fix(control): a battery charge rise fits each phase before it is sent - #1924
Merged
Merged
Conversation
Core now works to the fuse rating unless a site sets a margin. Every explicit safety_margin_a is kept. A stored value of exactly 0.5 A, the old default, adds one load-time notice and changes nothing. The peak-limit error names the margin only when it is above 0, and the settings field shows 0 with help that says the margin is opt-in. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
The changeset said FTW works to the fuse rating unless a site sets a margin. On this PR's base every per-phase line still sits 1 A under the rating; that holds only once #1910 and the step-4 amendment of #1891 land. The changeset now names what this PR changes: the default, and the whole-site import and export limits. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
The battery fuse guard judged a rise from the battery's own reading and the meter's phases, so it took a rise the meter did not show yet as already shown. With the meter a poll behind the battery, a PV surplus that grew each tick stacked rises past the line, then the relief cut them back: 16.4 A on a 16 A fuse and a charge that rose and fell (C2, seeds 207530, 207535). fitBatteryRisesToFuse caps charge above the battery's latest order to (fuseLineA - worst phase - own unshown rises) x V x phases. The unshown rises are the battery's orders of the last evSettle and the chargers' raises, counted as evShownW counts them, so the car comes first. Holding an order is never a rise and the check never cuts; an overage stays with the relief. No margin and no floor: the order ends at the line. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Codex Review SummaryThis comment shows the latest Codex review activity on this pull request.
ℹ️ About Codex in GitHubYour team has set up Codex to review pull requests in this repo. Reviews are triggered when you
Codex reacts with 👀 while any review is running, comments if it has suggestions, and reacts with 👍 once all reviews finish with no findings. |
…less phases A battery order now stays unshown until evSettle after the battery's own reading reaches it, so a battery that ramps slower than evSettle no longer gets a second rise on top of an order the meter cannot show yet. On a meter with phase currents but no phase power while the total exports, a phase counts as export only when the other phases cannot carry the export alone; any other phase counts as import. Before, every phase flipped to export, so a three-phase charge could rise into a phase that imports beside two exporting ones. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
With battery_covers_ev off, dispatch took the car out of the meter reading before the battery decided. The battery then saw the PV the car was using as export and charged from it while the site imported for the car (rig seeds 207535, 207539, 207530: about 10 kW import). The battery now charges only from the surplus the meter shows after the car. Where the house alone has surplus, the battery sees the meter with the car included, and any discharge stops at once, since it would feed the car. A planned PV charge on the energy path takes only the surplus the car leaves; a planned grid purchase keeps its charge. Cover off still never discharges the battery for the car. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Manual peak_shaving gave zero error for any import under the peak limit, so a battery charge that was running when the car started held while the site imported for the car, with battery_covers_ev on or off. When the site imports while the car and the battery both charge, the charge now comes down by the import, to 0 at most. Under the peak limit the battery still never discharges. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
…hows After a restart, the 0 A orders FTW sent while the meter was stale counted as the EV base the meter shows. With the car still drawing 8.2 kW from before, a new 6.2 kW order then counted as a 9 A rise to come, and the battery was held in discharge for the car (seed 207532). Until a charger's first order of this run can have landed, the battery side now counts the charger's live measured draw as in the reading, never above the latest order and never above the consumption the site meter shows. The car's own limit does not read it. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Review of #1926 found two ways the restart credit let the battery end a discharge into room the car's pending rise still needs: - The charger reading counted with no check that it was current. A held reading after a failed poll, or a sample older than the site reading, could show a car that a fast charger had already stopped. The draw now counts only when the last poll succeeded and the charger measured it within one control interval of the site reading. - The consumption bound subtracted the smoothed battery, PV and V2X values, which lag an output that just fell. It now takes the higher of raw and smoothed for each, so the bound stays at or below what the meter shows. New tests pin both, plus the shown-offer subtractions and a window that outlasts evSettle. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Rebases #1914 onto the top of the fuse stack. The one conflict was the margin in the site sim's boot; it now reads simFuseSafetyA. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
simFuseSafetyA follows the config default, now 0. fitScenario takes the room under the line and sets the house from simFuseSafetyA, so its exact fit stays twelve whole steps at any margin. "charger's own load balancer" passes at margin 0, so its known line goes. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
With the stack under it, the default moves the car's and the battery's per-phase line as well as the site totals. 0.5 A stops being the default, so #1910's changeset no longer calls it that. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Brings in #1891's tip (fd07863, b19d30d and master through 7840c33) by way of #1913 and #1923. Both sides pulled the signed phase currents out of phaseFuseReliefW: #1891 as signedA, which flips every phase when the total exports and no phase shows a direction, and this branch as signedPhasesA, which flips only a phase the total forces to export. Resolution: keep signedPhasesA and drop signedA, so the relief, #1891's new phaseSentReliefW and fitBatteryRisesToFuse read the phases one way. phaseMoveW is gone; #1891's phaseSample.moveW, which reads each battery live and also returns the move from the last command, replaces it. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
At the 0 A default the scenario passes only because the charger's own balancer sits at 25 A, the rating and so the line. The bug is still in Core: a cut comes off an offer the car does not draw. Two known variants keep it tracked and turn red once it is fixed: the stored 0.5 A margin (over 24.5 A for more than 11 s) and a balancer at 25.5 A at margin 0 (over 25 A for more than 11 s). Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
