of this run can have landed, the battery
side now counts the charger's live measured draw as in the reading, never
above the latest order and never above the consumption the site meter
shows. The car's own limit does not read it.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): credit a found car only from a current charger sample

Review of #1926 found two ways the restart credit let the battery end a
discharge into room the car's pending rise still needs:

- The charger reading counted with no check that it was current. A held
  reading after a failed poll, or a sample older than the site reading,
  could show a car that a fast charger had already stopped. The draw now
  counts only when the last poll succeeded and the charger measured it
  within one control interval of the site reading.
- The consumption bound subtracted the smoothed battery, PV and V2X
  values, which lag an output that just fell. It now takes the higher of
  raw and smoothed for each, so the bound stays at or below what the
  meter shows.

New tests pin both, plus the shown-offer subtractions and a window that
outlasts evSettle.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): run the site sim at the new 0 A default margin

simFuseSafetyA follows the config default, now 0. fitScenario takes the
room under the line and sets the house from simFuseSafetyA, so its exact
fit stays twelve whole steps at any margin. "charger's own load
balancer" passes at margin 0, so its known line goes.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* docs(changeset): say what margin 0 moves once the fuse stack lands

With the stack under it, the default moves the car's and the battery's
per-phase line as well as the site totals. 0.5 A stops being the
default, so #1910's changeset no longer calls it that.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): keep the load-balancer bug as a known line above the line

At the 0 A default the scenario passes only because the charger's own
balancer sits at 25 A, the rating and so the line. The bug is still in
Core: a cut comes off an offer the car does not draw. Two known variants
keep it tracked and turn red once it is fixed: the stored 0.5 A margin
(over 24.5 A for more than 11 s) and a balancer at 25.5 A at margin 0
(over 25 A for more than 11 s).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): EV room reads battery relief through live telemetry

evFuseReliefW read each battery's cached RawW, which survives a driver
going offline. It now reads Store.OnlineRawW. A battery with no live
reading counts its whole recorded relief, so the car never builds on
discharge Core can no longer hold.

fuseSaverEarlyExit read each battery's SmoothedW a second time to record
relief. It now records against the live snapshot the fuse-saver decision
already took (fleetAtLivePower), so it adds no read of its own.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): only a rise extends a stretch; raises after a step are FTW's

Second review of #1920:

- A house event that is no fault extends a step's stretch only if the
  worst phase rose 0.5 A or more within 3 s. Load events that change
  nothing and the inverter's own return no longer chain the allowance.
- The inverter is back at the end of its outage, so at its return the
  battery is the 2 s lever, not the charger.
- A window does not explain a stretch if FTW raised the car after the
  window's meter delay and before the stretch: FTW's raise after a step
  or after a Core restart is its own.
- A stretch stays open across dips while a phase's heat is over the
  fuse, so a warm fuse held 3 s over and 1 s under fails. A window that
  opens after the allowance, with no over second in between, still gives
  a new step its own time.
- Tests pin the export lever, the heat clock for steps and the 60 s
  restart window.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): a raise over the fuse on import is FTW's own

The random judge credited FTW's own raises to a step in three shapes
from the third review of #1920:

- a car raise sent while a step's import stretch was over the fuse
  passed as part of the step;
- a house event that changed nothing, opening as that raise landed,
  took the rise and gave the stretch a fresh lever time;
- a battery charge raise after a Core restart or a step's meter delay
  was never counted (triage C2), so the restart window excused it.

For import, a window no longer explains a stretch when FTW raised the
battery's charge after the window's meter delay and before the stretch,
or raised the car or the battery while the stretch was over the fuse.
A raise in a dip under the fuse still counts as allowed, a battery
order moved while the inverter is off reaches no battery, and raising
the car into export stays the right answer.

The 10 recorded seeds keep every verdict and allowance.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): an offline battery's fuse relief ends after evSettle

With no battery online, ComputeDispatch returns before it records relief,
so batteryFuseRelief kept its last value and evFuseReliefW counted all of
it for as long as the battery stayed offline. The car was held up to the
whole relief below the line. The relief now counts in full until the
default mode Core sent at the transition can have reached the meter
(evSettle), then ends.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): judge FTW's battery orders as the inverter sees them

Fourth review of #1920 (4985523):

