fix(config): fuse safety_margin_a defaults to 0 - #1914

Merged
frahlg merged 14 commits into
ev-base-after-restartfrom
d-fuse-margin-default-0
Oct 28, 2026
Merged

frahlg merged 14 commits into
ev-base-after-restartfrom
d-fuse-margin-default-0

Conversation

@frahlg

@frahlg frahlg commented Oct 27, 2026 •

Copy link
Copy Markdown
Member

This PR is step 6 (PR d) of the fuse-at-rating plan (owner rule of 27 Oct). Each phase's working limit is the fuse rating less safety_margin_a. The margin is opt-in and defaults to 0, and nothing holds amps back below that line.

Final review fix (2b30933b)

Blocking: siterig/short went red at margin 0 on s8-60-25 as well as s18-16, because the rig still judged at fuse - 1 A. This PR now carries #1907's judge hunks (see Change). On this head: make verify clean (Docker unavailable, so the avahi and release-context runs were skipped), go test -race ./internal/control/ ./cmd/ftw/ ./internal/configreload/ and the hygiene scripts pass. siterig/short has not run on this head yet; the runner does that.

Merge order

This PR sits on top of the fuse stack and lands last. Its base is ev-base-after-restart (#1926). Merge in this order:

  1. fix(control): car and battery work to the fuse rating (fuse stack #1910, #1891, #1913, #1923, #1924, #1925, #1926, #1914) #1910 b-ev-fuse-line-at-rating: the car's line moves to the rating less safety_margin_a.
  2. fix(control): battery fuse guard reads each phase with its direction #1891 a5-battery-fuse-signed-phases: battery relief uses the same line, with no 1 A floor.
  3. fix(control): battery fuse cut lands on the line, not half a margin below #1913 c-battery-fuse-no-buffer: the battery cut lands on the line.
  4. fix(control): a landed EV cut covers nothing later; a raise that no longer fits comes off #1923 ev-cut-landed-and-unshown: a cut the meter already shows covers nothing later.
  5. fix(control): a battery charge rise fits each phase before it is sent #1924 battery-rise-per-phase-cap: a battery charge rise fits each phase before it is sent.
  6. fix(control): the car comes before battery charge #1925 car-before-battery-charge: the car comes before battery charge.
  7. fix(control): after a restart the battery credits the car the meter shows #1926 ev-base-after-restart: after a restart the battery credits the car the meter shows.
  8. This PR.

Two PRs off master must land before this one:

#1907 need not land first: this PR carries its judge hunks (see Change).

When this PR is retargeted and origin/master is merged in, go/cmd/ftw/main.go conflicts in the reload block. Take master's side: this PR's only main.go change is a comment in that block, and the block now lives in go/internal/configreload/apply.go. Then reword apply.go's "nil → 0.5, explicit 0 → disabled" (line 88 on master) to "nil → 0 (work to the fuse rating), an explicit value wins". Review's trial merge on a5cdeae, with master's main.go taken, builds, vets, and passes go test on cmd/ftw, configreload and config.

In the same retarget merge, add the reload-path test below as go/internal/configreload/apply_fuse_margin_test.go. It cannot land before then: this branch has no configreload package, and its reload block is a closure inside main(). Without it, a hidden 0.5 A default put back on reload passes every suite (review's mutation, after ctrl.SiteFuseSafetyA = newCfg.Fuse.EffectiveSafetyMarginA(): if newCfg.Fuse.SafetyMarginA == nil { ctrl.SiteFuseSafetyA = 0.5 }). I checked it on a copy of master (573d24f) with DefaultFuseSafetyMarginA = 0: it passes under -race, and with that mutation in apply.go it fails with "margin after reload = 0.5 A, want 0 A". It also fails if the reload stops setting the margin, since Core starts at 0.5 A.

apply_fuse_margin_test.go
package configreload

import (
	"sync"
	"testing"

	"github.com/srcfl/ftw/go/internal/config"
	"github.com/srcfl/ftw/go/internal/control"
)

// A reload with no fuse.safety_margin_a works to the fuse rating, the same as
// startup; an explicit margin still wins. Core starts at 0.5 A so a reload
// that leaves the old value in place, or puts a hidden default back, fails.
func TestApplyUnsetFuseMarginReloadsAsZero(t *testing.T) {
	half := 0.5
	for _, tc := range []struct {
		name   string
		margin *float64
		want   float64
	}{
		{"unset", nil, 0},
		{"explicit 0.5 A", &half, 0.5},
	} {
		t.Run(tc.name, func(t *testing.T) {
			var cfgMu sync.RWMutex
			var ctrlMu sync.Mutex
			cfg := &config.Config{}
			cfg.Fuse.MaxAmps = 16
			cfg.Fuse.Voltage = 230
			cfg.Fuse.Phases = 3
			cfg.Fuse.SafetyMarginA = &half

			ctrl := control.NewState(0, 50, "meter")
			ctrl.SiteFuseSafetyA = 0.5

			newCfg := *cfg
			newCfg.Fuse.SafetyMarginA = tc.margin
			Apply(&cfgMu, cfg, &ctrlMu, ctrl, &newCfg, nil)

			if ctrl.SiteFuseSafetyA != tc.want {
				t.Fatalf("margin after reload = %v A, want %v A", ctrl.SiteFuseSafetyA, tc.want)
			}
		})
	}
}

When each PR squash-merges, move the next one's base to master, then merge origin/master into it and push. The push matters: see "CI on the stack" below.

Land #1910 and #1891 close together. On #1910 alone the rig's siterig/short fails s18-16 ("battery yields before the minimum-step car"); it passes on master and on #1891 and everything above it.

Sync (28 Oct, 09:00)

#1913 gained 358da3b at 08:01 (a test only: the battery beside a minimum-step car holds the fuse line, rig s18-16). I merged it up the stack, each step a plain merge with no conflict, pushed fast-forward:

PR Branch New head
#1923 ev-cut-landed-and-unshown a059b6a
#1924 battery-rise-per-phase-cap 48fb649
#1925 car-before-battery-charge 5c9c336
#1926 ev-base-after-restart b82e44d
#1914 d-fuse-margin-default-0 0befc58

TestBatteryBesideMinimumCarHoldsTheFuseLine passes at each step. At margin 0.5 A (#1923 to #1926) the battery holds 4473..4485 W and the peak phase is 15.59 A. On this branch, at margin 0, it holds 4818..4830 W, drops 4824 → 4756 W across the house step, and the peak phase is 16.09 A.