The phase anti-windup from a5 read phases through signedA, which this branch had folded into signedPhasesA. It now uses signedPhasesA, so it reads phase direction the same way as the relief and the rise check. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Removing the PI path's immediate discharge stop left every named test green; only the golden replay caught it. A peak_shaving loop with battery_covers_ev off, starting from a 2.9 kW discharge while the house alone has surplus, now requires that no order discharges into the car. The comment on the plan back-off said the plan's grid leaves out the car. It counts the car it planned; the comment now says so. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
fitBatteryRisesToFuse, unshownBatteryW and recordBatteryReadings read the battery's cached RawW, which survives the driver going offline, and added three direct telemetry reads that the repo-hygiene check refuses. They now use Store.OnlineRawW, as phaseSample.moveW does: an offline battery's last value no longer sets the rise base or the shown level. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
After a restart Core does not know the offer in force on the charger, so a car drawing below it may still rise before Core's order lands. The credit now counts only the draw less that possible rise past the latest offer, with the rise measured to the loadpoint's max_charge_w; a charger with no max_charge_w gets no credit. The charger and output reads move into health-gated telemetry accessors (OnlineLowerW, SumOnlineHigherW). Tests cover the raw and smoothed guards, a 10 s OCPP sample cadence on the plant, and the review's car rising under a 16 A offer in force. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Site rig s1-16, s1-25 and s15-25 failed on c9b52c3: the charger answered within a second, and the meter reading that showed the car at 15.9 A came in 7 ms before the tick that first logged the 16 A offer. The reading could not show an offer logged after it, so the landing counted as a raise still to come, 15.9 + 16 A passed 1.2 x In, and Core cut 11,040 W to 5,520 W with 9 A of room on every phase. The same run of the base at 281f9f6, without this branch's commits, fails the same way; #1923's ab02710, merged here in c0a5274, reads the meter's own rise and fixes it. This test pins that rig shape. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
The battery side's restart credit (evFoundDrawW) had two gaps. A charger sample measured after the site reading counted as part of it. A car that rose in that gap was credited for draw the meter did not show yet, and the battery ended its discharge into room the rise had taken. With a 3 s meter, L2 reached 19.30 A. A sample now counts only when measured at or before the site reading. The rise reserve took max_charge_w as the most the unknown offer in force can be. A charger still on an offer from before a restart that lowered max_charge_w, or on its own higher default, could rise past it: 19.00 A per phase on the unit fixture, 19.30 A on the plant. The reserve now runs to the larger of max_charge_w and the site fuse's rating. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
The restart credit compared a charger's sample time, stamped by the charger's own clock (OCPP MeterValues), with the time the site reading arrived on Core's clock. A charger clock 1 s or more behind Core's let a rise sampled after the reading count as already in it, and L2 reached 19.30 A on the third review's plant case. A sample now counts only when stamped evClockAllowance (5 s) before the reading arrived, and the draw is the lowest of that sample and every sample since. noteDraw keeps the charger's samples while the restart window is open. Also tests the max_charge_w half of the rise cap: a 22 kW charger on a 3 x 25 A fuse keeps the reserve up to max_charge_w. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Brings in the current tips of #1910, #1891, #1913, #1923, #1924, #1925 and #1926. The only conflict was #1910's changeset: it now carries #1910's new sentence on an offline battery's relief, and keeps this branch's "a 0.5 A margin" wording, since 0.5 A is no longer the default here. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
…move The SiteFuseSafetyA comment read as if the margin were needed by default; it now says zero is the default and when to set one. The changeset named "the site's total import and export limits", which reads as the hourly import_limit; that limit does not move. It now names the fuse's import and export ceilings. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
A mutation that restored a hidden 0.5 A margin at startup passed every suite. This test pins the value newControlStateFromConfig hands Core. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
At margin 0 Core holds the phases at the 16 A line. Rig s18-16's 0.1 A house step at small_step then lands over the line until Core cuts: on fdfbfec the phase read 16.101 A for 3 s and Core cut the battery 4851 -> 4719 W within 2 s. The criterion "own commands stay inside the rated fuse" counted that stretch as Core's and failed. The owner's rule judges an overage between In and 1.2 x In by the I2t model. The criterion now skips the 10 s after the step, the same gap the minor window already leaves. On the fdfbfec record Core's own commands peak at 16.008 A before the step and 16.005 A after it, inside 16.01 A. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
The 5 s clock allowance let the restart credit count a charger sample taken 5-7 s before the site reading. A car that stopped after that sample (a fast charger applying the 0 A sent while the meter was stale, or the car pausing) still counted, the battery ended the discharge the car's return needed, and L2 reached 21 A on a 16 A fuse when it resumed. Core now judges a sample by when it first arrived on Core's clock. It counts as in the reading only when it arrived evMeterDelay (1 s) before the reading, and no more than one control interval before that. A sample already there when Core began to watch the charger arrived at a time Core does not know, so it never counts. The charger's stamp only tells samples apart, so a charger clock behind Core's no longer matters. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
# Conflicts: # go/cmd/ftw/main.go
At margin 0 the car in s8-60-25 settles at the rating, as the owner's rule says, and the rig's old 1 A hidden margin failed it: 271 s above 24 A against 67 s allowed, with no second over 25 A. siterig/full has the same threshold in overage() (s9, s10, s11), the random invariants and s15bat. Port #1907's judge hunks: s3, s8, s9-s11, s15bat and the invariants now count time over the fuse rating. TestS8JudgesAtTheFuse and #1907's TestInvariantsJudgeAtTheFuse fail on the old judges. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
fix(config): fuse safety_margin_a defaults to 0
fix(control): after a restart the battery credits the car the meter shows
fix(control): the car comes before battery charge
frahlg
added a commit
that referenced
this pull request
Oct 28, 2026