- A missing status.dispatch (Core down, or before its first tick) keeps
  the last order, as the inverter does, instead of reading as 0 W. A
  charge order restored after a restart is no raise.
- A battery move counts from 0.5 A a phase (345 W), as raisedAt does,
  so a one-sample closed-loop wobble is no raise.
- A car raise before a stretch makes it FTW's own only on import.
- On export, a battery order moved toward export after a window's
  meter delay, or while the stretch is over the fuse, makes the
  stretch FTW's own, so a Core restart no longer excuses it.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): each offline battery's fuse relief ends after evSettle

The expiry in 8150b45 ran only when no battery was online. With a
second battery online, an offline battery's relief stayed until a
recorded dispatch rewrote the map: never while the legacy modes sat in
the deadband, and on the first tick when one did record, so the car
could rise onto discharge Core ordered a second earlier. Each offline
battery now has its own clock: its relief counts whole for evSettle
and then ends, on every dispatch path. A battery back online leaves the
clock, so its next offline period counts whole again; a test now covers
that reset.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery phase relief neither pins mixed phases nor winds up

The last-command bound held the battery at its last command when one
phase sat at the import line and another was over the export line: the
guard cut the discharge for the exporting phase and the bound put it
back. Now the bound gives way on one side while any phase is over the
other side's line, and phaseFuseReliefW's least-over move decides.

When the meter does not show the battery's move (a frozen meter, or a
worst phase a one-phase battery cannot reach), each tick added the same
overage again and the order ran out to the discharge limit. Now the
relief toward the worst phase stops at the last command once the
batteries' raw power has moved one ampere per phase since the worst
phase last moved by half an ampere. One ampere is the step in which P1
meters report phase current.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery phase anti-windup stops only when the meter cannot show the move

phaseUnresponsive stopped the relief whenever the batteries had moved
690 W and the worst phase had not moved half an ampere. On a live meter
that also happens when a load cancels the move (a balanced load starting
with the relief step, or a slow rise on the worst phase), and when the
battery's reading catches up with an order the meter already showed.
The relief then held over the line with no end.

Now it stops only when the meter repeats its phases exactly while the
batteries moved one ampere per phase, or when another phase moved by
twice the balanced share of that move (a battery off the worst phase).
The repeat is measured from the reading the meter last changed in, so a
meter that freezes on any reading is still caught.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery off the worst phase goes back, and a stale reference ends

Fourth review of the phase anti-windup (c066892):

- The worst phase's reference had no end while that phase sat over the
  line. A relief that follows a slow drift keeps it there, so the
  reference stayed while the battery moved hundreds of watts, and a load
  that later switched off on another phase read as a battery off the
  worst phase. The relief then held L1 up to 0.49 A over the line with no
  time limit. The reference now also ends when the worst phase is at or
  inside the line, or when another phase becomes the worst.
- An off-phase verdict no longer holds the last command. The batteries go
  back to their power when the worst phase last moved: what they moved
  since did not reach it. A one-phase battery no longer holds its own
  phase at -17.97 A for the whole overage (and -19.83 A, past 1.2 x In,
  when PV returns). A false verdict on a balanced battery moves the
  worst phase by at least one ampere on the next reading, which ends the
  reference, so it costs one tick instead of an open-ended hold. The
  verdict holds until the reference ends, so the relief does not go out
  again once the battery is back.
- The frozen-meter test now also compares the meter's total. A P1 meter
  reports whole amperes, so a live meter can repeat its phases while its
  total moves; that latched the relief at 1.11 x In.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): the drift test also wants no verdict on the load change

With L1 at the line ending the reference, no off-phase verdict comes when
the load on L3 switches off. Without it, the step back still ends the
hold, but with L1 at 16.8 and 17.7 A for two ticks; the test now sees
that.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): our battery order's move is not the car's cut landing

The guard in seeOffers that stops reading the meter while our battery
order moves had no test; removing it left every test green. A battery
order that lands and goes back while a cut travels to a 40 s charger
now must not lead to a second cut.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): the car-first discharge stop has its own test

Removing the PI path's immediate discharge stop left every named test
green; only the golden replay caught it. A peak_shaving loop with
battery_covers_ev off, starting from a 2.9 kW discharge while the house
alone has surplus, now requires that no order discharges into the car.

The comment on the plan back-off said the plan's grid leaves out the car.
It counts the car it planned; the comment now says so.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): the battery rise check reads only live battery power

fitBatteryRisesToFuse, unshownBatteryW and recordBatteryReadings read
the battery's cached RawW, which survives the driver going offline, and
added three direct telemetry reads that the repo-hygiene check refuses.
They now use Store.OnlineRawW, as phaseSample.moveW does: an offline
battery's last value no longer sets the rise base or the shown level.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): judge a raise's landing from the meter's rise

C4 counted a raise as landed only when a reading-to-reading move had a
charger's shape. A slow ramp, or a house load on another phase that moved
in the landing reading, left the whole raise counted as on its way on top
of a reading that already held it, and Core cut a raise that fit under
the line. The rise still to come now reads the meter's own rise since the
raise went out: the smallest across the phases for a three-phase order,
the car's phase for a one-phase car.