This branch now holds the current tips of #1910 (ddab122), #1891 (b36e951), #1913 (358da3b), #1923, #1924, #1925 and #1926, plus master through 7840c33. git branch -r --merged HEAD lists every stack branch.

The earlier sync (28 Oct, morning) merged ev-base-after-restart at 551febd. Only #1910's changeset conflicted. The merge kept #1910's new sentence on an offline battery's relief and kept "a 0.5 A margin" in place of "the default 0.5 A margin".

The earlier restack (28 Oct, night) merged #1891's tip up the stack. Only #1924 conflicted, in dispatch.go. The merge kept signedPhasesA, dropped signedA, and replaced phaseMoveW with phaseSample.moveW. The merge commit e2faf1e explains the resolution.

Problem

An unset fuse.safety_margin_a resolved to 0.5 A. Every line built on it sat 0.5 A per phase (345 W on 3 × 230 V) under the fuse, though nobody had asked for a margin. That covered the car's and the battery's per-phase line (after #1910 and #1891) and the aggregate ceilings: the guard, the joint EV/battery allocator, the PV export guard and the peak-limit ceiling. The settings form showed 0.5, and its help promised headroom. The peak-limit error always named "a 0.0 A safety margin", even when there was none.

This PR was first blocked: on #1910 alone, margin 0 made TestSiteSimRandomHouse/1 fail. An EV cut the meter already showed kept covering a later house step, so Core cut one step and stopped. #1923 fixes that, and seed 1 passes on this branch.

Change

  • go/internal/config/config.go: DefaultFuseSafetyMarginA = 0. The pointer stays, so any explicit value, 0 included, still wins. The field and resolver comments say the margin is opt-in.
  • Stored configs (owner decision): FTW keeps every explicit value. When the loaded value is exactly 0.5 A, loading adds one notice on the retired-setting channel (c.Retired, logged once at startup): "fuse.safety_margin_a is 0.5 A, FTW's old default. FTW now works to the fuse rating. Set 0 to use it." Both load paths (YAML and stored settings) do this. It changes no stored state, and DropRetiredSettings leaves the value alone.
  • go/internal/control/dispatch.go: the peak-limit error names the margin only when it is above 0. The SiteFuseSafetyA comment now says the margin is opt-in and zero is the default.
  • go/cmd/ftw/control_state.go, go/internal/configreload/apply.go: the "nil → 0.5" comments now say nil → 0. fix(drivers): bound driver_init and apply fuse settings before reload #1893 moved the main.go comment into configreload/apply.go.
  • web/settings/tabs/control.js: the field shows 0 when unset. New help: "Optional. Amps to keep below the fuse rating, for an inverter whose own phase limiter trips at the rating. 0 works to the rating."
  • Site sim: simFuseSafetyA = 0, the new default. fitScenario takes the room under the line and sets the house from simFuseSafetyA, so its "exact fit" cases stay exact at any margin. The "charger's own load balancer" scenario passes at margin 0 only because the balancer sits at 25 A, which is the rating and so the new line. The Core bug remains: a cut comes off an offer the car does not draw (stepEVMeterLimit). Two known variants keep it tracked and turn red once someone fixes it: the stored 0.5 A margin, and a balancer at 25.5 A at margin 0.
  • Rig s18 (go/test/site/ev_battery_priority_test.go): "own commands stay inside the rated fuse" now skips the 10 s after the house's 0.1 A step, the same gap the scenario's minor window leaves. At margin 0 Core holds the phases at 16.00 A, so that step lands over the line until Core cuts. On fdfbfec siterig/short failed s18-16 on this criterion (and s8-60-25, see the next item): the phase read 16.101 A for 3 s right after the step, and Core cut the battery 4851 → 4719 W within 2 s. The owner's rule judges an overage between In and 1.2 × In by the I²t model, and "fuse holds" still covers it. On that run's record Core's own commands peak at 16.008 A before the step and 16.005 A after it, inside the 16.01 A bound. A new metric, max_i_own_commands, reports that number beside the old one.
  • Rig judges, ported from test(site): the rig judges "over the limit" above the fuse #1907 (go/test/site): s3, s8, s9-s11 (overage()), s15bat and the random invariants now count time over the fuse rating, not over fuse - 1 A. At margin 0 the car in s8-60-25 settles at 25 A, the rating, and the old judge counted 271 s above 24 A against 67 s allowed (fdfbfec: over_fuse_longest_s 0, fuse_blown false). The hunks match test(site): the rig judges "over the limit" above the fuse #1907's, so test(site): the rig judges "over the limit" above the fuse #1907 merges cleanly after this.
  • Changesets (patch): d-fuse-margin-default-0.md says what moves once the stack has landed. On a site with no saved margin, the car, the battery's charge and fuse relief, and the fuse's total import and export ceilings each move up 0.5 A per phase, to the rating. The hourly import_limit does not move. In fix(control): car and battery work to the fuse rating (fuse stack #1910, #1891, #1913, #1923, #1924, #1925, #1926, #1914) #1910's changeset, "with the default 0.5 A margin" now reads "with a 0.5 A margin".