…1913, #1923, #1924, #1925, #1926, #1914) * fix(control): one log of FTW's own EV offers The battery side read a 20 s pool log of EV offers (State.evOffers), while the EV fuse limit keeps each charger's offers for its declared response time, or 180 s when it declares none. After 20 s the battery counted a slow charger's unshown raise as already in the meter and charged into that room; when the car started, a 25 A site read 32.6 A per phase for 3 s. Delete State.evOffers and its two writers. evInMeterW and clampEVBatteryHeadroom read evShownW, each charger's latest offer less what it may not show yet. The hourly peak in stepEVMeterLimit takes each charger's highest offer of the last evSettle from the same log. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): battery fuse guard reads each phase with its direction Delete perPhaseOverageW, perPhaseOverageReadingW and perPhaseReliefW. The battery fuse guard, the fuse saver and the forced discharge read the signed phase currents (phaseCurrentsA, with #1849's sum check and dead zone), count the batteries' own move on each phase, and relieve to the car's working limit, the fuse less max(1 A, safety_margin_a). Item A5 of the stable plan. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): battery waits only for a declared charger response time The first A6 change gave the battery side the EV limit's 180 s guess for every charger that declares no response time. Only Easee Cloud declares one, so on every other charger the battery reserved the car's whole demand on top of a reading that already showed the car, and stopped charging for 3 minutes after each car start or raise. On the #1868 shape (rig s18) battery charge stayed at 0 W until 180 s. evShownW now uses the charger's declared power_max_age_s, and evSettle when it declares none, as master did. Easee Cloud declares 180 s, so the slow-charger case stays fixed. Tests: the slow-charger test now declares 180 s, and a new plant test runs the s18 shape with a fast charger that declares nothing. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): fuse guard reads phases after the hold caps the targets The guard took the phase relief from the original request, then the 30 s fuse hold capped that request and the relief came off again. A charge limited by one phase switched between 1380 W and 0 W on every dispatch. Predict the aggregate and the phases from the held targets instead. The phase reader now takes the meter's raw total from OnlineMeterW, the same reading as its currents, so an offline meter's cached phases drive no relief. The batteries' raw power is read in one helper. dispatch.go keeps its 41 cached telemetry reads. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): car and battery-beside-car work to the fuse rating less safety_margin_a The EV phase limit was In - 1 A, fixed in code. It is now fuseLineA(): In - safety_margin_a, with no floor. A rise moves one step once it fits under the line, a start takes all the room, and battery charge beside a car uses the same line. The hour's import limit keeps its own margins. Starts and per-phase cuts round down to whole charger amps, since chargers round offers to the nearest amp. Step 3 (PR b) of the fuse-at-rating plan (owner rule of 27 Oct). Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): keep covered offers whole and leave battery relief out of EV room Two review findings on the fuse-line change: - A cut rounds to whole charger amps only when a new cut is needed. When cuts on their way cover the overage, the offer stays as it is. Rounding a kept step-table offer took the car 6200 -> 5500 -> 4800 -> 0 W in 3 s on a 0.6 A overage while a 180 s cut travelled. - Dispatch records the discharge the fuse guard adds to each battery, and an EV rise or start does not count it as room. Before, the car rose into the relief and the battery fed it 650 W at the line for as long as the house load stayed. The noisy-line sim test now pins the slow one-step cycle at an exact fit (at most 5 cuts an hour, never a stop) and no moves with part of a step left, instead of allowing 45 moves an hour. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): battery fuse guard reads each phase with its direction Delete perPhaseOverageW, perPhaseOverageReadingW and perPhaseReliefW. The battery fuse guard, the fuse saver and the forced discharge read the signed phase currents (phaseCurrentsA, with #1849's sum check and dead zone), count the batteries' own move on each phase, and relieve to the car's working limit, the fuse less max(1 A, safety_margin_a). Item A5 of the stable plan. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): fuse guard reads phases after the hold caps the targets The guard took the phase relief from the original request, then the 30 s fuse hold capped that request and the relief came off again. A charge limited by one phase switched between 1380 W and 0 W on every dispatch. Predict the aggregate and the phases from the held targets instead. The phase reader now takes the meter's raw total from OnlineMeterW, the same reading as its currents, so an offline meter's cached phases drive no relief. The batteries' raw power is read in one helper. dispatch.go keeps its 41 cached telemetry reads. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): battery relieves to the fuse less safety_margin_a phaseFuseReliefW now reads fuseLineA(), the line the car uses since the EV change, instead of max(1 A, safety_margin_a). There is no floor under the margin: at margin 0 the battery works to the fuse rating. Tests return to the rating where they had moved to the 1 A limit, and a new property test covers In x phases x margin in both directions. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * test(control): re-record golden records at the fuse less safety_margin_a Replayed from stored inputs; only records whose dispatch changed against the parent branch were replaced. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): battery fuse cut lands on the line, not half a margin below applyFuseGuard cut a battery charge or discharge by the overage plus half of safety_margin_a. The guard now predicts from the held targets and keeps its 30 s hold, so the extra cut only parked the phase below the line the user set. Cut by the overage only. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * docs(changeset): name the limit the battery cut lands on The changeset said the phase lands on the fuse less safety_margin_a. On #1891 as it stands, the phase line is the fuse less max(1 A, safety_margin_a), so at the 0.5 A default a 16 A phase settles at 15 A, not 15.5 A. Say what this PR changes, cutting only by the overage, without naming a line that depends on step 4. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(config): fuse safety_margin_a defaults to 0 Core now works to the fuse rating unless a site sets a margin. Every explicit safety_margin_a is kept. A stored value of exactly 0.5 A, the old default, adds one load-time notice and changes nothing. The peak-limit error names the margin only when it is above 0, and the settings field shows 0 with help that says the margin is opt-in. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * docs(changeset): say what the default change moves on its own The changeset said FTW works to the fuse rating unless a site sets a margin. On this PR's base every per-phase line still sits 1 A under the rating; that holds only once #1910 and the step-4 amendment of #1891 land. The changeset now names what this PR changes: the default, and the whole-site import and export limits. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * test(control): relief stays at the line after a PV drop (C3, seed 207533) On a 16 A fuse with no margin the battery holds 3 kW of discharge with L1 at 14.4 A; PV drops 1280 W and L1 reads 16.3 A. The relief must bring L1 to 16 A and keep it there while the reading sits at the line with the battery at its relief power. Without phaseFuseReliefW's own-move count the relief flips between -3214 W and -3005 W on every tick and L1 crosses the rating 13 times; with it, L1 crosses once. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * test(control): phase relief reads each battery live, in the decision's reading The merge of #1876 moved stopPhaseReliefW's live reads into phaseSample.moveW. Pin it: a battery that went offline, moved on to a newer reading or has no reading gives no phase relief. With the cached RawW read #1891 had, the offline and newer-reading cases relieve 2310 W and the no-reading case counts a 2000 W charge from 0 W. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): battery relief holds when the battery's reading lags the meter The phase relief counts the battery's move from its own reading. When that reading lags the meter by a tick, the meter already shows the relief while the reading does not, so the relief came off; on the next tick it went back on top of the reading's catch-up. In the 207533 shape (16 A, margin 0) with a one-tick lag the order ran -3214, -3005, -3422, -3005, ... -5717 W and L1 went back to 16.3 A on every other tick: 13 crossings. A move from the battery's last command (the one it got in the last dispatch) may now not pass the room the meter shows either. That bound only tightens, and a phase already over the line gives it no room, so it never asks for more than to stay at the last command: a battery that falls short of its order does not wind it up. With lag 1 or 2 the order holds -3214 W with L1 at 16.0 A and one crossing, on the PV step. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): a landed EV cut covers nothing later; a raise that no longer fits comes off The site meter now tells Core how much of a charger's offers it already shows. A move shaped like an order landing (every phase alike, or one phase alone for a one-phase car) moves that level toward the latest offer. A cut the meter shows no longer covers an overage that an outside step causes after it, and no longer nets against a raise sent after it. Where a landing and a house step fall in one reading, a cut covers a phase that has risen since only up to the overage it had then. C4: our own rise on its way, as the meter tells it, is judged as the reading it will make. Above 1.2 x In, or over the line on a phase whose heat budget is spent, it comes off on this reading, down to the line. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): a one-phase house move is not the car's cut landing seeOffers kept one shown level for every phase, so a house load moving on one phase alone read as a three-phase cut landing and took the cut's cover off the phase it was sent for. With a 40 s charger Core then stacked a second cut and left L1 2 A under the line for over 2 min. The shown level is now kept per phase: a three-phase order moves every phase alike, and a phase that moves alone moves only its own level. The loadpoint now reports a car it has seen draw on all three phases as CarPhases 3. For such a car a one-phase move is never the car, so a house step on one phase while a raise travels no longer hides the raise, and C4 cuts on that reading. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): a battery charge rise fits each phase before it is sent The battery fuse guard judged a rise from the battery's own reading and the meter's phases, so it took a rise the meter did not show yet as already shown. With the meter a poll behind the battery, a PV surplus that grew each tick stacked rises past the line, then the relief cut them back: 16.4 A on a 16 A fuse and a charge that rose and fell (C2, seeds 207530, 207535). fitBatteryRisesToFuse caps charge above the battery's latest order to (fuseLineA - worst phase - own unshown rises) x V x phases. The unshown rises are the battery's orders of the last evSettle and the chargers' raises, counted as evShownW counts them, so the car comes first. Holding an order is never a rise and the check never cuts; an overage stays with the relief. No margin and no floor: the order ends at the line. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): battery rise check counts slow batteries and direction-less phases A battery order now stays unshown until evSettle after the battery's own reading reaches it, so a battery that ramps slower than evSettle no longer gets a second rise on top of an order the meter cannot show yet. On a meter with phase currents but no phase power while the total exports, a phase counts as export only when the other phases cannot carry the export alone; any other phase counts as import. Before, every phase flipped to export, so a three-phase charge could rise into a phase that imports beside two exporting ones. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): the car comes before battery charge With battery_covers_ev off, dispatch took the car out of the meter reading before the battery decided. The battery then saw the PV the car was using as export and charged from it while the site imported for the car (rig seeds 207535, 207539, 207530: about 10 kW import). The battery now charges only from the surplus the meter shows after the car. Where the house alone has surplus, the battery sees the meter with the car included, and any discharge stops at once, since it would feed the car. A planned PV charge on the energy path takes only the surplus the car leaves; a planned grid purchase keeps its charge. Cover off still never discharges the battery for the car. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): peak shaving drops a running charge for the car Manual peak_shaving gave zero error for any import under the peak limit, so a battery charge that was running when the car started held while the site imported for the car, with battery_covers_ev on or off. When the site imports while the car and the battery both charge, the charge now comes down by the import, to 0 at most. Under the peak limit the battery still never discharges. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): after a restart the battery credits the car the meter shows After a restart, the 0 A orders FTW sent while the meter was stale counted as the EV base the meter shows. With the car still drawing 8.2 kW from before, a new 6.2 kW order then counted as a 9 A rise to come, and the battery was held in discharge for the car (seed 207532). Until a charger's first order of this run can have landed, the battery side now counts the charger's live measured draw as in the reading, never above the latest order and never above the consumption the site meter shows. The car's own limit does not read it. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): credit a found car only from a current charger sample Review of #1926 found two ways the restart credit let the battery end a discharge into room the car's pending rise still needs: - The charger reading counted with no check that it was current. A held reading after a failed poll, or a sample older than the site reading, could show a car that a fast charger had already stopped. The draw now counts only when the last poll succeeded and the charger measured it within one control interval of the site reading. - The consumption bound subtracted the smoothed battery, PV and V2X values, which lag an output that just fell. It now takes the higher of raw and smoothed for each, so the bound stays at or below what the meter shows. New tests pin both, plus the shown-offer subtractions and a window that outlasts evSettle. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * test(control): run the site sim at the new 0 A default margin simFuseSafetyA follows the config default, now 0. fitScenario takes the room under the line and sets the house from simFuseSafetyA, so its exact fit stays twelve whole steps at any margin. "charger's own load balancer" passes at margin 0, so its known line goes. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * docs(changeset): say what margin 0 moves once the fuse stack lands With the stack under it, the default moves the car's and the battery's per-phase line as well as the site totals. 0.5 A stops being the default, so #1910's changeset no longer calls it that. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * test(control): keep the load-balancer bug as a known line above the line At the 0 A default the scenario passes only because the charger's own balancer sits at 25 A, the rating and so the line. The bug is still in Core: a cut comes off an offer the car does not draw. Two known variants keep it tracked and turn red once it is fixed: the stored 0.5 A margin (over 24.5 A for more than 11 s) and a balancer at 25.5 A at margin 0 (over 25 A for more than 11 s). Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): EV room reads battery relief through live telemetry evFuseReliefW read each battery's cached RawW, which survives a driver going offline. It now reads Store.OnlineRawW. A battery with no live reading counts its whole recorded relief, so the car never builds on discharge Core can no longer hold. fuseSaverEarlyExit read each battery's SmoothedW a second time to record relief. It now records against the live snapshot the fuse-saver decision already took (fleetAtLivePower), so it adds no read of its own. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): an offline battery's fuse relief ends after evSettle With no battery online, ComputeDispatch returns before it records relief, so batteryFuseRelief kept its last value and evFuseReliefW counted all of it for as long as the battery stayed offline. The car was held up to the whole relief below the line. The relief now counts in full until the default mode Core sent at the transition can have reached the meter (evSettle), then ends. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): each offline battery's fuse relief ends after evSettle The expiry in 8150b45 ran only when no battery was online. With a second battery online, an offline battery's relief stayed until a recorded dispatch rewrote the map: never while the legacy modes sat in the deadband, and on the first tick when one did record, so the car could rise onto discharge Core ordered a second earlier. Each offline battery now has its own clock: its relief counts whole for evSettle and then ends, on every dispatch path. A battery back online leaves the clock, so its next offline period counts whole again; a test now covers that reset. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): battery phase relief neither pins mixed phases nor winds up The last-command bound held the battery at its last command when one phase sat at the import line and another was over the export line: the guard cut the discharge for the exporting phase and the bound put it back. Now the bound gives way on one side while any phase is over the other side's line, and phaseFuseReliefW's least-over move decides. When the meter does not show the battery's move (a frozen meter, or a worst phase a one-phase battery cannot reach), each tick added the same overage again and the order ran out to the discharge limit. Now the relief toward the worst phase stops at the last command once the batteries' raw power has moved one ampere per phase since the worst phase last moved by half an ampere. One ampere is the step in which P1 meters report phase current. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): battery phase anti-windup stops only when the meter cannot show the move phaseUnresponsive stopped the relief whenever the batteries had moved 690 W and the worst phase had not moved half an ampere. On a live meter that also happens when a load cancels the move (a balanced load starting with the relief step, or a slow rise on the worst phase), and when the battery's reading catches up with an order the meter already showed. The relief then held over the line with no end. Now it stops only when the meter repeats its phases exactly while the batteries moved one ampere per phase, or when another phase moved by twice the balanced share of that move (a battery off the worst phase). The repeat is measured from the reading the meter last changed in, so a meter that freezes on any reading is still caught. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): battery off the worst phase goes back, and a stale reference ends Fourth review of the phase anti-windup (c066892): - The worst phase's reference had no end while that phase sat over the line. A relief that follows a slow drift keeps it there, so the reference stayed while the battery moved hundreds of watts, and a load that later switched off on another phase read as a battery off the worst phase. The relief then held L1 up to 0.49 A over the line with no time limit. The reference now also ends when the worst phase is at or inside the line, or when another phase becomes the worst. - An off-phase verdict no longer holds the last command. The batteries go back to their power when the worst phase last moved: what they moved since did not reach it. A one-phase battery no longer holds its own phase at -17.97 A for the whole overage (and -19.83 A, past 1.2 x In, when PV returns). A false verdict on a balanced battery moves the worst phase by at least one ampere on the next reading, which ends the reference, so it costs one tick instead of an open-ended hold. The verdict holds until the reference ends, so the relief does not go out again once the battery is back. - The frozen-meter test now also compares the meter's total. A P1 meter reports whole amperes, so a live meter can repeat its phases while its total moves; that latched the relief at 1.11 x In. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * test(control): the drift test also wants no verdict on the load change With L1 at the line ending the reference, no off-phase verdict comes when the load on L3 switches off. Without it, the step back still ends the hold, but with L1 at 16.8 and 17.7 A for two ticks; the test now sees that. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * test(control): our battery order's move is not the car's cut landing The guard in seeOffers that stops reading the meter while our battery order moves had no test; removing it left every test green. A battery order that lands and goes back while a cut travels to a 40 s charger now must not lead to a second cut. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * test(control): the car-first discharge stop has its own test Removing the PI path's immediate discharge stop left every named test green; only the golden replay caught it. A peak_shaving loop with battery_covers_ev off, starting from a 2.9 kW discharge while the house alone has surplus, now requires that no order discharges into the car. The comment on the plan back-off said the plan's grid leaves out the car. It counts the car it planned; the comment now says so. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): the battery rise check reads only live battery power fitBatteryRisesToFuse, unshownBatteryW and recordBatteryReadings read the battery's cached RawW, which survives the driver going offline, and added three direct telemetry reads that the repo-hygiene check refuses. They now use Store.OnlineRawW, as phaseSample.moveW does: an offline battery's last value no longer sets the rise base or the shown level. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): judge a raise's landing from the meter's rise C4 counted a raise as landed only when a reading-to-reading move had a charger's shape. A slow ramp, or a house load on another phase that moved in the landing reading, left the whole raise counted as on its way on top of a reading that already held it, and Core cut a raise that fit under the line. The rise still to come now reads the meter's own rise since the raise went out: the smallest across the phases for a three-phase order, the car's phase for a one-phase car. For a three-phase order, a move on one phase alone no longer moves the shown level of a car not yet seen. A load cycling on the phase over the line took the cut's cover off on each drop and never gave it back, so Core cut again and again. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): a car not yet seen may take a raise on one phase The smallest rise across the phases read a one-phase car not yet seen as a raise that had not landed: its phase rose, the other two did not. Core then cut the car from 11040 W to 0 with every phase under the line (field matrix, car1p cases). One phase that has risen alone since the raise went out, the others within half a step, now counts as that car taking the raise, as the shape tracker read it before. The changeset again says what holds: the one-phase house step case is closed for a car seen on three phases. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): judge a one-phase landing reading by reading For a car not yet seen on three phases, a raise counted as landed on one phase only while the other phases stayed within 0.5 A of their reading when the raise went out. That window spans the charger's whole response time, so 0.6 A of house drift on another phase made the full raise count as still to come on top of a reading that already showed it, and Core cut the car with every phase under the line (field matrix with 0.7 A on L2: car1p cut 11100 -> 0 W). Each phase now keeps its rise over the readings in which the other phases moved less than a step (aloneA). A rise of a step or more there may be the car on that phase. Drift between readings, or under a step in the landing reading, no longer hides it; a house load that moves a step or more on another phase in the same reading still does. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): restart credit keeps room for the car's rise to its max After a restart Core does not know the offer in force on the charger, so a car drawing below it may still rise before Core's order lands. The credit now counts only the draw less that possible rise past the latest offer, with the rise measured to the loadpoint's max_charge_w; a charger with no max_charge_w gets no credit. The charger and output reads move into health-gated telemetry accessors (OnlineLowerW, SumOnlineHigherW). Tests cover the raw and smoothed guards, a 10 s OCPP sample cadence on the plant, and the review's car rising under a 16 A offer in force. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * test(control): Charge now landing shown before Core logs its offer Site rig s1-16, s1-25 and s15-25 failed on c9b52c3: the charger answered within a second, and the meter reading that showed the car at 15.9 A came in 7 ms before the tick that first logged the 16 A offer. The reading could not show an offer logged after it, so the landing counted as a raise still to come, 15.9 + 16 A passed 1.2 x In, and Core cut 11,040 W to 5,520 W with 9 A of room on every phase. The same run of the base at 281f9f6, without this branch's commits, fails the same way; #1923's ab02710, merged here in c0a5274, reads the meter's own rise and fixes it. This test pins that rig shape. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): restart credit counts no sample newer than the meter The battery side's restart credit (evFoundDrawW) had two gaps. A charger sample measured after the site reading counted as part of it. A car that rose in that gap was credited for draw the meter did not show yet, and the battery ended its discharge into room the rise had taken. With a 3 s meter, L2 reached 19.30 A. A sample now counts only when measured at or before the site reading. The rise reserve took max_charge_w as the most the unknown offer in force can be. A charger still on an offer from before a restart that lowered max_charge_w, or on its own higher default, could rise past it: 19.00 A per phase on the unit fixture, 19.30 A on the plant. The reserve now runs to the larger of max_charge_w and the site fuse's rating. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): restart credit holds against a charger clock behind Core's The restart credit compared a charger's sample time, stamped by the charger's own clock (OCPP MeterValues), with the time the site reading arrived on Core's clock. A charger clock 1 s or more behind Core's let a rise sampled after the reading count as already in it, and L2 reached 19.30 A on the third review's plant case. A sample now counts only when stamped evClockAllowance (5 s) before the reading arrived, and the draw is the lowest of that sample and every sample since. noteDraw keeps the charger's samples while the restart window is open. Also tests the max_charge_w half of the rise cap: a 22 kW charger on a 3 x 25 A fuse keeps the reserve up to max_charge_w. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * docs(control): the fuse margin is opt-in, and only the fuse ceilings move The SiteFuseSafetyA comment read as if the margin were needed by default; it now says zero is the default and when to set one. The changeset named "the site's total import and export limits", which reads as the hourly import_limit; that limit does not move. It now names the fuse's import and export ceilings. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * test(control): battery beside a minimum-step car holds the fuse line (rig s18-16) On #1910 and #1891 the battery rises beside the car to the working limit, the fuse guard cuts it by the overage plus half of safety_margin_a and holds 30 s, and the battery rises again: it hunts between 15.0 and 15.5 A on a 16 A site. Where it stands when the house moves is chance, which is why rig s18-16 failed 3 of 57 runs on those heads. #1913's cut by the overage only keeps it on the line. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * test(config): an unset fuse margin reaches Core as 0 A mutation that restored a hidden 0.5 A margin at startup passed every suite. This test pins the value newControlStateFromConfig hands Core. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * test(site): s18 judges own commands apart from the house's step At margin 0 Core holds the phases at the 16 A line. Rig s18-16's 0.1 A house step at small_step then lands over the line until Core cuts: on fdfbfec the phase read 16.101 A for 3 s and Core cut the battery 4851 -> 4719 W within 2 s. The criterion "own commands stay inside the rated fuse" counted that stretch as Core's and failed. The owner's rule judges an overage between In and 1.2 x In by the I2t model. The criterion now skips the 10 s after the step, the same gap the minor window already leaves. On the fdfbfec record Core's own commands peak at 16.008 A before the step and 16.005 A after it, inside 16.01 A. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): no cut of an unseen car, no landing from a 1p house move Two regressions against #1913 from the final review. A car the loadpoint has not seen on three phases may draw on one phase Core does not know. The alone rise (aloneA) missed its landing when any other phase moved a step in the same reading, so the whole raise counted as still to come and C4 cut a car with every phase under the line, at most session starts with a 10 s meter. riseAheadA now takes the largest rise for such a car, as for a one-phase car whose phase is not known, and the smallest only once the car is seen on three phases. A one-phase order never knows the car's phase, so a house load moving alone on any phase read as its cut landing and took the cover off a cut still on its way. A one-phase move now counts only on a known car phase. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * fix(control): judge a restart sample by its arrival, not its stamp The 5 s clock allowance let the restart credit count a charger sample taken 5-7 s before the site reading. A car that stopped after that sample (a fast charger applying the 0 A sent while the meter was stale, or the car pausing) still counted, the battery ended the discharge the car's return needed, and L2 reached 21 A on a 16 A fuse when it resumed. Core now judges a sample by when it first arrived on Core's clock. It counts as in the reading only when it arrived evMeterDelay (1 s) before the reading, and no more than one control interval before that. A sample already there when Core began to watch the charger arrived at a time Core does not know, so it never counts. The charger's stamp only tells samples apart, so a charger clock behind Core's no longer matters. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> * test(site): judge overages at the fuse rating, not fuse - 1 A At margin 0 the car in s8-60-25 settles at the rating, as the owner's rule says, and the rig's old 1 A hidden margin failed it: 271 s above 24 A against 67 s allowed, with no second over 25 A. siterig/full has the same threshold in overage() (s9, s10, s11), the random invariants and s15bat. Port #1907's judge hunks: s3, s8, s9-s11, s15bat and the invariants now count time over the fuse rating. TestS8JudgesAtTheFuse and #1907's TestInvariantsJudgeAtTheFuse fail on the old judges. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> --------- Co-authored-by: Claude Opus 5.5 <noreply@anthropic.com>
This file contains hidden or bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Sign up for free
to join this conversation on GitHub.
Already have an account?
Sign in to comment
Add this suggestion to a batch that can be applied as a single commit.This suggestion is invalid because no changes were made to the code.Suggestions cannot be applied while the pull request is closed.Suggestions cannot be applied while viewing a subset of changes.Only one suggestion per line can be applied in a batch.Add this suggestion to a batch that can be applied as a single commit.Applying suggestions on deleted lines is not supported.You must change the existing code in this line in order to create a valid suggestion.Outdated suggestions cannot be applied.This suggestion has been applied or marked resolved.Suggestions cannot be applied from pending reviews.Suggestions cannot be applied on multi-line comments.Suggestions cannot be applied while the pull request is queued to merge.Suggestion cannot be applied right now. Please check back later.
Problem
Item C2 of the 27 October rig triage (section 3, item 2): Core raised battery charge into a phase that was already full.
On master the battery's charge is checked against the total import ceiling only. #1891, lower in this stack, adds a check on each phase, but it measures the rise from the battery's own reading. That fails when the meter's reading is older than the battery's: the battery already reads its last order while the meter still shows it before the move. The guard then takes the order as shown and stacks the next rise on top. The rig's plant shows that lag (207535, 39 s: battery 871 W, L3 still 14.27 A; 40 s: 15.52 A). A charger's raise that the meter does not show yet counts only while the car has a fuse demand (
clampEVBatteryHeadroom).Site rig on c9b52c3 (28 Oct)
siterig/shortfailed s1-16, s1-25 and s15-25 on this branch's c9b52c3 ("holds 95 % of the time"; on 25 A also "no fuse_limit with room to spare"), while #1923 at 53b8aa3 passed all nine. The cause is not this branch's battery check. c9b52c3 held #1923 only up to 281f9f6, before #1923's ab02710. In s1-25 the charger took the 16 A offer within a second, and the meter reading that showed it came in 7 ms before the tick that first logged the offer:A reading cannot show an offer logged after it, so the C4 tracker held the shown current at 0 A. The landing then counted as a raise still to come: 15.9 + 16 A passed 1.2 × In, and Core cut 11,040 W to 5,520 W with 9 A of room on every phase. The car crept back 1 A at a time and held 9,660 W on
fuse_limit. s15-25 cut a one-phase 3,680 W offer to 1,840 W the same way; s1-16 cut to 0 W. The battery covered the house throughout (about −2,090 W), andfitBatteryRisesToFusenever touched the car.I ran the same three scenarios here with the device simulator. #1923's 281f9f6 alone, without this branch's commits, fails s1-25 and s15-25 the same way, with the same log line. This branch's head c0a5274, which merges #1923's ab02710 ("judge a raise's landing from the meter's rise"), passes all three.
Change
fitBatteryRisesToFuseruns right afterapplyFuseGuard. It caps charge above the battery's latest order (its reading before Core's first order) toOwn unshown rises are the battery's latest order less the least the meter may show of the battery (
unshownBatteryW), plus each charger's raise, counted the wayevShownWcounts them (batterySettle: the declared response time, elseevSettle). The car comes first. The least the meter may show is the lowest of the battery's orders over the lastevSettleand of its own readings over that time, the current one included. So an order stays unshown untilevSettleafter the battery reads it, which covers a battery that ramps slower thanevSettle. Core now logs each battery's reading next to its order (batteryReadings).A discharge that the target ends uses room first.