For a three-phase order, a move on one phase alone no longer moves the
shown level of a car not yet seen. A load cycling on the phase over the
line took the cut's cover off on each drop and never gave it back, so
Core cut again and again.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): a car not yet seen may take a raise on one phase

The smallest rise across the phases read a one-phase car not yet seen
as a raise that had not landed: its phase rose, the other two did not.
Core then cut the car from 11040 W to 0 with every phase under the line
(field matrix, car1p cases). One phase that has risen alone since the
raise went out, the others within half a step, now counts as that car
taking the raise, as the shape tracker read it before. The changeset
again says what holds: the one-phase house step case is closed for a
car seen on three phases.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): judge a one-phase landing reading by reading

For a car not yet seen on three phases, a raise counted as landed on one
phase only while the other phases stayed within 0.5 A of their reading
when the raise went out. That window spans the charger's whole response
time, so 0.6 A of house drift on another phase made the full raise count
as still to come on top of a reading that already showed it, and Core
cut the car with every phase under the line (field matrix with 0.7 A on
L2: car1p cut 11100 -> 0 W).

Each phase now keeps its rise over the readings in which the other
phases moved less than a step (aloneA). A rise of a step or more there
may be the car on that phase. Drift between readings, or under a step
in the landing reading, no longer hides it; a house load that moves a
step or more on another phase in the same reading still does.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): restart credit keeps room for the car's rise to its max

After a restart Core does not know the offer in force on the charger, so
a car drawing below it may still rise before Core's order lands. The
credit now counts only the draw less that possible rise past the latest
offer, with the rise measured to the loadpoint's max_charge_w; a charger
with no max_charge_w gets no credit.

The charger and output reads move into health-gated telemetry accessors
(OnlineLowerW, SumOnlineHigherW). Tests cover the raw and smoothed
guards, a 10 s OCPP sample cadence on the plant, and the review's car
rising under a 16 A offer in force.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): Charge now landing shown before Core logs its offer

Site rig s1-16, s1-25 and s15-25 failed on c9b52c3: the charger answered
within a second, and the meter reading that showed the car at 15.9 A came
in 7 ms before the tick that first logged the 16 A offer. The reading
could not show an offer logged after it, so the landing counted as a
raise still to come, 15.9 + 16 A passed 1.2 x In, and Core cut 11,040 W
to 5,520 W with 9 A of room on every phase. The same run of the base at
281f9f6, without this branch's commits, fails the same way; #1923's
ab02710, merged here in c0a5274, reads the meter's own rise and fixes
it. This test pins that rig shape.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): restart credit counts no sample newer than the meter

The battery side's restart credit (evFoundDrawW) had two gaps.

A charger sample measured after the site reading counted as part of
it. A car that rose in that gap was credited for draw the meter did
not show yet, and the battery ended its discharge into room the rise
had taken. With a 3 s meter, L2 reached 19.30 A. A sample now counts
only when measured at or before the site reading.

The rise reserve took max_charge_w as the most the unknown offer in
force can be. A charger still on an offer from before a restart that
lowered max_charge_w, or on its own higher default, could rise past
it: 19.00 A per phase on the unit fixture, 19.30 A on the plant. The
reserve now runs to the larger of max_charge_w and the site fuse's
rating.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): restart credit holds against a charger clock behind Core's

The restart credit compared a charger's sample time, stamped by the
charger's own clock (OCPP MeterValues), with the time the site reading
arrived on Core's clock. A charger clock 1 s or more behind Core's let
a rise sampled after the reading count as already in it, and L2 reached
19.30 A on the third review's plant case.

A sample now counts only when stamped evClockAllowance (5 s) before the
reading arrived, and the draw is the lowest of that sample and every
sample since. noteDraw keeps the charger's samples while the restart
window is open.