Tests

  • TestFuseSafetyMarginNilUsesDefault: an unset key resolves to 0.
  • TestFuseSafetyMarginLoadKeepsExplicitValues: unset gives 0 with no notice. Explicit 0, 0.4 and 1.2 stay, with no notice. Explicit 0.5 stays 0.5, with exactly one notice.
  • TestStoredOldDefaultFuseMarginIsKeptWithANotice: a 0.5 A margin in state.db keeps steering the site over two loads. It gives one notice per load, survives DropRetiredSettings and stays in the stored document.
  • TestUnsetFuseMarginReachesCoreAsZero (cmd/ftw): a config with no safety_margin_a reaches Core as 0, a peak limit at the fuse (43470 W on 63 A × 3 × 230 V) is accepted and 1 W more is refused, and an explicit 0.5 A reaches Core as 0.5 A. Review showed that a mutation restoring a hidden 0.5 A default at startup (if cfg.Fuse.SafetyMarginA == nil { ctrl.SiteFuseSafetyA = 0.5 } after EffectiveSafetyMarginA) passed every suite. This test fails on it: "unset margin reached Core as 0.5 A, want 0".
  • Reload path: no test on this branch; see Merge order for the configreload test that lands with the retarget.
  • TestS8JudgesAtTheFuse (new) and test(site): the rig judges "over the limit" above the fuse #1907's TestInvariantsJudgeAtTheFuse (go/test/site, no simulator): a phase at exactly the fuse passes; 0.1 A over it past the time budget fails. Both fail on the old judges ("a phase at exactly the 25 A fuse failed").
  • TestS18OwnCommandsSkipTheHouseStep (go/test/site, runs without a simulator): 4 s at 16.1 A right after the house's step passes; the same 4 s at 50 s or 150 s, with no outside step, fails. Before the judge change it failed with "4 s at 16.1 A right after the house's step failed".
  • TestSetPeakLimitMessageNamesOnlyARealMargin: with 0.5 A the error names the margin. With 0 it names none, and the fuse itself (11040 W) is the ceiling.
  • Site sim at margin 0: #1761 replay, safety_margin_a 0.5 A keeps the old value covered as an opt-in.
  • TestSiteSimCarEndsAtTheLine: with the old fitScenario at margin 0 it fails (car 8280 W ... want 8625 W), because a 3.5 A house leaves 12.5 A of room, not twelve whole steps. With fitScenario reading simFuseSafetyA, it passes, and the car ends at 8280 W on the 16 A line.
  • TestSiteSimScenarios: the load-balancer scenario at 25 A passes at margin 0. Its two known variants fail as known: at 0.5 A with "over Core's limit for more than 11s (heat 24.6 A, limit 24.5 A)", and with the balancer at 25.5 A with "(heat 25.1 A, limit 25.0 A)".
  • On 0befc58 (the sync merge), make verify exits 0 with its Docker steps skipped, go test -race -count=1 ./internal/control/ passes (223 s), and the hygiene checks against origin/master (573d24f) find no planning documents, 133 telemetry reads with none added, and no new legacy brand copy. On dbc4332 (the head) go vet and go test -race -count=1 ./test/site/... pass and the hygiene checks give the same result.
  • On fdfbfec, go test -race -count=1 passes on ./cmd/ftw/ and ./internal/config/, make verify exits 0, and the hygiene checks against origin/master (573d24f) find no planning documents and 133 telemetry reads, none added.
  • On a5cdeae, go test -race -count=1 passes on ./internal/control/, ./cmd/ftw/, ./internal/config/, ./internal/configreload/, ./internal/api/, ./internal/loadpoint/ and ./internal/telemetry/.
  • make verify is clean on the synced head. Its Docker steps skipped (no daemon).
  • node --test 'web/**/*.test.mjs' (the CI web job): 893 of 893 pass.
  • The repo-hygiene checks, run by hand against master (7840c33) for the whole stack: no planning documents added; telemetry reads outside go/internal/telemetry go from 134 to 133, with no file adding one; no new legacy brand copy; both helper unit suites pass.
  • Not run here: TestSite / siterig. The runner on macmini runs those.
  • The settings field still needs a human look in a browser.

200-seed count

This is TestSiteSimRandomHouse's random house: 200 seeds, 1 h each, on the sync merge b621bab. Review reran it on fdfbfec and got the same counts and seeds. Since then this branch gained only tests (358da3b and the s18 judge). It uses review's harness. The "step judge" restarts the over-limit allowance at each outside step, as #1920 (triage R2) does for the rig.

House drawn up to Margin Plain judge Step judge
line (In − margin) 0 6 0
line (In − margin) 0.5 A 5 0
In 0.5 A 87 not run (the house alone passes the line)

Before the sync (4ecebfd) the counts were 7, 5 and 86. Seed 172 now passes at margin 0.

Plain-judge failures. At margin 0 these are seeds 70, 99 (twice), 138, 158, 179 and 189. At 0.5 A they are 138, 172, 179, 189 and 198. Each one has the same cause:

  • The charger has a 40 s delay.
  • Core cuts within 1 to 3 s of the heat crossing the line.
  • A second house step lands inside the same run, and Core cuts to 0 W within 1 to 2 s of that step.
  • The 40 s charger applies that last cut after the 46 s allowance, which the plain judge counts from the first crossing.

The step judge counts none of them.

The house-at-In row. 87 seeds fail:

  • 81 seeds: the house alone. Every failure has the car offered 0 W and drawing 0 W. The house alone holds a phase over the line.
  • Seeds 103, 161, 172 and 189: the 40 s judge case above. The offer is 0 W and the car still draws until its cut lands.
  • Seed 110: two phases cross at different times. Phase 3's heat crossed the line first, and Core cut 2 A for it. Phase 1 (28.6 A) crossed 16 s later, and Core cut again. The 40 s charger applied the second cut after the allowance, which ran from phase 3's crossing. Core cut each phase when that phase's heat crossed, as the I²t rule asks.
  • Seed 69: a real Core fault, not new in this stack. Core cut the car 9 to 6 A in the same second that a house step raised phase 3 by 2.5 A. The meter then showed phase 3 at 26.5 A, 0.5 A below the reading the cut was sent for. To Core, the cut had not landed. The sim's charger declares no power_max_age_s, so Core waits evUnknownSettle (3 min) for it to show. For those 3 min Core held the car's 6 A minimum, with the phase at 26.5 A on a 25 A fuse and the heat rising to 26.2 A. A targeted reproduction (a house step on every phase in the same second as the cut) does the same at margin 0, on this branch and on master alike: 3 min over the line, heat 26.8 A. With a declared 5 s or 40 s charger delay the hold is 23 s or 43 s, the time Core gives the charger. It is not fixed here. EV fuse cut: a house step in the same second hides the cut's landing, and Core holds a phase over the line for evUnknownSettle #1931 tracks it, for a fix in ev_fuse_budget.go (unshownOrders, cutForA) before stable.

CI on the stack

GitHub's required check is go test + vet, the aggregate job in test.yml. test.yml, repo-hygiene.yml, changeset-check.yml, brand-cleanup.yml, core-binaries.yml and history-converter.yml run only on PRs into master. native-solver.yml runs on any PR that touches its paths, and the macmini runner posts siterig/short on stacked heads.

As GitHub showed it at 09:00 on 28 Oct, after the sync pushes:

PR Base Head Has run Has not run
#1910 master ddab122 all of the above; siterig/short fails s18-16 —
#1891 #1910 b36e951 siterig/short pass go test + vet and its suites, repo hygiene, changeset, brand, Core binaries, history converter
#1913 #1891 358da3b siterig/short pass same
#1923 #1913 a059b6a nothing yet (the old head 8a10b27 passed siterig/short) same, plus siterig/short
#1924 #1923 48fb649 nothing yet (19d8a29 passed siterig/short) same, plus siterig/short
#1925 #1924 5c9c336 nothing yet (3623603 passed siterig/short) same, plus siterig/short
#1926 #1925 b82e44d nothing yet (551febd passed siterig/short) same, plus siterig/short
#1914 #1926 dbc4332 nothing yet. fdfbfec passed native-solver; its siterig/short failed s18-16 on "own commands stay inside the rated fuse" (see Change) same, plus siterig/short

The sync heads differ from the passed ones only by 358da3b, a test file in go/internal/control.

test.yml and the other master-only workflows listen for opened, synchronize and reopened. Moving a PR's base to master starts none of them. Each PR needs a push after the retarget, which merging origin/master provides. The local runs above (race tests, make verify, web tests, the hygiene checks) cover the whole stack's code on this branch. They do not stand in for the required check on each squash commit.