Holding an order is never a rise, and this check never cuts. A phase over the line stays with the relief (
applyFuseGuard,forceFuseDischargeand its heat model), which reads the battery's own power.No margin and no 1 A floor. The working limit is
fuseLineA, In −safety_margin_a, so the order ends at the line. TheevSettlewait for our own rise is an anti-hunting timer at the line, not current held back.The direction of a meter that gives no phase power while the total exports moves into
phaseSample.signedPhasesA.phaseFuseReliefWand the new check both use it. A phase there counts as export only when the other phases' currents, at most V × A of real power each, cannot carry the export alone (tolerance as inphasePowersAddUp). Any other phase may be a load beside exporting phases and counts as import. Before this, every phase flipped to export. Tibber Pulse is such a meter: it emitsl*_aand nol*_w.The battery's own power comes from
Store.OnlineRawW, asphaseSample.moveWreads it, so an offline battery's last value never sets the rise base or the least the meter may show. This keeps the repo-hygiene check "no new direct telemetry reads" green; the first version added three directRawWreads.Merge fallout from fix(control): battery fuse cut lands on the line, not half a margin below #1913: a5's phase anti-windup (
phaseReliefForTargets) calledsignedA, which this branch had folded intosignedPhasesA. It now callssignedPhasesA, so it reads phase direction the same way as the relief and this check.Rig finding (s1, s15): no code change. fix(control): a landed EV cut covers nothing later; a raise that no longer fits comes off #1923's ab02710, merged in c0a5274, fixes it. A new test pins the rig's shape so it cannot come back unseen.
This is #1789's
fitBatteryRisesToFusewithout its 1 A minimum margin, cut down to the rise check. #1789 is not merged or needed.Tests
New in
go/internal/control/battery_rise_phase_test.go, all throughComputeDispatch, on a 16 A fuse with no margin:TestBatteryRiseIntoPhaseOverTheLine: 207530, phases 8.5/10.5/16.04 A, reading 491 W, ask 3350 W, order ≤ 491 WTestBatteryRiseCountsOwnUnshownRise: 207535, phases 13.77/13.97/14.27 A, ask 871 W goes out whole; then the battery reads 871 W, the meter has not shown it, ask 1500 W, order ≤ 12 + (16 − 14.27) × 690 = 1205.7 WTestBatteryRiseClosedLoopStopsAtTheLine: closed loop, the ask grows 300 W a tick, the battery moves one tick late, the meter one tick after the batteryTestBatteryRiseLeavesRoomForUnshownCarRaise: car first, a 6 → 10 A raise not shown yet, L3 at 11 A, battery ask 2000 W → ≤ 690 W, then 690 W and L3 at 16 A once shownclampEVBatteryHeadroom); fails without it: 2000 WTestBatteryRiseMagnitudeOnlyMeter: no phase power, 15.5/8.7/8.7 A, total −1300 W, ask 3000 W → ≤ (16 − 15.5) × 690 = 345 W; then 17.5 A on each phase with −12075 W total, every phase must export, and the whole 3000 W goes outTestBatteryRiseSlowBatteryLaggingMeter: the battery ramps 50 W a tick, the meter shows it two ticks after the battery reads it, 120 ticksThe last two came from review. Each test was run against the code before its fix and failed as shown.
One golden record moved:
early_exit/deadband_per_phase_export_side_quiet(L1 26 A, L2/L3 8 A, no phase power, total −6000 W). L2 and L3 may import there, so the relief's per-phase overage attribution drops from 2300 W to 2070 W: a 10 A charge shift would push them to 18 A, and the relief takes the middle instead. The targets did not change. I edited that one value by hand, since a full re-dump also rewrites unrelated rounding in other families. The plain fix (no flip at all) moved 8seeded_fuserecords and cut charge that soaks up export above the fuse. With the per-phase test, those records do not move.Second check, on the stack as merged on 28 Oct: the reviewer's tests
TestReviewRiseMagnitudeOnlyMeterMixedDirections,TestReviewRiseSlowBatteryLaggingMeterandTestReviewRiseClosedLoopSlowMeterAndSteppass.TestReviewRiseFrozenValuesMeterstill climbs to 3581 W, as expected: C5 (#1921) owns frozen meters. With the live battery reading switched off,TestBatteryRiseSlowBatteryLaggingMeterfails again (order falls 1294 → 1287 W), so theOnlineRawWpath is the one the tests use..github/scripts/check-telemetry-reads.shagainst this PR's base: before,dispatch.go: 40 -> 43; after, none added.go test -race -count=1 ./internal/control/...passes.make verifypasses ("vet + test + build clean"). The Docker steps skipped because no Docker daemon is running here.Rig finding:
TestEVFuseRaiseShownBeforeItsOfferIsLogged(new,ev_fuse_offer_logged_late_test.go) replays the s1/s15 shape throughEVFuseBudget. Each meter reading comes in 7 ms before the tick that reads it, and Core logs the offer one tick after it went out, when the meter already shows the car.Local
TestSite(FTW_SITE=s1-16,s1-25,s15-25), same device simulator pin as the runner:The runner has not run c0a5274 or later yet.
Risk
evSettle(20 s), because Core waits for the meter to show its last rise. Away from the line, nothing changes.Stack and merge order
Stacked on #1923 (
ev-cut-landed-and-unshown), which sits on #1913 → #1891 → #1910 → master. Merge after #1923.#1923's head
8a10b27d(fourth-review fix of its C4 rule) is merged in here (c0a52740). The merge touched onlyev_fuse_budget.goandev_fuse_cut_netting_test.go, with no conflict. On the top of the stack (#1925 at5babe51a),go test -racepasses for./internal/control,./internal/loadpointand./cmd/ftw, and so does the non-race control run with the field matrix.The rig-finding test commit
19d8a298is merged into #1925 (3623603a), with no conflict. Therego test -racepasses for./internal/control,./internal/loadpointand./cmd/ftw. On this head,go test -racefor./internal/controland./cmd/ftwpasses, as domake verifyand the repo-hygiene checks (no planning docs; telemetry reads 133, none added, against both master and #1923).Other open PRs that touch these files: #1914 (margin default 0, a sibling on #1913) changes only the peak-limit error text in
dispatch.go, so there is no overlap. #1921 (frozen meter), #1916 and #1878 (SoC floor) touch other parts ofdispatch.go. #1789 and #1816 are older drafts of the same idea; this PR does not depend on them.🤖 Generated with Claude Code