Also tests the max_charge_w half of the rise cap: a 22 kW charger on a
3 x 25 A fuse keeps the reserve up to max_charge_w.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* docs(control): the fuse margin is opt-in, and only the fuse ceilings move

The SiteFuseSafetyA comment read as if the margin were needed by
default; it now says zero is the default and when to set one. The
changeset named "the site's total import and export limits", which
reads as the hourly import_limit; that limit does not move. It now
names the fuse's import and export ceilings.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): battery beside a minimum-step car holds the fuse line (rig s18-16)

On #1910 and #1891 the battery rises beside the car to the working limit,
the fuse guard cuts it by the overage plus half of safety_margin_a and holds
30 s, and the battery rises again: it hunts between 15.0 and 15.5 A on a
16 A site. Where it stands when the house moves is chance, which is why
rig s18-16 failed 3 of 57 runs on those heads. #1913's cut by the overage
only keeps it on the line.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(config): an unset fuse margin reaches Core as 0

A mutation that restored a hidden 0.5 A margin at startup passed every
suite. This test pins the value newControlStateFromConfig hands Core.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): s18 judges own commands apart from the house's step

At margin 0 Core holds the phases at the 16 A line. Rig s18-16's 0.1 A
house step at small_step then lands over the line until Core cuts: on
fdfbfec the phase read 16.101 A for 3 s and Core cut the battery
4851 -> 4719 W within 2 s. The criterion "own commands stay inside the
rated fuse" counted that stretch as Core's and failed. The owner's rule
judges an overage between In and 1.2 x In by the I2t model.

The criterion now skips the 10 s after the step, the same gap the minor
window already leaves. On the fdfbfec record Core's own commands peak
at 16.008 A before the step and 16.005 A after it, inside 16.01 A.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): R8 reads Core's reconnect backoff from source

The judge's reconnectBackoffMaxS was a fixed 60 s, checked against
modbus/client.go. #1930 cuts Core's cap to 10 s, so the check would
fail whichever of the two lands second. The judge now reads the cap
from the source the rig builds Core from, and the 207539 shapes are
set relative to it. The unit tests pass with 60 s and with #1930's
10 s applied.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): no cut of an unseen car, no landing from a 1p house move

Two regressions against #1913 from the final review.

A car the loadpoint has not seen on three phases may draw on one phase
Core does not know. The alone rise (aloneA) missed its landing when any
other phase moved a step in the same reading, so the whole raise counted
as still to come and C4 cut a car with every phase under the line, at
most session starts with a 10 s meter. riseAheadA now takes the largest
rise for such a car, as for a one-phase car whose phase is not known,
and the smallest only once the car is seen on three phases.

A one-phase order never knows the car's phase, so a house load moving
alone on any phase read as its cut landing and took the cover off a cut
still on its way. A one-phase move now counts only on a known car phase.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): judge a restart sample by its arrival, not its stamp

The 5 s clock allowance let the restart credit count a charger sample
taken 5-7 s before the site reading. A car that stopped after that
sample (a fast charger applying the 0 A sent while the meter was stale,
or the car pausing) still counted, the battery ended the discharge the
car's return needed, and L2 reached 21 A on a 16 A fuse when it resumed.

Core now judges a sample by when it first arrived on Core's clock. It
counts as in the reading only when it arrived evMeterDelay (1 s) before
the reading, and no more than one control interval before that. A sample
already there when Core began to watch the charger arrived at a time
Core does not know, so it never counts. The charger's stamp only tells
samples apart, so a charger clock behind Core's no longer matters.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): judge overages at the fuse rating, not fuse - 1 A

At margin 0 the car in s8-60-25 settles at the rating, as the owner's
rule says, and the rig's old 1 A hidden margin failed it: 271 s above
24 A against 67 s allowed, with no second over 25 A. siterig/full has the
same threshold in overage() (s9, s10, s11), the random invariants and
s15bat.

Port #1907's judge hunks: s3, s8, s9-s11, s15bat and the invariants now
count time over the fuse rating. TestS8JudgesAtTheFuse and #1907's
TestInvariantsJudgeAtTheFuse fail on the old judges.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): cap a stretch's events by the fuse heat; a car cut into export is FTW's own

Owner decisions of 28 Oct 2026 for the random judge:

- A car cut FTW sends that pushes export over the fuse is FTW's own, as
  a battery move toward export already was: after a step's meter delay
  and before the stretch, or while the stretch is over the fuse.
- What events add to a stretch (R2 growth) stops at the fuse's heat
  budget: once a phase's 60 s heat passes the fuse, Core's cut gets its
  lever's time and no further event extends the stretch. A window that
  opens after the allowance ran out, with the current under the fuse
  since, is a new step and its cap runs from it. This closes E3 (small
  real rises chaining a stretch's allowance).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

---------

Co-authored-by: Claude Opus 5.5 <noreply@anthropic.com>