Risk

Medium. On sites with no saved key, which is every rig run and most sites, every line moves up 0.5 A per phase together. An inverter whose own phase limiter trips at the rating may now cut to 0 W. That is why the old default existed, and the opt-in margin is the remedy. Watch for it on the validation sites during the beta. Sites with a stored 0.5 A keep it and see one startup notice. No new control mechanism, and no dead zone or timer moves.

With Core at the line, any house rise puts a phase over In until Core cuts. On rig s18-16 a 0.1 A step read 16.10 A for about 3 s. The I²t rule allows that, and the s18 judge now says so (see Change).

At margin 0, a whole-ampere meter has no cushion either. Many P1 meters (p1_dsmr, zuidwijk_p1) report phase current in whole amperes, and Core read magnitude from l*_a alone. Review measured a phase at 16.60 A (truncating) and 16.45 A (rounding) on a 16 A fuse for 20 min at margin 0, against 15.60 A and 15.45 A at 0.5 A. #1932 reads each phase as at least its power over its measured voltage. On this stack with #1932, the same probes end at 15.60 A and 15.45 A at margin 0, with no time over In. Land #1932 first.

At margin 0, a frozen site meter has no 0.5 A cushion. #1921 (C5, frozen meter counts as stale) is independent, with base master, and touches main.go and dispatch.go away from this PR's lines. It should reach the same beta as this PR or an earlier one.

Related open PRs

🤖 Generated with Claude Code

Core now works to the fuse rating unless a site sets a margin. Every
explicit safety_margin_a is kept. A stored value of exactly 0.5 A, the
old default, adds one load-time notice and changes nothing.

The peak-limit error names the margin only when it is above 0, and the
settings field shows 0 with help that says the margin is opt-in.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
@chatgpt-codex-connector

chatgpt-codex-connector Bot commented Oct 27, 2026 •

Copy link
Copy Markdown

Codex Review Summary

This comment shows the latest Codex review activity on this pull request.

Review Status Commit Review trigger
📝 Code Review ✅ Completed 2026-10-27T18:06:42.941763Z fab8f6f PR opened
ℹ️ About Codex in GitHub

Your team has set up Codex to review pull requests in this repo. Reviews are triggered when you

  • Open a pull request for review
  • Mark a draft as ready
  • Comment "@codex review" or "@codex security review".

Codex reacts with 👀 while any review is running, comments if it has suggestions, and reacts with 👍 once all reviews finish with no findings.

The changeset said FTW works to the fuse rating unless a site sets a
margin. On this PR's base every per-phase line still sits 1 A under the
rating; that holds only once #1910 and the step-4 amendment of #1891
land. The changeset now names what this PR changes: the default, and
the whole-site import and export limits.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
frahlg and others added 3 commits October 28, 2026 01:02
Rebases #1914 onto the top of the fuse stack. The one conflict was the
margin in the site sim's boot; it now reads simFuseSafetyA.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
simFuseSafetyA follows the config default, now 0. fitScenario takes the
room under the line and sets the house from simFuseSafetyA, so its exact
fit stays twelve whole steps at any margin. "charger's own load
balancer" passes at margin 0, so its known line goes.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
With the stack under it, the default moves the car's and the battery's
per-phase line as well as the site totals. 0.5 A stops being the
default, so #1910's changeset no longer calls it that.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
@frahlg
frahlg changed the base branch from c-battery-fuse-no-buffer to ev-base-after-restart October 28, 2026 00:04
frahlg and others added 2 commits October 28, 2026 01:20
At the 0 A default the scenario passes only because the charger's own
balancer sits at 25 A, the rating and so the line. The bug is still in
Core: a cut comes off an offer the car does not draw. Two known variants
keep it tracked and turn red once it is fixed: the stored 0.5 A margin
(over 24.5 A for more than 11 s) and a balancer at 25.5 A at margin 0
(over 25 A for more than 11 s).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
frahlg and others added 3 commits October 28, 2026 07:42
Brings in the current tips of #1910, #1891, #1913, #1923, #1924,
#1925 and #1926.

The only conflict was #1910's changeset: it now carries #1910's new
sentence on an offline battery's relief, and keeps this branch's
"a 0.5 A margin" wording, since 0.5 A is no longer the default here.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
…move

The SiteFuseSafetyA comment read as if the margin were needed by
default; it now says zero is the default and when to set one. The
changeset named "the site's total import and export limits", which
reads as the hourly import_limit; that limit does not move. It now
names the fuse's import and export ceilings.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
A mutation that restored a hidden 0.5 A margin at startup passed every
suite. This test pins the value newControlStateFromConfig hands Core.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
frahlg and others added 4 commits October 28, 2026 08:46
At margin 0 Core holds the phases at the 16 A line. Rig s18-16's 0.1 A
house step at small_step then lands over the line until Core cuts: on
fdfbfec the phase read 16.101 A for 3 s and Core cut the battery
4851 -> 4719 W within 2 s. The criterion "own commands stay inside the
rated fuse" counted that stretch as Core's and failed. The owner's rule
judges an overage between In and 1.2 x In by the I2t model.

The criterion now skips the 10 s after the step, the same gap the minor
window already leaves. On the fdfbfec record Core's own commands peak
at 16.008 A before the step and 16.005 A after it, inside 16.01 A.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
At margin 0 the car in s8-60-25 settles at the rating, as the owner's
rule says, and the rig's old 1 A hidden margin failed it: 271 s above
24 A against 67 s allowed, with no second over 25 A. siterig/full has the
same threshold in overage() (s9, s10, s11), the random invariants and
s15bat.

Port #1907's judge hunks: s3, s8, s9-s11, s15bat and the invariants now
count time over the fuse rating. TestS8JudgesAtTheFuse and #1907's
TestInvariantsJudgeAtTheFuse fail on the old judges.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
frahlg added a commit that referenced this pull request Oct 28, 2026
…1913, #1923, #1924, #1925, #1926, #1914)

* fix(control): one log of FTW's own EV offers

The battery side read a 20 s pool log of EV offers (State.evOffers), while
the EV fuse limit keeps each charger's offers for its declared response
time, or 180 s when it declares none. After 20 s the battery counted a slow
charger's unshown raise as already in the meter and charged into that room;
when the car started, a 25 A site read 32.6 A per phase for 3 s.

Delete State.evOffers and its two writers. evInMeterW and
clampEVBatteryHeadroom read evShownW, each charger's latest offer less
what it may not show yet. The hourly peak in stepEVMeterLimit takes each
charger's highest offer of the last evSettle from the same log.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery fuse guard reads each phase with its direction

Delete perPhaseOverageW, perPhaseOverageReadingW and perPhaseReliefW.
The battery fuse guard, the fuse saver and the forced discharge read the
signed phase currents (phaseCurrentsA, with #1849's sum check and dead
zone), count the batteries' own move on each phase, and relieve to the
car's working limit, the fuse less max(1 A, safety_margin_a).

Item A5 of the stable plan.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery waits only for a declared charger response time

The first A6 change gave the battery side the EV limit's 180 s guess
for every charger that declares no response time. Only Easee Cloud
declares one, so on every other charger the battery reserved the car's
whole demand on top of a reading that already showed the car, and
stopped charging for 3 minutes after each car start or raise. On the
#1868 shape (rig s18) battery charge stayed at 0 W until 180 s.

evShownW now uses the charger's declared power_max_age_s, and evSettle
when it declares none, as master did. Easee Cloud declares 180 s, so the
slow-charger case stays fixed.

Tests: the slow-charger test now declares 180 s, and a new plant test
runs the s18 shape with a fast charger that declares nothing.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): fuse guard reads phases after the hold caps the targets

The guard took the phase relief from the original request, then the 30 s
fuse hold capped that request and the relief came off again. A charge
limited by one phase switched between 1380 W and 0 W on every dispatch.
Predict the aggregate and the phases from the held targets instead.

The phase reader now takes the meter's raw total from OnlineMeterW, the
same reading as its currents, so an offline meter's cached phases drive
no relief. The batteries' raw power is read in one helper. dispatch.go
keeps its 41 cached telemetry reads.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): car and battery-beside-car work to the fuse rating less safety_margin_a

The EV phase limit was In - 1 A, fixed in code. It is now fuseLineA():
In - safety_margin_a, with no floor. A rise moves one step once it fits
under the line, a start takes all the room, and battery charge beside a
car uses the same line. The hour's import limit keeps its own margins.
Starts and per-phase cuts round down to whole charger amps, since
chargers round offers to the nearest amp.

Step 3 (PR b) of the fuse-at-rating plan (owner rule of 27 Oct).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): keep covered offers whole and leave battery relief out of EV room

Two review findings on the fuse-line change:

- A cut rounds to whole charger amps only when a new cut is needed. When
  cuts on their way cover the overage, the offer stays as it is. Rounding
  a kept step-table offer took the car 6200 -> 5500 -> 4800 -> 0 W in 3 s
  on a 0.6 A overage while a 180 s cut travelled.
- Dispatch records the discharge the fuse guard adds to each battery, and
  an EV rise or start does not count it as room. Before, the car rose into
  the relief and the battery fed it 650 W at the line for as long as the
  house load stayed.

The noisy-line sim test now pins the slow one-step cycle at an exact fit
(at most 5 cuts an hour, never a stop) and no moves with part of a step
left, instead of allowing 45 moves an hour.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery fuse guard reads each phase with its direction

Delete perPhaseOverageW, perPhaseOverageReadingW and perPhaseReliefW.
The battery fuse guard, the fuse saver and the forced discharge read the
signed phase currents (phaseCurrentsA, with #1849's sum check and dead
zone), count the batteries' own move on each phase, and relieve to the
car's working limit, the fuse less max(1 A, safety_margin_a).

Item A5 of the stable plan.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): fuse guard reads phases after the hold caps the targets

The guard took the phase relief from the original request, then the 30 s
fuse hold capped that request and the relief came off again. A charge
limited by one phase switched between 1380 W and 0 W on every dispatch.
Predict the aggregate and the phases from the held targets instead.

The phase reader now takes the meter's raw total from OnlineMeterW, the
same reading as its currents, so an offline meter's cached phases drive
no relief. The batteries' raw power is read in one helper. dispatch.go
keeps its 41 cached telemetry reads.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery relieves to the fuse less safety_margin_a

phaseFuseReliefW now reads fuseLineA(), the line the car uses since the
EV change, instead of max(1 A, safety_margin_a). There is no floor under
the margin: at margin 0 the battery works to the fuse rating.

Tests return to the rating where they had moved to the 1 A limit, and a
new property test covers In x phases x margin in both directions.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): re-record golden records at the fuse less safety_margin_a

Replayed from stored inputs; only records whose dispatch changed against
the parent branch were replaced.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery fuse cut lands on the line, not half a margin below

applyFuseGuard cut a battery charge or discharge by the overage plus
half of safety_margin_a. The guard now predicts from the held targets
and keeps its 30 s hold, so the extra cut only parked the phase below
the line the user set. Cut by the overage only.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* docs(changeset): name the limit the battery cut lands on

The changeset said the phase lands on the fuse less safety_margin_a.
On #1891 as it stands, the phase line is the fuse less max(1 A,
safety_margin_a), so at the 0.5 A default a 16 A phase settles at
15 A, not 15.5 A. Say what this PR changes, cutting only by the
overage, without naming a line that depends on step 4.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(config): fuse safety_margin_a defaults to 0

Core now works to the fuse rating unless a site sets a margin. Every
explicit safety_margin_a is kept. A stored value of exactly 0.5 A, the
old default, adds one load-time notice and changes nothing.

The peak-limit error names the margin only when it is above 0, and the
settings field shows 0 with help that says the margin is opt-in.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* docs(changeset): say what the default change moves on its own

The changeset said FTW works to the fuse rating unless a site sets a
margin. On this PR's base every per-phase line still sits 1 A under the
rating; that holds only once #1910 and the step-4 amendment of #1891
land. The changeset now names what this PR changes: the default, and
the whole-site import and export limits.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): relief stays at the line after a PV drop (C3, seed 207533)

On a 16 A fuse with no margin the battery holds 3 kW of discharge with L1
at 14.4 A; PV drops 1280 W and L1 reads 16.3 A. The relief must bring L1
to 16 A and keep it there while the reading sits at the line with the
battery at its relief power. Without phaseFuseReliefW's own-move count
the relief flips between -3214 W and -3005 W on every tick and L1 crosses
the rating 13 times; with it, L1 crosses once.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): phase relief reads each battery live, in the decision's reading

The merge of #1876 moved stopPhaseReliefW's live reads into
phaseSample.moveW. Pin it: a battery that went offline, moved on to a
newer reading or has no reading gives no phase relief. With the cached
RawW read #1891 had, the offline and newer-reading cases relieve 2310 W
and the no-reading case counts a 2000 W charge from 0 W.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery relief holds when the battery's reading lags the meter

The phase relief counts the battery's move from its own reading. When
that reading lags the meter by a tick, the meter already shows the relief
while the reading does not, so the relief came off; on the next tick it
went back on top of the reading's catch-up. In the 207533 shape (16 A,
margin 0) with a one-tick lag the order ran -3214, -3005, -3422, -3005,
... -5717 W and L1 went back to 16.3 A on every other tick: 13 crossings.

A move from the battery's last command (the one it got in the last
dispatch) may now not pass the room the meter shows either. That bound
only tightens, and a phase already over the line gives it no room, so it
never asks for more than to stay at the last command: a battery that
falls short of its order does not wind it up. With lag 1 or 2 the order
holds -3214 W with L1 at 16.0 A and one crossing, on the PV step.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): a landed EV cut covers nothing later; a raise that no longer fits comes off

The site meter now tells Core how much of a charger's offers it already
shows. A move shaped like an order landing (every phase alike, or one
phase alone for a one-phase car) moves that level toward the latest
offer. A cut the meter shows no longer covers an overage that an outside
step causes after it, and no longer nets against a raise sent after it.
Where a landing and a house step fall in one reading, a cut covers a
phase that has risen since only up to the overage it had then.

C4: our own rise on its way, as the meter tells it, is judged as the
reading it will make. Above 1.2 x In, or over the line on a phase whose
heat budget is spent, it comes off on this reading, down to the line.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): a one-phase house move is not the car's cut landing

seeOffers kept one shown level for every phase, so a house load moving on
one phase alone read as a three-phase cut landing and took the cut's cover
off the phase it was sent for. With a 40 s charger Core then stacked a
second cut and left L1 2 A under the line for over 2 min. The shown level
is now kept per phase: a three-phase order moves every phase alike, and a
phase that moves alone moves only its own level.

The loadpoint now reports a car it has seen draw on all three phases as
CarPhases 3. For such a car a one-phase move is never the car, so a house
step on one phase while a raise travels no longer hides the raise, and C4
cuts on that reading.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): a battery charge rise fits each phase before it is sent

The battery fuse guard judged a rise from the battery's own reading and
the meter's phases, so it took a rise the meter did not show yet as
already shown. With the meter a poll behind the battery, a PV surplus that
grew each tick stacked rises past the line, then the relief cut them back:
16.4 A on a 16 A fuse and a charge that rose and fell (C2, seeds 207530,
207535).

fitBatteryRisesToFuse caps charge above the battery's latest order to
(fuseLineA - worst phase - own unshown rises) x V x phases. The unshown
rises are the battery's orders of the last evSettle and the chargers'
raises, counted as evShownW counts them, so the car comes first. Holding
an order is never a rise and the check never cuts; an overage stays with
the relief. No margin and no floor: the order ends at the line.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery rise check counts slow batteries and direction-less phases

A battery order now stays unshown until evSettle after the battery's own
reading reaches it, so a battery that ramps slower than evSettle no longer
gets a second rise on top of an order the meter cannot show yet.

On a meter with phase currents but no phase power while the total
exports, a phase counts as export only when the other phases cannot
carry the export alone; any other phase counts as import. Before, every
phase flipped to export, so a three-phase charge could rise into a phase
that imports beside two exporting ones.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): the car comes before battery charge

With battery_covers_ev off, dispatch took the car out of the meter
reading before the battery decided. The battery then saw the PV the
car was using as export and charged from it while the site imported
for the car (rig seeds 207535, 207539, 207530: about 10 kW import).

The battery now charges only from the surplus the meter shows after
the car. Where the house alone has surplus, the battery sees the meter
with the car included, and any discharge stops at once, since it would
feed the car. A planned PV charge on the energy path takes only the
surplus the car leaves; a planned grid purchase keeps its charge.
Cover off still never discharges the battery for the car.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): peak shaving drops a running charge for the car

Manual peak_shaving gave zero error for any import under the peak
limit, so a battery charge that was running when the car started held
while the site imported for the car, with battery_covers_ev on or off.
When the site imports while the car and the battery both charge, the
charge now comes down by the import, to 0 at most. Under the peak limit
the battery still never discharges.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): after a restart the battery credits the car the meter shows

After a restart, the 0 A orders FTW sent while the meter was stale counted
as the EV base the meter shows. With the car still drawing 8.2 kW from
before, a new 6.2 kW order then counted as a 9 A rise to come, and the
battery was held in discharge for the car (seed 207532).

Until a charger's first order of this run can have landed, the battery
side now counts the charger's live measured draw as in the reading, never
above the latest order and never above the consumption the site meter
shows. The car's own limit does not read it.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): credit a found car only from a current charger sample

Review of #1926 found two ways the restart credit let the battery end a
discharge into room the car's pending rise still needs:

- The charger reading counted with no check that it was current. A held
  reading after a failed poll, or a sample older than the site reading,
  could show a car that a fast charger had already stopped. The draw now
  counts only when the last poll succeeded and the charger measured it
  within one control interval of the site reading.
- The consumption bound subtracted the smoothed battery, PV and V2X
  values, which lag an output that just fell. It now takes the higher of
  raw and smoothed for each, so the bound stays at or below what the
  meter shows.

New tests pin both, plus the shown-offer subtractions and a window that
outlasts evSettle.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): run the site sim at the new 0 A default margin

simFuseSafetyA follows the config default, now 0. fitScenario takes the
room under the line and sets the house from simFuseSafetyA, so its exact
fit stays twelve whole steps at any margin. "charger's own load
balancer" passes at margin 0, so its known line goes.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* docs(changeset): say what margin 0 moves once the fuse stack lands

With the stack under it, the default moves the car's and the battery's
per-phase line as well as the site totals. 0.5 A stops being the
default, so #1910's changeset no longer calls it that.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): keep the load-balancer bug as a known line above the line

At the 0 A default the scenario passes only because the charger's own
balancer sits at 25 A, the rating and so the line. The bug is still in
Core: a cut comes off an offer the car does not draw. Two known variants
keep it tracked and turn red once it is fixed: the stored 0.5 A margin
(over 24.5 A for more than 11 s) and a balancer at 25.5 A at margin 0
(over 25 A for more than 11 s).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): EV room reads battery relief through live telemetry

evFuseReliefW read each battery's cached RawW, which survives a driver
going offline. It now reads Store.OnlineRawW. A battery with no live
reading counts its whole recorded relief, so the car never builds on
discharge Core can no longer hold.

fuseSaverEarlyExit read each battery's SmoothedW a second time to record
relief. It now records against the live snapshot the fuse-saver decision
already took (fleetAtLivePower), so it adds no read of its own.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): an offline battery's fuse relief ends after evSettle

With no battery online, ComputeDispatch returns before it records relief,
so batteryFuseRelief kept its last value and evFuseReliefW counted all of
it for as long as the battery stayed offline. The car was held up to the
whole relief below the line. The relief now counts in full until the
default mode Core sent at the transition can have reached the meter
(evSettle), then ends.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): each offline battery's fuse relief ends after evSettle

The expiry in 8150b45 ran only when no battery was online. With a
second battery online, an offline battery's relief stayed until a
recorded dispatch rewrote the map: never while the legacy modes sat in
the deadband, and on the first tick when one did record, so the car
could rise onto discharge Core ordered a second earlier. Each offline
battery now has its own clock: its relief counts whole for evSettle
and then ends, on every dispatch path. A battery back online leaves the
clock, so its next offline period counts whole again; a test now covers
that reset.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery phase relief neither pins mixed phases nor winds up

The last-command bound held the battery at its last command when one
phase sat at the import line and another was over the export line: the
guard cut the discharge for the exporting phase and the bound put it
back. Now the bound gives way on one side while any phase is over the
other side's line, and phaseFuseReliefW's least-over move decides.

When the meter does not show the battery's move (a frozen meter, or a
worst phase a one-phase battery cannot reach), each tick added the same
overage again and the order ran out to the discharge limit. Now the
relief toward the worst phase stops at the last command once the
batteries' raw power has moved one ampere per phase since the worst
phase last moved by half an ampere. One ampere is the step in which P1
meters report phase current.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery phase anti-windup stops only when the meter cannot show the move

phaseUnresponsive stopped the relief whenever the batteries had moved
690 W and the worst phase had not moved half an ampere. On a live meter
that also happens when a load cancels the move (a balanced load starting
with the relief step, or a slow rise on the worst phase), and when the
battery's reading catches up with an order the meter already showed.
The relief then held over the line with no end.

Now it stops only when the meter repeats its phases exactly while the
batteries moved one ampere per phase, or when another phase moved by
twice the balanced share of that move (a battery off the worst phase).
The repeat is measured from the reading the meter last changed in, so a
meter that freezes on any reading is still caught.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): battery off the worst phase goes back, and a stale reference ends

Fourth review of the phase anti-windup (c066892):

- The worst phase's reference had no end while that phase sat over the
  line. A relief that follows a slow drift keeps it there, so the
  reference stayed while the battery moved hundreds of watts, and a load
  that later switched off on another phase read as a battery off the
  worst phase. The relief then held L1 up to 0.49 A over the line with no
  time limit. The reference now also ends when the worst phase is at or
  inside the line, or when another phase becomes the worst.
- An off-phase verdict no longer holds the last command. The batteries go
  back to their power when the worst phase last moved: what they moved
  since did not reach it. A one-phase battery no longer holds its own
  phase at -17.97 A for the whole overage (and -19.83 A, past 1.2 x In,
  when PV returns). A false verdict on a balanced battery moves the
  worst phase by at least one ampere on the next reading, which ends the
  reference, so it costs one tick instead of an open-ended hold. The
  verdict holds until the reference ends, so the relief does not go out
  again once the battery is back.
- The frozen-meter test now also compares the meter's total. A P1 meter
  reports whole amperes, so a live meter can repeat its phases while its
  total moves; that latched the relief at 1.11 x In.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): the drift test also wants no verdict on the load change

With L1 at the line ending the reference, no off-phase verdict comes when
the load on L3 switches off. Without it, the step back still ends the
hold, but with L1 at 16.8 and 17.7 A for two ticks; the test now sees
that.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): our battery order's move is not the car's cut landing

The guard in seeOffers that stops reading the meter while our battery
order moves had no test; removing it left every test green. A battery
order that lands and goes back while a cut travels to a 40 s charger
now must not lead to a second cut.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): the car-first discharge stop has its own test

Removing the PI path's immediate discharge stop left every named test
green; only the golden replay caught it. A peak_shaving loop with
battery_covers_ev off, starting from a 2.9 kW discharge while the house
alone has surplus, now requires that no order discharges into the car.

The comment on the plan back-off said the plan's grid leaves out the car.
It counts the car it planned; the comment now says so.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): the battery rise check reads only live battery power

fitBatteryRisesToFuse, unshownBatteryW and recordBatteryReadings read
the battery's cached RawW, which survives the driver going offline, and
added three direct telemetry reads that the repo-hygiene check refuses.
They now use Store.OnlineRawW, as phaseSample.moveW does: an offline
battery's last value no longer sets the rise base or the shown level.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): judge a raise's landing from the meter's rise

C4 counted a raise as landed only when a reading-to-reading move had a
charger's shape. A slow ramp, or a house load on another phase that moved
in the landing reading, left the whole raise counted as on its way on top
of a reading that already held it, and Core cut a raise that fit under
the line. The rise still to come now reads the meter's own rise since the
raise went out: the smallest across the phases for a three-phase order,
the car's phase for a one-phase car.

For a three-phase order, a move on one phase alone no longer moves the
shown level of a car not yet seen. A load cycling on the phase over the
line took the cut's cover off on each drop and never gave it back, so
Core cut again and again.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): a car not yet seen may take a raise on one phase

The smallest rise across the phases read a one-phase car not yet seen
as a raise that had not landed: its phase rose, the other two did not.
Core then cut the car from 11040 W to 0 with every phase under the line
(field matrix, car1p cases). One phase that has risen alone since the
raise went out, the others within half a step, now counts as that car
taking the raise, as the shape tracker read it before. The changeset
again says what holds: the one-phase house step case is closed for a
car seen on three phases.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): judge a one-phase landing reading by reading

For a car not yet seen on three phases, a raise counted as landed on one
phase only while the other phases stayed within 0.5 A of their reading
when the raise went out. That window spans the charger's whole response
time, so 0.6 A of house drift on another phase made the full raise count
as still to come on top of a reading that already showed it, and Core
cut the car with every phase under the line (field matrix with 0.7 A on
L2: car1p cut 11100 -> 0 W).

Each phase now keeps its rise over the readings in which the other
phases moved less than a step (aloneA). A rise of a step or more there
may be the car on that phase. Drift between readings, or under a step
in the landing reading, no longer hides it; a house load that moves a
step or more on another phase in the same reading still does.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): restart credit keeps room for the car's rise to its max

After a restart Core does not know the offer in force on the charger, so
a car drawing below it may still rise before Core's order lands. The
credit now counts only the draw less that possible rise past the latest
offer, with the rise measured to the loadpoint's max_charge_w; a charger
with no max_charge_w gets no credit.

The charger and output reads move into health-gated telemetry accessors
(OnlineLowerW, SumOnlineHigherW). Tests cover the raw and smoothed
guards, a 10 s OCPP sample cadence on the plant, and the review's car
rising under a 16 A offer in force.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): Charge now landing shown before Core logs its offer

Site rig s1-16, s1-25 and s15-25 failed on c9b52c3: the charger answered
within a second, and the meter reading that showed the car at 15.9 A came
in 7 ms before the tick that first logged the 16 A offer. The reading
could not show an offer logged after it, so the landing counted as a
raise still to come, 15.9 + 16 A passed 1.2 x In, and Core cut 11,040 W
to 5,520 W with 9 A of room on every phase. The same run of the base at
281f9f6, without this branch's commits, fails the same way; #1923's
ab02710, merged here in c0a5274, reads the meter's own rise and fixes
it. This test pins that rig shape.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): restart credit counts no sample newer than the meter

The battery side's restart credit (evFoundDrawW) had two gaps.

A charger sample measured after the site reading counted as part of
it. A car that rose in that gap was credited for draw the meter did
not show yet, and the battery ended its discharge into room the rise
had taken. With a 3 s meter, L2 reached 19.30 A. A sample now counts
only when measured at or before the site reading.

The rise reserve took max_charge_w as the most the unknown offer in
force can be. A charger still on an offer from before a restart that
lowered max_charge_w, or on its own higher default, could rise past
it: 19.00 A per phase on the unit fixture, 19.30 A on the plant. The
reserve now runs to the larger of max_charge_w and the site fuse's
rating.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): restart credit holds against a charger clock behind Core's

The restart credit compared a charger's sample time, stamped by the
charger's own clock (OCPP MeterValues), with the time the site reading
arrived on Core's clock. A charger clock 1 s or more behind Core's let
a rise sampled after the reading count as already in it, and L2 reached
19.30 A on the third review's plant case.

A sample now counts only when stamped evClockAllowance (5 s) before the
reading arrived, and the draw is the lowest of that sample and every
sample since. noteDraw keeps the charger's samples while the restart
window is open.

Also tests the max_charge_w half of the rise cap: a 22 kW charger on a
3 x 25 A fuse keeps the reserve up to max_charge_w.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* docs(control): the fuse margin is opt-in, and only the fuse ceilings move

The SiteFuseSafetyA comment read as if the margin were needed by
default; it now says zero is the default and when to set one. The
changeset named "the site's total import and export limits", which
reads as the hourly import_limit; that limit does not move. It now
names the fuse's import and export ceilings.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(control): battery beside a minimum-step car holds the fuse line (rig s18-16)

On #1910 and #1891 the battery rises beside the car to the working limit,
the fuse guard cuts it by the overage plus half of safety_margin_a and holds
30 s, and the battery rises again: it hunts between 15.0 and 15.5 A on a
16 A site. Where it stands when the house moves is chance, which is why
rig s18-16 failed 3 of 57 runs on those heads. #1913's cut by the overage
only keeps it on the line.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(config): an unset fuse margin reaches Core as 0

A mutation that restored a hidden 0.5 A margin at startup passed every
suite. This test pins the value newControlStateFromConfig hands Core.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): s18 judges own commands apart from the house's step

At margin 0 Core holds the phases at the 16 A line. Rig s18-16's 0.1 A
house step at small_step then lands over the line until Core cuts: on
fdfbfec the phase read 16.101 A for 3 s and Core cut the battery
4851 -> 4719 W within 2 s. The criterion "own commands stay inside the
rated fuse" counted that stretch as Core's and failed. The owner's rule
judges an overage between In and 1.2 x In by the I2t model.

The criterion now skips the 10 s after the step, the same gap the minor
window already leaves. On the fdfbfec record Core's own commands peak
at 16.008 A before the step and 16.005 A after it, inside 16.01 A.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): no cut of an unseen car, no landing from a 1p house move

Two regressions against #1913 from the final review.

A car the loadpoint has not seen on three phases may draw on one phase
Core does not know. The alone rise (aloneA) missed its landing when any
other phase moved a step in the same reading, so the whole raise counted
as still to come and C4 cut a car with every phase under the line, at
most session starts with a 10 s meter. riseAheadA now takes the largest
rise for such a car, as for a one-phase car whose phase is not known,
and the smallest only once the car is seen on three phases.

A one-phase order never knows the car's phase, so a house load moving
alone on any phase read as its cut landing and took the cover off a cut
still on its way. A one-phase move now counts only on a known car phase.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* fix(control): judge a restart sample by its arrival, not its stamp

The 5 s clock allowance let the restart credit count a charger sample
taken 5-7 s before the site reading. A car that stopped after that
sample (a fast charger applying the 0 A sent while the meter was stale,
or the car pausing) still counted, the battery ended the discharge the
car's return needed, and L2 reached 21 A on a 16 A fuse when it resumed.

Core now judges a sample by when it first arrived on Core's clock. It
counts as in the reading only when it arrived evMeterDelay (1 s) before
the reading, and no more than one control interval before that. A sample
already there when Core began to watch the charger arrived at a time
Core does not know, so it never counts. The charger's stamp only tells
samples apart, so a charger clock behind Core's no longer matters.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

* test(site): judge overages at the fuse rating, not fuse - 1 A

At margin 0 the car in s8-60-25 settles at the rating, as the owner's
rule says, and the rig's old 1 A hidden margin failed it: 271 s above
24 A against 67 s allowed, with no second over 25 A. siterig/full has the
same threshold in overage() (s9, s10, s11), the random invariants and
s15bat.

Port #1907's judge hunks: s3, s8, s9-s11, s15bat and the invariants now
count time over the fuse rating. TestS8JudgesAtTheFuse and #1907's
TestInvariantsJudgeAtTheFuse fail on the old judges.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>

---------

Co-authored-by: Claude Opus 5.5 <noreply@anthropic.com>